Terminals: A9 (+), A10 (–)
Communication Ports
Interface
RS-232: Full duplex
RS-485: Half duplex
Connections
Com 0: Front panel DB-9 connector
Com 1: Right-side panel DB-9 connector
Com 2: Left-side panel screw terminals (A43. A44. A45)
Parameters
Baud: 1200 to 19200
Data Bits: 8
Parity: None
Stop Bits: 1 (Com 0. Com 1) or 2 (Com 2)
Contact Inputs
Type: Dry contact; accept PLC open-collector outputs
Interrogation Voltage: 12 Vdc
Terminal Assignments
Start: A21. A22
Stop: A23. A24
Auto (AVR): A25. A26
Manual (FCR): A27. A28
Raise: A29. A30
Lower: A31. A32
Pre-Position: A33. A34
Unit/Parallel (52L/M): A35. A36
Var/PF (52J/K): A37. A38
Secondary Enable: A39. A40
Alarm Reset: A41. A42
Contact Outputs
Make and Break Ratings (Resistive)
24 Vdc: 7.0 A
48 Vdc: 0.7 A
125 Vdc: 0.2 A
120/240 Vac: 7.0 A
Carry Ratings (Resistive)
24/48/125 Vdc: 7.0 A
120/240 Vac: 7.0 A
Terminal Assignments
Start/Stop (ON, OF): A11. A12
Watchdog (WTCHD): A13. A14
Relay 1 (RLY1): A15. A16
Relay 2 (RLY2): A17. A18
Relay 3 (RLY3): A19. A20
Field Output
Continuous Output Rating
60 Vac Input: 32 Vdc, 15 Adc
120 Vac Input: 63 Vdc, 15 Adc
240 Vac Input: 125 Vdc, 15 Adc
10 Second Forcing Output Rating
60 Vac Input: 50 Vdc, 30 Adc
120 Vac Input: 100 Vdc, 30 Adc
240 Vac Input: 200 Vdc, 30 Adc
Minimum Field Resistance
32 Vdc Application: 2.13 Ω
63 Vdc Application: 4.2 Ω
125 Vdc Application: 8.3 Ω
Regulation
AVR Operating Mode
Accuracy: ±0.25% over load range at rated PF and constant generator frequency
Steady State Stability: ±0.1% at constant load and generator frequency
Temperature Drift: ±0.5% for a 0 to 50°C change
V/Hz Characteristic: Slope from 0 to 3 PU is adjust-able in 0.1 PU increments. Voltage
regulation error is within ±2.0% of the nominal voltage.
Response Time: <1 cycle