DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

The Versatility of Signal Interface Instruments

From:automation | Author:H | Time :2024-11-27 | 120 Browse: | Share:

The Versatility of Signal Interface Instruments

Whether they are called “signal isolators,” “signal converters” or “signal interfaces,” these useful process instruments solve important ground loop and signal conversion challenges every day. Just as important, they are called on to do much more. They can be used to share, split, boost, protect, step down, linearize, and even digitize process signals. This article explains many of the important ways these signal interface instruments can be used, and what to look for when specifying them. 


Signal isolation 

The need for signal isolation began to flourish in the 1960s and continues today. Electronic transmitters were quickly replacing their pneumatic predecessors because of cost, installation, maintenance, and performance advantages. However, it was soon discovered that when 4-20 mA (or other dc) signal wires have paths to ground at both ends of the loop, problems are likely to occur. 

The loop in question may be as simple as a differential pressure (DP) transmitter sending a 4-20 mA measurement to a receiver such as a proportional-integral-derivative (PID) Controller. But when the voltages at the two ground points are different, a circulating, closed current (I) path is formed by the copper wires used for the 4-20 mA signal and ground (Figure 1). When this happens, an additional and unpredictable amount of current is introduced into the loop, which distorts the true measurement. This current path, known as a ”ground loop,” is a common source of signal inaccuracies. 

A ground loop forms when three conditions are present:
1. There are two grounds.
2. The grounds are at different potentials.
3. There is a galvanic path between the grounds. 

Figure 1: A ground loop forms when the voltages at two ground points in a loop are at different potentials.


To remove the ground loop, any one of these three conditions must be eliminated. The challenge is, the first and second conditions are not plausible candidates for elimination because the number of grounds cannot always be controlled, and it is often impossible to just “lift” a ground. 

The ground may be required for the safe operation of an electronic device. It’s also possible that the ground exists because the instrument is in physical contact with the process, which, in turn, is in physical contact with the ground. From a practical standpoint, one cannot reach into the earth and regulate the voltage at these permanent ground points. 

Figure 2: A signal isolator “breaks” the galvanic path between two grounds.

Using a signal isolator to “break” the galvanic path between the two grounds (Figure 2) can correct this situation. When the conductive path between the differential voltages is broken, a current cannot form. Even though there are two grounds and different voltages at each ground, there is no current flow. The ground loop has been eliminated.



Breaking the galvanic path

The duty of an isolator is to break the galvanic path between circuits that are tied or “grounded” to different potentials. A galvanic path is defined as a path in which there is a direct electrical connection between two or more electrical circuits that allow current to flow. Breaking this galvanic path can be accomplished by electromagnetic, optic, capacitive, inductive and even acoustic methods. 

With most industrial measuring equipment, the two prevalent methods chosen for galvanic isolation are optical and transformer.

Optical isolation. Optical isolation uses light to transfer a signal between elements of a circuit. The opto-coupler or opto-isolator is usually self-contained in a small compact module that can be easily mounted on a circuit board. 

An optical isolation circuit is comprised of two basic parts: a light source (usually an LED acting as the transmitter) and a photo-sensitive detector (usually a phototransistor) acting as the receiver. The output signal of the opto-coupler is proportional to the light intensity of the source. The insulating air gap between the LED and the phototransistor serves as the galvanic separation between the circuits, thus providing the desired isolation between two circuits at different potentials. 

Optical isolation has better common-mode noise rejection, is usually seen in digital circuits, is not frequency sensitive, is smaller, and can sometimes provide higher levels of isolation than transformer isolation. 

Transformer isolation. Transformer isolation, often referred to as electromagnetic isolation, uses a transformer to electromagnetically couple the desired signal across an air gap or non-conductive isolation gap. The electromagnetic field intensity is proportional to the input signal applied to the transformer. Transformers are very efficient and fast at transferring ac signals. Since many process control signals are dc, they must be electrically “chopped” into an ac signal so they can pass across the transformer. Once passed, they must be rectified and amplified back into the desired dc signal output. 


