be put into service without warning.
Internal Tracking Between DECS-200 Operating Modes
In applications using a single DECS-200. the DECS-200 can be programmed so that the inactive
operating modes track the active operating mode. Operating modes include AVR, FCR, PF, and var. If
the excitation system is normally operating on-line in Internal mode and a loss of sensing occurs, the
DECS-200 could be transferred to manual (FCR) mode where the loss of sensing has no impact on the
exciter's ability to maintain proper excitation levels. While performing routine testing of the DECS-200 in
backup mode, the internal tracking feature allows a transfer to an inactive mode that will result in no
disturbance to the system.
Communication With a PC
Communication between the DECS-200 (front panel RS-232 port) and a PC is possible through
BESTCOMS software. BESTCOMS enables fast and easy programming of setpoints and ranges and
allows for step changes to facilitate proper stability settings. BESTCOMS also provides easy start and
stop control and operator adjustment of the excitation system with real-time metering. The software
catalog number is BESTCOMS-DECS200. BESTCOMS is provided with the DECS-200 as part of the
software/manual package.

Sample Style Number
The style number identification chart (Figure 1-2) defines the electrical characteristics and operational
features included in the DECS-200. For example, if the style number were DECS-200-1L, the device
would have the following characteristics and features.
DECS-200 -- Digital Excitation Control System
1 --- Internal autotracking/transfer
L --- 24/48 Vdc control power supply
SPECIFICATIONS
DECS-200 electrical and physical characteristics are listed in the following paragraphs.
Control Power
Input Voltage
DC Input: 16 to 60 Vdc (style XL) or 90 to 150 Vdc (style XC)
AC Input: 85 to 132 Vac, 50/60 Hz (style XC only)
Note: Isolation transformer for ac input is required when dual control
power sources are used.
Burden
DC Input: 30 W
AC Input: 50 VA
Terminals
DC Input: B7 (+), B8 (–)
AC Input: B9 (L), B10 (N) (style XC only)
Operating Power
To achieve the proper DECS-200 output voltage, the appropriate operating power input voltage must be
provided.
32 Vdc PWM Output
Nominal: 60 Vac
Operating Range: 56 to 70 Vac, ±10%
Frequency Range: 50 to 500 Hz
Configuration: 1-phase or 3-phase
Burden: 780 VA
63 Vdc PWM Output
Nominal: 120 Vac
Operating Range: 100 to 139 Vac, ±10%
Frequency Range: 50 to 500 Hz
Configuration: 1-phase or 3-phase
Burden: 1.570 VA
125 Vdc PWM Output
Nominal: 240 Vac
Operating Range: 190 to 277 Vac, ±10%
Frequency Range: 50 to 500 Hz
Configuration: 1-phase or 3-phase
Burden: 3.070 VA
Voltage Buildup
From a minimum of 3 Vac
Terminals
C2 (A-phase), C3 (B-phase), C4 (C-phase)
Sample Style Number
The style number identification chart (Figure 1-2) defines the electrical characteristics and operational
features included in the DECS-200. For example, if the style number were DECS-200-1L, the device
would have the following characteristics and features.
DECS-200 -- Digital Excitation Control System
1 --- Internal autotracking/transfer
L --- 24/48 Vdc control power supply
SPECIFICATIONS
DECS-200 electrical and physical characteristics are listed in the following paragraphs.
Control Power
Input Voltage
DC Input: 16 to 60 Vdc (style XL) or 90 to 150 Vdc (style XC)
AC Input: 85 to 132 Vac, 50/60 Hz (style XC only)
Note: Isolation transformer for ac input is required when dual control
power sources are used.
Burden
DC Input: 30 W
AC Input: 50 VA
Terminals
DC Input: B7 (+), B8 (–)
AC Input: B9 (L), B10 (N) (style XC only)
Operating Power
To achieve the proper DECS-200 output voltage, the appropriate operating power input voltage must be
provided.
32 Vdc PWM Output
Nominal: 60 Vac
Operating Range: 56 to 70 Vac, ±10%
Frequency Range: 50 to 500 Hz
Configuration: 1-phase or 3-phase
Burden: 780 VA
63 Vdc PWM Output
Nominal: 120 Vac
Operating Range: 100 to 139 Vac, ±10%
Frequency Range: 50 to 500 Hz
Configuration: 1-phase or 3-phase
Burden: 1.570 VA
125 Vdc PWM Output
Nominal: 240 Vac
Operating Range: 190 to 277 Vac, ±10%
Frequency Range: 50 to 500 Hz
Configuration: 1-phase or 3-phase
Burden: 3.070 VA
Voltage Buildup
From a minimum of 3 Vac
Terminals
C2 (A-phase), C3 (B-phase), C4 (C-phase)
Burden: <1 VA per phase
Terminals: A1. A2. A3
50 Hertz Sensing
Range 1: 100 Vac (85 to 127 Vac)
Range 2: 200 Vac (170 to 254 Vac)
Range 3: 400 Vac (340 to 508 Vac)
Range 4: 500 Vac (425 to 625 Vac)
60 Hertz Sensing
Range 1: 120 Vac (94 to 153 Vac)
Range 2: 240 Vac (187 to 305 Vac)
Range 3: 400 Vac (374 to 600 Vac)
Range 4: 600 Vac (510 to 660 Vac)
Generator Current Sensing
Type: Two ranges, two channels
Frequency: 50/60 Hz
Ranges: 1 A or 5 A nominal, continuous
Burden: <1 VA per phase
Terminals
1 A Sensing: B1. B3 (phase B, metering, var/PF, UEL)
B4. B6 (phase B, crosscurrent compensation)
5 A Sensing: B2. B3 (phase B, metering, var/PF, UEL)
B5. B6 (phase B, crosscurrent compensation)
Bus Voltage Sensing
Type: 1-phase, 4 ranges,
Burden: <1 VA
Sensing Ranges: Identical to generator voltage sensing
Terminals: A4. A5
Accessory Inputs
Current Input
Range: 4 to 20 mAdc
Terminals: A6 (+), A7 (–)
Voltage Input
Range: –10 to +10 Vdc