Industrial Security Router EAGLE20/30
Installation site requirements
If you connect the device to a power supply that does NOT meet the
requirements for Limited Power Source, NEC Class 2 or PS2
according to IEC/EN 62368-1 and is NOT limited to 100 W output
power, the device must be installed in either a switch cabinet or other
fire enclosure.
The fire enclosure can be made of metal or plastic with fire-protection
properties of at least V-1 according to IEC 60695-11-10. Bottom
openings of the fire enclosure must NOT exceed 2 mm in diameter.
Only for device variants featuring supply voltage with characteristic
value K9 or KK:
Install this device only in a switch cabinet or in an operating site with
restricted access, to which maintenance staff have exclusive access.
Strain relief
Note: If the strain relief is insufficient, there is a potential risk of torsion,
contact problems and creeping interruptions.
Relieve the connection points of cables and lines from mechanical
stress.
Design strain reliefs in such a way that they help prevent any
mechanical damage to cables, wires or conductors caused by external
influences or their own weight.
To help prevent damage to device connections, connectors and
cables, follow the instructions for proper installation in accordance with
DIN VDE 0100-520:2013-06. sections 522.6. 522.7 and 522.13.
Device casing
Only technicians authorized by the manufacturer are permitted to open
the casing.
Never insert pointed objects (narrow screwdrivers, wires, etc.) into the
device or into the connection terminals for electric conductors. Do not
touch the connection terminals.
Keep the ventilation slits free to ensure good air circulation.
See “Installing the device onto the DIN rail” on page 34.
Mount the device in the vertical position.
At ambient air temperatures > +60 °C (+140 °F):
The surfaces of the device housing may become hot. Avoid touching
the device while it is operating.
Qualification requirements for personnel
Only allow qualified personnel to work on the device.
Qualified personnel have the following characteristics:
Qualified personnel are properly trained. Training as well as practical
knowledge and experience make up their qualifications. This is the
prerequisite for grounding and labeling circuits, devices, and systems
in accordance with current standards in safety technology.
Qualified personnel are aware of the dangers that exist in their work.
Qualified personnel are familiar with appropriate measures against
these hazards in order to reduce the risk for themselves and others.
Qualified personnel receive training on a regular basis.
National and international safety regulations
Verify that the electrical installation meets local or nationally applicable
safety regulations.
Grounding the device
Grounding the device is by means of a separate ground connection on the
device.
Ground the device before connecting any other cables.
Disconnect the grounding only after disconnecting all other cables.
Shielding ground
The overall shield of a connected shielded twisted pair cable is connected
to the grounding connector on the front panel as a conductor.
Beware of possible short circuits when connecting a cable section with
conductive shielding braiding.
Requirements for connecting electrical wires
Before connecting the electrical wires, always verify that the
requirements listed are complied with.