Two-way versus three-way isolation 

Two common terms used within the process control industry with respect to isolation are two-way and three-way isolation. Isolation specifications often detail what the isolation levels are from input to output. This is often referred to as two-way (input-to-output) isolation and is the appropriate specification for a two-wire transmitter since it is powered from either its input or output terminals. 

However, many manufacturers fail to mention or outline the isolation details when their isolators are four-wire (line/mains-powered) and require 24 Vdc, 110 Vac or 220 Vac to operate its circuits. In these instances, ensure that an isolator has full three-way isolation. 

Three-way isolation is defined as input-to-output, power-to-input, and power-to-output isolation. If the isolator is powered by a dc supply, many manufacturers use common signal wires between the output and the power input. In these situations, there could be problems with common mode noise or a failing switching power supply that could create unwanted output signal errors. 


Signal conversion 

Signal converters are used to get legacy signal types, such as 10-50 mA, converted to a standard 4-20 mA or some other signal type that is compatible with a particular receiving device (Figure 3).

Figure 3: Signal converters convert one signal type to another that is compatible with a particular receiving device.


Fixed range or configurable signal converters? 

There are three approaches to performing signal conversion:

1. One is to use fixed-ranged signal converters designed and built specifically for the conversion need such as 0-10 V in and 4-20 mA out. The advantage is simplicity, as there is nothing to configure. Just mount and wire the device, and you’re up and running. The disadvantage is lack of flexibility. If the application changes, the fixed-range signal converter is not easily, or simply can’t be, modified to accommodate signal types other than what was originally specified. 

2. Another solution is to use a signal converter that has switches or jumpers to select or re-range the input and/or output. There’s a little more work to make the instrument suitable to the application, but a configurable signal interface is more flexible in addressing multiple applications or changing signal conversion needs. Fewer instruments need to be kept in stock. 

3. The third approach is to use a signal converter that is PC-configurable to provide similar application flexibility, plus some performance enhancements. Usually, the rangeability has more resolution, and there are no potentiometers, jumpers or switches that can be easily changed without authorization. 


Step down dangerous ac signals 

Normally, when one thinks of isolators, they think of solving a problem at the instrument control level layer, typically dealing with dc signals. However, very common applications use a signal converter to monitor, trend, or alarm on ac signals. With preventive maintenance budgets shrinking, companies are closely monitoring expensive and critical equipment purchases. Pumps, motors and fans are quick to fall into this category. 

Since much of this equipment is powered with ac voltage and high levels of current, a current transformer (CT) is installed. The role of a CT is two-fold. First, a CT is used to step down the current to a level that can easily be monitored. Second, safety is always a large concern. No one, especially a plant safety manager, wants technicians used to working with 24 Vdc grabbing hold of 5 amps ac. 

A signal converter with an ac current input is used in these situations to convert and isolate a “high level” ac signal to a lower level 4-20 mA dc signal. The secondary of the CT, which is almost always 0-5 amps, can be directly wired into the input of the signal converter. As an added measure of protection, some manufacturers offer an externally mounted CT option that makes use of a “mini-CT” to step the 0-5 amps ac down to 0-5 mA ac. This signal interface with the much lower ac signal is now very safe to wire and handle. 


Digital signal conversion 

An emerging method of converting signals ignores all the previous rules laid down by analog isolators and converters. This new “digital signal conversion” is becoming especially popular in locations where power is sparse, and wires are few. A common application deals with digitally converting or “mapping” HART digital signals to the popular MODBUS RTU serial communications protocol (Figure 4). 

Figure 4: Digital signal conversion is becoming a popular strategy where power is sparse and wires are few.

Many programmable logic controllers  (PLCs) and distributed control systems (DCSs)—new and old—accept MODBUS RTU, so this becomes a quick and efficient way to get HART data into a control system that doesn’t natively accept HART. HART devices and HART signals contain multiple pieces of data per instrument.

