automatically, and the default Password security and EnerVista security are disabled.
To maximize security, see the UR Family Secure Deployment Guide.
2.2.0.1 EnerVista security
The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to
manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a
substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security
management system is disabled by default to allow the administrator direct access to the EnerVista software after
installation. It is recommended that security be enabled before placing the device in service.
Basic password or enhanced CyberSentry security applies, depending on purchase.
2.2.0.2 Password security
Password security is a basic security feature present by default.
Two levels of password security are provided: command and setting. Use of a password for each level controls whether all
users can enter commands and/or change settings.
Two types of connection security are provided: password entry from local or remote connection. Local access is defined as
access to settings or commands via the front panel interface. This includes both keypad entry and the through a front
panel port. Remote access is defined as access to settings or commands via any rear communications port. This includes
both Ethernet and RS485 connections. These two settings are on by default and apply to all users.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the G60. the remote password is used. If the
connection is to a front panel port, the local password applies. (These two local and remote password settings are not
shown in the figure.)
Password access events are logged in the Event Recorder.