➤ Eight Programmable Pushbuttons Each With Two
Tricolor LEDs
➤ Advanced SELOGIC Control Equations
➤ 32 Programmable Display Messages
➤ MIRRORED BITS Communications
➤ Breaker Wear Monitor
➤ Event Messenger Compatible
➤ Front-Panel HMI With 5-Inch, Color,
800 x 480 Pixel Touchscreen Display
Instantaneous Overcurrent Elements
5
Combined Overcurrent Elements
The following instantaneous overcurrent elements are
provided in the SEL-700BT as shown in Table 2. All
instantaneous overcurrent elements provide torque
control and definite-time delay settings.
➤ As many as six instantaneous phase overcurrent
elements (50P) with peak detection algorithms to
enhance element sensitivity during high-fault
current conditions where severe CT saturation may
occur.
➤ As many as two instantaneous negative-sequence
overcurrent (50Q) elements.
➤ As many as two residual-ground instantaneous
overcurrent (50G) elements. These elements use
calculated residual (3I0) current levels.
➤ As many as two neutral instantaneous overcurrent
elements (50N).
Directional Instantaneous Overcurrent
Elements
The following directional overcurrent elements are
available in the SEL-700BT with directional control (see
Table 2).
➤ As many as two directional phase overcurrent
elements (67P).
➤ As many as two directional negative-sequence
overcurrent elements (67Q).
➤ As many as two directional residual-ground
overcurrent elements (67G).
Time-Overcurrent Elements
The SEL-700BT provides the time-overcurrent elements
listed in Table 2. These time-overcurrent elements
support the IEC and US (IEEE) time-overcurrent
characteristics. Electromechanical disc reset capabilities
are provided for all time-overcurrent elements.
➤ As many as two phase time-overcurrent (51P)
elements are provided. These phase elements
operate on the maximum of phase currents. One
51P element has directional control.
➤ As many as two negative-sequence time
overcurrent (51Q) elements are provided. These
elements operate on the calculated negative
sequence current for each set of three-phase inputs.
One 51Q element has directional control.
➤ As many as two residual time-overcurrent (51G)
elements are provided. These elements use
calculated residual (3I0) current levels. Both 51G
elements have directional control.
➤ One neutral time-overcurrent (51N) element is
provided with directional control.
The combined overcurrent elements can be used for
equipment connected to a ring-bus or breaker and one
half systems. Each combined winding current supports
two levels of instantaneous overcurrent (50P) elements,
one time overcurrent (51P) element, two instantaneous
residual overcurrent (50G) elements, and one residual
time overcurrent (51G) element.
Synchronism Check Elements
(25X and 25Y)
The SEL-700BT has a synchronism-check function on
both the X-side and the Y-side that provides the closing
window for the breaker when connecting to the utility
system.
Synchroscope
The touchscreen display comes with a built-in
Synchroscope application in the Monitor folder, which
displays a graphical representation of the phasor differ
ence between the bus and the feeder, as shown in