SEL-487E Transformer Protection Relay
High-speed transformer differential
protection for up to seven terminals
• Minimize damage and limit expensive repairs to transformers with
advanced differential protection and three restricted earth fault
(REF) elements.
• Consolidate protection schemes using a combination of differential,
distance, and overcurrent elements suitable for transformer, bus, line,
and feeder protection.
• Simplify engineering and reduce maintenance costs by using a single
device for pad-mounted switchgear applications.
• Benefit from comprehensive substation asset management with
through-fault, thermal, and circuit breaker monitoring.
• Transform and simplify the way you modernize your substation with
SEL Time-Domain Link (TiDL®) or Sampled Values (SV) technologies.
ANSI Number/Acronyms and Functions
16 SEC Access Security (Serial, Ethernet)
21* Phase and Ground Distance
24 Volts/Hertz
25 Synchronism Check
27 Undervoltage
32 Directional Power
46 Current Unbalance
49 IEEE C59.71- and IEC 60255-Compliant Thermal Model
50BF Dual Breaker Failure Overcurrent
50N Neutral Overcurrent
50 Overcurrent (Phase, Zero Sequence, Neg. Seq.)
51N Neutral Time Overcurrent
51 Time Overcurrent (Phase, Zero Sequence, Neg. Seq.)
59 Overvoltage
67 Directional Overcurrent (Phase, Zero Sequence,
Neg. Seq.)
68* Out-of-Step Block
79* Autoreclosing
81 Over-/Underfrequency
85 RIO SEL Mirrored Bits® Communications
87T Transformer Differential (Unrestrained, Restrained,
Neg. Seq.)
87B* Bus Differential (Restrained)
Additional Functions
BRM Breaker Wear Monitor
DFR Event Reports
ENV SEL-2600 RTD Module*
HBL Harmonic Blocking
HMI Operator Interface
LDP Load Data Profiling
LGC SELogic® Control Equations
MET High-Accuracy Metering
PMU Synchrophasors
REF Restricted Earth Fault
RTU Remote Terminal Unit
SBM Station Battery Monitor
SER Sequential Events Recorder
SIP Software-Invertible Polarities
SV IEC 61850-9-2 or IEC 61869-9 Sampled Values*†
TiDL Time-Domain Link Technology*†
TRM Transformer Monitor
Key Features
Multiwinding Protection
Configure the SEL-487E Transformer Protection Relay
for differential protection in transformer applications
using up to seven restraint currents. This includes single
transformers with tertiary windings. Three independent
REF elements offer protection for grounded-wye windings.
You can invert individual or grouped CT or PT polarities to
account for field wiring or protection zone changes.
High-Speed, Adaptive Differential Protection
Implement a two-stage slope that automatically adapts
to internal or external fault conditions, even with CT
saturation and heavily distorted waveforms, for fast,
sensitive, dependable, and secure differential protection.
The adaptive differential element responds to internal
fault conditions in less than 1.5 cycles. The SEL-487E
includes two differential elements: one intended for
protecting transformers and the other intended for
protecting busbar applications.
Diverse Applications
Simultaneously protect transformers, buses, lines,
and feeders in centralized protection applications.
Protect large transformers and autotransformers with
breaker-and-a-half high- and low-side connections. You
can configure the SEL-487E for a typical two-winding
transformer application and use the remaining three
phase current inputs for feeder or line backup protection.
Sensitive Turn-to-Turn Fault Detection
The patented negative-sequence differential element
detects turn-to-turn faults involving as little as
2 percent of the total winding, helping avoid catastrophic
transformer failure.
Configurable Distance Protection
Apply up to four zones of phase and ground distance
protection using mho or quadrilateral characteristics. The
SEL-487E distance elements can be applied as primary
transmission line or backup transformer protection.
Dependable Backup Protection
Provide backup protection with phase, negative
sequence, and zero-sequence overcurrent elements and
21 configurable time overcurrent elements. By setting up
breaker failure protection with subsidence detection, you
can rapidly detect breaker failure and minimize system
coordination times.
Generator Step-Up Transformer Protection
Protect generator step-up (GSU) transformers with built-in
temperature measurement (requires the SEL-2600 RTD
Module) that monitors generator and transformer winding
temperatures simultaneously. In addition, the volts/hertz
element provides overexcitation protection for loaded and
unloaded generator operating conditions. By setting the
directional power elements to detect forward and reverse
power flow conditions, you can monitor and protect the
GSU transformer in prime-power, standby, base-load, and
peak-shaving applications. Built-in synchronism-check
elements verify the generator breaker synchronization.
Advanced Asset Monitoring
Track transformer wear with through-fault and thermal
monitoring. Advanced breaker monitoring reduces
inefficient and costly breaker maintenance. You can also
monitor substation dc power systems for out-of-tolerance
voltage levels or excessive voltage ripple.
Station Phasor Measurement Unit (PMU)
Improve power quality with IEEE C37.118 synchrophasors
from all 18 analog channels (6 voltage and 18 current
sources) in your relay. Using synchrophasors over serial or