AKM 105. 115: Rotary actuator for ball valve
Improving energy efficiency
Torque-dependent cut-off facility for efficient usage of energy
Features
• For actuating 2- and 3-way ball valves (types VKR and BKR)
• For controllers with a switching output (2-/3-point control)
• Fitted to ball valves up to DN 50 without the need to use tools
• Synchronous motor with electronic activation and cut-out
•Maintenance-free gear unit
• Gear unit can be disengaged in order to position the ball valve manually (using the lever)
• Bracket and bayonet ring made of glass-fibre-reinforced plastic for fitting onto ball valve
• Fitting vertically upright to horizontal, not suspended
Technical data
Power supply
Power supply 230 V~ ±15%, 50...60 Hz
Power supply 24 V~ ±20%, 50...60 Hz
Parameters
Power cable 1.2 m, 3 × 0.75 mm2
Response time Min. 200 ms
Angle of rotation 90°
Ambient conditions
Admissible ambient temperature–10...55 °C
Admissible ambient humidity 5...95% rh, no condensation
Temperature of medium1) Max. 100 °C
Operation
Control 2-/3-point
Construction
Weight 0.7 kg
Housing Lower section black, upper section
yellow
Housing material Fire-retardant plastic
Standards and directives
Type of protection2) IP 54 as per EN 60529 (horizontal)
Protection class 24 V III as per IEC 60730
Protection class 230 V II as per IEC 60730
Over-voltage categories III
Degree of contamination II
CE conformity as per Directive 2006/95/EC EN 60730-1/EN 60730-2-14
EMC Directive 2004/108/EC EN 61000-6-1. EN 61000-6-2
EN 61000-6-3. EN 61000-6-4
Overview of types
Type Power consumption Running time Torque Voltage
AKM105F100 2.4 W, 4.5 VA 30 s 4 Nm 230 V~
AKM105F120 2.0 W, 4.0 VA 120 s 4 Nm 230 V~
AKM105F122 1.6 W, 1.7 VA 120 s 4 Nm 24 V~
AKM115F120 2.0 W, 4.0 VA 120 s 8 Nm 230 V~
AKM115F122 1.6 W, 1.7 VA 120 s 8 Nm 24 V~
Accessories
Type
0372459100
0372459102
0510420001
0510240011
0510480001
0510480002
Description
External switching, 230 V version for parallel operation with A*M 1*4 or drives with limit switch,
incl. junction box
External switching, 24 V version for parallel operation with A*M 1*4 or drives with limit switch,
incl. junction box
Adaptor required when temperature of the medium > 100 °C
Adaptor required when temperature of the medium < 5 °C
Auxiliary change-over contacts, single
Auxiliary change-over contacts, double
A Auxiliary change-over contacts: infinitely variable 0...100%, admissible load 5(2) A, 24...230 V
Description of operation
When voltage is applied to the cable, the control unit to be activated is moved to any desired position
by means of the carrier stem.
Direction of rotation for 3-point control (viewing the spindle of the ball valve from the actuator):
• The stem turns in the anti-clockwise direction, with the voltage on the brown cable, and the through
passage of the ball valve is opened.
• The stem turns in the clockwise direction, with the voltage on the black cable, and the through pas
sage of the ball valve is closed.
With 3-point control, the direction of rotation is changed by swapping the connections.
Direction of rotation for 2-point control (viewing the spindle of the ball valve from the actuator):
There is always voltage on the black cable.
• The stem turns in the anti-clockwise direction, with the voltage on the brown cable, and the ball
valve is opened.
• The stem turns in the clockwise direction, with no voltage on the brown cable, and the ball valve is
closed.
In the end positions (limit stop in actuator), or in the case of an overload, the magnetic coupling is
activated. The positioning signal is switched off by the electronic cut-out after 3 minutes or 60 sec
onds (F100).
The manual adjustment is performed by releasing the gear unit (slide switch beside the connection
cable) and simultaneously turning it with the lever. The actuator position can be determined by look
ing at the lever or the indicator knob on the top part of the actuator.
Outdoor installation
We recommend protecting the devices from the weather if they are installed outside the building.
Additional technical data
The upper section of the housing with the cover and indicator knob contains the synchronous motor
with capacitor and the electronics for the cut-off. The lower section of the housing contains the main
tenance-free gear unit and the gear-release knob.
Auxiliary change-over contacts:
• Switch rating max. 230 V~, current min. 20 mA at 20 V
• Switch rating max. 4...30 V=, current 1...100 mA
Power consumption
Running time [s]
Status
Type
AKM105F100
30
Operation
AKM105F120
120
Operation
AKM105F122
120
Operation
AKM115F120
120
AKM115F122
120
Disposal
When disposing of the product, observe the currently applicable local laws.
More information on materials can be found in the Declaration on materials and the environment for
this product.