Therefore, a HART-to-MODBUS converter can be an effective tool when additional process variable and diagnostic data from field instruments are desired. 

On the data acquisition side, a remote terminal unit (RTU) or supervisory control and data acquisition (SCADA) system that supports MODBUS RTU can be found. A HART-to-MODBUS converter (Figure 4) represents a new trend in digital signal conversion. Not only does the converter gather all of the HART data from the HART transmitters and convert it to MODBUS, but it also powers the HART bus using its 9-24 Vdc power input. This allows any MODBUS RTU-enabled RTU or SCADA system to monitor any HART variable from any of the up to 16 HART field devices on a multidrop HART network. 



Powering an isolator/converter 

A signal isolator/converter can be four-wire (line/mains powered) or two-wire (loop-powered). Selecting the correct type of isolator and power configuration depends on the application. 

Four-wire signal isolators. A four-wire isolator/converter is used when the instrument output must be voltage (i.e., 0-10 V), zero-based (i.e., 0-20 mA), or bipolar (i.e., -10 V to +10 V). A four-wire isolator usually sources its current output and typically has a drive capacity of around 1,000 to 1,200 ohms. Some isolators will drive up to 1,800 ohms. 

Two-wire signal isolators. A two-wire isolator/converter typically costs less to install than a four-wire unit because power wires don’t have to be run to the unit. Loop-powered instruments can be powered from the loop either on their output side or their input side. 

Isolators/converters that are output loop-powered are powered just like any other two-wire DP, pressure, or temperature transmitter. The output always has to be some form of 4-20 mA, but signal conversion (such as 1-5 V to 4-20 mA) and split ranging, like a 4-12 mA range, can still be performed. When powered with 24 V, these isolators typically drive into 600 ohms. 

A two-wire, input loop-powered isolator is a great solution when applied correctly. The beauty of this isolator is its overall simplicity, with integration into the loop nearly seamless. For example, refer to Figure 5 and imagine that the isolator was not originally implemented. Soon after startup, it is discovered that isolation is required for the process. The good news is that to install this type of isolator, just break the loop where convenient and insert the isolator. A simple solution, wiring changes and installation costs are minimal. 

Figure 5: Two-wire, input loop-powered signal isolator/converter.

However, it’s also simple to misapply an input loop-powered isolator. Certain “rules” must be followed. An input loop-powered isolator is powered from the four-wire transmitter in the field. The transmitter’s 4-20 mA output and its compliance voltage must power the isolator electronics and the isolator’s output. Because loop power is limited, the isolator’s output load is held to 250 ohms. The receiver’s input impedance can be anywhere from 0 to 250 ohms, and it should be a fixed load. In addition, there can be no voltage on the output of the isolator. 

To run the isolator electronics, the isolator consumes 5.5 V from the loop or, to put it another way, the isolator itself looks like a 275 ohm load on the transmitter. To calculate the total burden on the transmitter, add the isolator load to the 275 ohm load. The total load could then be as high as 525 ohms plus wire resistance. That is not usually a challenge for a four-wire transmitter, but it can be for a loop-powered transmitter limited to 600 ohms. 


