times the TAP setting. This pickup setting is only
exceeded for internal faults.
Restricted Earth-Fault Protection
Apply the REF protection feature to provide sensitive
detection of internal ground faults on grounded wye-con
nected transformer windings and autotransformers. Only
one of the three ABC inputs of Winding 4 is used for
introduction of neutral CT polarizing current. Operating
current is derived from the residual current calculated for
the protected winding. A directional element determines
whether the fault is internal or external. Zero-sequence
current thresholds and selectable CT saturation logic
supervise tripping. One of the Winding 4 inputs is used
for the neutral CT, so a maximum of three winding
inputs may be used for normal differential and overcur
rent protection.
Overcurrent Protection
The SEL-387 has 11 overcurrent elements for each set of
3-phase current inputs, 44 elements total. Nine torque
controlled elements encompass one instantaneous, one
definite-time, and one inverse-time element for each
phase of the negative-sequence and residual currents.
The phase elements operate on the maximum of the
phase currents. The remaining two elements are phase
segregated to assist in phase identification for targeting
purposes or for level sensing type functions. These are
not torque controlled.
Two sets of combined overcurrent elements operate on
the vector sum of the Winding 1 and Winding 2 currents
and the vector sum of the Winding 3 and Winding 4
currents, respectively. The individual currents are scaled
by the appropriate ratio so that the combined current
accurately reflects the primary system current. Inverse
time phase and residual elements are available for each
of the combined currents. These combined elements
offer added flexibility when the relay is applied with
multiple breakers, such as in ring-bus or breaker-and-a
half applications. Different CT ratios are permitted on
the two windings that are summed to create the
combined current. For ideal CTs, these combined
overcurrent functions do not respond to circulating
current passing through both circuit breakers.
The time-overcurrent curves listed in Table 1 have two
reset characteristic choices for each time-overcurrent
element. One choice resets the elements if current drops
below pickup for at least one cycle. The other choice
emulates reset of an electromechanical induction disk
relay