play it on an HMI (panel), if necessary.
▶ Replace battery three days after the first diagnostic message at the latest.
This is how you replace the battery:
▪ You can exchange the battery while the controller is on or off. There is no data
loss if it is performed while the controller is on. When the controller is switched off,
the time period of the data buffering without a battery is approx. 5 minutes.
WARNING
THERE IS A RISK OF EXPLOSION/FIRE IF THE WRONG BATTERY IS USED
• Only use the type of battery with the following data: 3V Lithium Renata Type
2450N.
Failure to follow these instructions can result in death or serious injury
Use insulated pliers to lightly pull the old battery out of its slot.
CAUTION
DANGER OF EXPLOSION WHEN REMOVING/REPLACING BATTERY
• Use a pair of suitable, insulated pliers.
• When replacing the battery use tools which contain no current conducting
material on the contact points.
• In general, be careful not to short circuit the battery poles.
• Do not recharge, dismantle or place battery in fire.
A non-observance of these instructions can cause bodily injury or damage the equipment.
▶ Carefully place the new battery on the guide and lightly push it into the device.
For ordering information (see 5.6 Type code).
3.4 On- /off / reset of the PacDrive Controller
reset
[reset] button
▶ Press this button to reset the controller and reboot it.
Connected Servo Amplifiers MC-4 have their own [reset] button.