  • Honeywell 30735863-502 - SWITCH
  • Honeywell TK-CCR014 - REDUNDANT NET INTERFACE NEW ORIGINAL FREE EXPEDITED SHIPPING/
  • Honeywell 51403165-400 - new 51403165400/
  • Honeywell318-049-001 - "100 Batteries(Japan Liion2Ah14.8Wh)INTERMEC/ PR2,PR3 P/N.:."
  • Honeywell FC-PSU-UNI2450U - Power Supply
  • Honeywell 965-0676-010 - WARNING COMPUTER SV
  • Honeywell 51403519-160 - module
  • Honeywell 107843 - HOUSING CARBON FILE P/N NE COND # 11438 (4)
  • Honeywell VR434VA5009-1000 - Brand new in box Condensing boiler valve DHL fast shipping
  • Honeywell SPXCDALMFX - plc new FREE EXPEDITED SHIPPING/
  • Honeywell BCM-PWS - BCM-ETH BCM-MS/TP BCM-MS/TP Network controller setFedEx or DHL
  • Honeywell YSTR12D-22/C/-2J0DFA/BE/400/T/-CM.HO.TG.SB.SM,ZS,F1,LP,/FX/,1C-BT - UNMP
  • Honeywell IWS-1603-HW - 90-250VAC 1.0A UNMP
  • Honeywell 51304386-150 - MEASUREX Factory Packed
  • Honeywell CC-IP0101 - Profibus Gateway Module
  • Honeywell CC-PFB401 - / CCPFB401 (NEW IN BOX)
  • Honeywell 50071726 - St 800 Series Pressure Transmitter Remote Diaphragm 11-42VDC
  • Honeywell 621-2150 - / 6212150 (NEW NO BOX)
  • Honeywell 80360206-001 - USED YAMATAKE CLI BOARD
  • Honeywell BMDX001A-001 - ACCURAY / BOARD BMDX001A001
  • Honeywell XCL8010A - New CPU Controller.
  • Honeywell PGM-7320 - 1PCS NEW Rae Systems MiniRAE 3000 Portable VOC Monitor#XR
  • Honeywell BK-G40 - U65 *FULL INSTALLATION* Gas Meter 3?± Inlet/Outlet Spool NEW UNUSED
  • Honeywell DM106-0-B-00-0-R-1-00000-000-E0 - DPR100 250V NSNP
  • Honeywell KFD840 - PRIMARY FLIGHT DISPLAY CORE PN: 066-01206-0104
  • Honeywell 51401914-100 - 51400996-100
  • Honeywell TK-PRS021 - Module Via FEDEX/DHL
  • Honeywell C7012A1145 - 1PC New UV Flame Detector Expedited Shipping
  • Honeywell OV210 - Baxter Bakery Oven Igition Control. For DRO. 00-616973 NEW
  • Honeywell 51304431-125 - 1PC New /51304431125 1 year warranty#XR
  • Honeywell QPP-0002 - Quad Processor Module / 5 Vdc / Massima 1.2A/24Vdc/max.25mA
  • Honeywell QPP-0002 - Quad Processor Module / 5Vdc / Max. 1.2A/24Vdc/max.25mA
  • Honeywell 8C-PCNT02 - 514543363-275 module
  • Honeywell DPCB21010002 - Tata Printed Circuit Board
  • Honeywell DPCB21010002 - Tata Printed Circuit Board Rev: 0
  • Honeywell 001649-M5T028 - Tata Printed Circuit Board Rev: 0
  • Honeywell YSTD924-(J2A)-00000-FF,W3,TP,TG,SS - NSFS
  • Honeywell XF523-A - / XF523A (NEW IN BOX)
  • Honeywell TK-PRS021 - NEW IN STOCK ship by UPS
  • Honeywell 2MLR-AC22 - " 2mlr-dbsf,2mlf-ad4s,2mlf-dc4s,2mlr-ac22 Rack"
  • Honeywell 9436610 - MEASUREX NSMP
  • Honeywell RT10A-L0N-18C12S0E - RT10A.WLAN.IN.6803.CAM.STD.GMS
  • Honeywell 51305896-200 - P:C1 Rev D Nim Modem - FAST SHIP BY Fedex
  • Honeywell TK-FTEB01 - PCL module Brand New Fast Shipping By DHL
  • Honeywell 8694500 - Measurex Control Processor Module
  • Honeywell DR4500 - Truline and DR4300 Circular Chart Recorder
  • Honeywell EC-7850-A-1122 - / EC7850A1122 (NEW IN BOX)
  • Honeywell XNX-UTAI-RNNNN - NEW Universal transmitter DHL Fast delivery
  • Honeywell SPXCDALMFX - plc new One Year Warranty #
  • Honeywell TC-RPFM01 - C200 system card brand new Fast Shipping
  • Honeywell 51196655-100 - NSMP
  • Honeywell XCL8010A - / XCL8010A (USED TESTED CLEANED)
  • Honeywell 51198801-100 - NEW CPU INTERFACE BOARD UPGRADE KIT UPIU 51306154-100
  • Honeywell 84795 - Sputtering Target 5N Al5Cu 7830x11640x13050
  • Honeywell W7704A-1004 - / W7704A1004 (USED TESTED CLEANED)
  • Honeywell RA890G1229 - FOR FSG UV Protectorelay /PL3
  • Honeywell KFS-599B - 071-01576-0101 UHF Communication Control with Mods (28V)
  • Honeywell WPC2000 - WINTRISS 9683001 WINTRISS CLUTCH/BRAKE CONTROL *NO KEYS*
  • Honeywell C7012E1112 - 1PC C7012E 1112 Burner Detector New In Box Expedited Ship #
  • Honeywell 8C-TCNTA1 - C300 system card brand new Fast Shipping
  • Honeywell ANT67A - TCAS Antenna 071-01548-0100 w/ October 2023 Repaired 8130
  • Honeywell CC-PDIS01 - PLC Module Brand New Fast Shipping FedEx or DHL
  • Honeywell R7247C1001 - 2-4SECS NSMP
  • Honeywell ALI-80A - Collins Encoding Altimeter - P/N 622-3975-011 - Tested 8130 -Serviceable
  • Honeywell 001650-M5T028 - Tata Relay Circuit Board
  • Honeywell 51196886-100 - PC BOARDS (126201 - NEW)
  • Honeywell J-HAM10 - NSNP
  • Honeywell TC-IXL062 - 1PCS module New fedex or DHL
  • Honeywell 114M4910-6 - PISTON ASSY PN NS COND 12037
  • Honeywell C7076 - 191002B Sensor Amplifier 220/240v
  • Honeywell 510STR12D21A-B77P - NSNP
  • Honeywell 51304511-200 - Module Nim Modem Via FEDEX/DHL
  • Honeywell IC-600 - Integrated Communication Unit RCZ851E 7510700-806 Removed Working
  • Honeywell TC-IAH161 - 1PC NEW REDUNDANT NET INTERFACE one year warranty#XR
  • Honeywell 2001-100-150-126-280-20-100000 - REMAN
  • Honeywell QPP-0001 - FSC QUAD PROCESSOR PACK QPP MODULE CC V1.4
  • Honeywell 30734558-001 - / 30734558001 (USED TESTED CLEANED)
  • Honeywell STD830-E1HS4AS-1-A-ADB-11C-B-21A0-00-0000 - 4500PSI NSNP
  • Honeywell 900C75-0560 - NEW HC900 Controller module FedEx DHL Fast delivery
  • Honeywell BL870 - Bezel 7014331-921 w/ October 2018 Repaired 8130
  • Honeywell STG77L-E1G000-1-A-CDC-11S-A-20A0-00-0000 - NSMP
  • Honeywell FF-SB14E12K-S2 - / FFSB14E12KS2 (USED TESTED CLEANED)
  • Honeywell 51198685-100 - "Rev. A, 140519-2-LF Power Supply Module 10A 100-240 VAC"
  • Honeywell 942-M96-M - plc new FREE EXPEDITED SHIPPING
  • Honeywell TK-IAH161 - 1PC New ANALOG INPUT TKIAH161 Expedited Shipping
  • Honeywell C7061F2001 - 1PC UV Flame Detector New In Box #
  • Honeywell 0190-20139/D - ONE Sputtering Coating Disc 4N5TI NEW
  • Honeywell 82408667-001 - NEW MEMORY BOARD ROM/RAM 82408667001
  • Honeywell C7012A1194 - NEW IN STOCK ship by UPS
  • Honeywell TK-FTEB01 - NEW IN BOX FTE BRIDGE Brand New Fast Shipping FedEx or DHL
  • Honeywell RA890G1344 - 1pc NEW Combustion Controller DHL or FedEX
  • Honeywell DH-AP-1/ - Miller 3 Workers per System 4-3/4 Ft Overall H Post Anchor
  • Honeywell TCOAV081 - NEW IN BOX ANALOG OUTPUT EXPEDITED SHIPPING
  • Honeywell W7704D1016 - Control Unit
  • Honeywell 9437710 - USED PIDP MEASUREX / 09437710-RP MODULE REV D STOCK 1603
  • Honeywell 51403165-400 - Brand new industrial computer Fast FedEx or DHL
  • Honeywell DC3200-EE-000R-240-00000-E0-0 - New DHL FastShip
  • Honeywell 51305348-100 - / 51305348100 (USED TESTED CLEANED)
  • Honeywell CC-PAIX01 - 1PCS Brand New Expedited Shipping
  • Honeywell 51305890-175 - REV B NEW
  • Honeywell XCL8010A - NEW IN STOCK ship by UPS
  • Honeywell D18-UU0000-D00000-0000-2-0000-00-E - CHART RECORDER CHART RECORDER
  • Honeywell TC-IAH161 - ANALOG INPUT NEW 1PCS
  • Honeywell 10020/1/2 - / 1002012 (NEW IN BOX)
  • Honeywell DC3200-EE-000R-240-00000-E0-0 - Digital Controller UPS Express New Zy
  • Honeywell 2MLR-CPUH/F - 1PC NEW EXPRESS P3097E YL/
  • Honeywell 9437710 - USED PIDP MEASUREX MODULE REV D STOCK 1608
  • Honeywell CC-PAIX02 - Fast Shipping
  • Honeywell DPR500 - Brand New Fast Shipping By DHL
  • Honeywell 10004/I/F - / 10004IF (USED TESTED CLEANED)
  • Honeywell C7012E1112 - 1PCS New in box UV Flame Detector
  • Honeywell HPTZ-361W - Brand New Expedited Shipping
  • Honeywell 10006/2/1 - / 1000621 (NEW NO BOX)
  • Honeywell SC-PCMX01 - 1PC NEW RTU2020 51307195-175 SHIP EXPRESS #P2254E YL
  • Honeywell X-NPMS(H) - 1PC Network Paging Console Fire Equipment Brand New Via DHL
  • Honeywell C7012E1112 - 1Pcs new Explosion-proof flame detector
  • Honeywell 0190-20139/D - 4N5TI Sputtering Coating Disc
  • Honeywell RM7840E1016 - SER. 3 REV. 4141 120VAC 15SEC NSMP
  • Honeywell C7012E1120 - Brand new Fast shipping via DHL
  • Honeywell MU-PSIM11 - 1PCS card Brand New Expedited Shipping
  • Honeywell DPR500 - Brand New Fast Shipping FedEx or DHL
  • Honeywell 2108B2101N - Gas Detector OPTIMA PLUS-UL-HC
  • Honeywell 51403578-100 - Rev F Operator Keyboard 1x Ship By DHL/FEDEX/UPS
  • Honeywell 51403165-400 - ONE industrial computer
  • Honeywell FF-SB12E/R02E-S2/3 - Securitram Pair FF-SB12E02E-S2/3 + FF-SB12R02E-S2/3
  • Honeywell STR12D-21A-1B0AFAAA21BP-1C,DE,MB+XXXX - NSMP
  • Honeywell STR17G-11A-1K0AFCAA21A0-A1,CC,HC,MB,NE,TG,W2,3H+XXXX - NSMP
  • Honeywell TK-FTEB01 - "FTE connection module , 51309512-175 Fast Shipping"