SEL-400G Advanced Generator Protection System
Advanced Generator Protection System
Key Features and Benefits
The SEL-400G Advanced Generator Protection System offers unsurpassed protection, integration, control, and monitor
ing features for all types of generators including hydro, pumped-storage hydro, large steam turbines, and combustion gas
turbines (CGTs).
➤ Protect generators and step-up transformers in a single device with two independent universal differential zones.
➤ Provide protection during generator startup with two independent frequency zones with frequency tracking from
5 Hz to 120 Hz.
➤ Increase machine life with advanced generator monitoring capabilities such as turn-to-turn fault detection to detect
faults and abnormal conditions before they cause permanent damage.
➤ Reduce complexity for pumped storage generation with internal relay logic that eliminates the need for external
switching.
➤ Implement comprehensive protection schemes for generator and auxiliary systems with 18 current and 6 voltage
inputs.
➤ Design, deploy, and commission relay settings with ease using SEL Grid Configurator
Features
➤Current and Voltage Inputs. With 18 CT inputs
and 6 PT inputs, the SEL-400G provides protection
for generators ranging in size from small to large,
and protection schemes ranging from simple to
complex.
➤Universal Differential Protection (87Z). The
SEL-400G supports two independent universal
differential elements that can provide fast, sensitive,
and secure protection for as many as two independent
protection zones.
➤Stator Winding Ground Fault Protection (64G/
64S). The SEL-400G offers passive and active
methods for detecting ground faults across 100 percent
of the stator winding without sacrificing security.
➤Field Winding Ground Fault Protection (64F).
The SEL-400G, when used in conjunction with the
SEL-2664 Field Ground Module, can provide field
winding ground fault protection. The element can
be configured to provide either an alarm or trip
functions for the first field winding to ground fault.
Restricted Earth fault Protection (REF). The
SEL-400G provides three REF elements that can
provide fast, sensitive, and secure ground fault
protection for a low impedance-grounded
generator or for the wye winding of a generator
step-up (GSU).
➤ Stator Winding Turn-to-Turn Fault Protection
(60P/60N). The SEL-400G provides two sensitive
split-phase protection elements that can turn-to
turn fault protection for multibranch hydro
machines. The elements can adapt to standing
current offset and secure for external faults.
➤ Pumped Storage Logic. The SEL-400G internally
corrects the phasing introduced by the reversing
switch.
➤ Extended Range Frequency Tracking of 5–120 Hz.
The SEL-400G wide-range frequency tracking
algorithm ensures that all protection functions are
secure and dependable regardless of the frequency.
The SEL-400G also independently tracks the
generator and system frequencies.
➤ Loss-of-Field Protection (40). The SEL-400G
offers two impedance-based loss-of-field (LOF)
schemes and a generator capability-based LOF
scheme to protect the generator during a LOF event.
➤ Current Unbalance Protection (46). The SEL-400G
provides two negative-sequence overcurrent
elements for generator current unbalance protection.
Each element provides two levels, one definite and
one inverse-time. Each element can be configured
to operate on fundamental or harmonic negative
sequence current.
➤ Overexcitation Protection (24). The SEL-400G
provides two volts-per-hertz elements that can
provide overexcitation protection for both
generator and GSU. Each element provides two
levels of definite-time and two user-defined inverse
time curves.
➤ Inadvertent Energization Protection (INAD).
The SEL-400G provides as many as four inadvertent
energization elements that arm themselves when
the generator is taken offline and protect the
generator from inadvertent energization.
➤ Directional Power Protection (32). The SEL-400G
provides four sensitive directional power elements
with independent time delays. Additionally, the
SEL-400G provides a biased characteristic that
ensures both security and dependability.
➤ Out-of-Step Protection (78). The SEL-400G
provides two out-of-step (OOS) protection schemes:
single or double blinder. The SEL-400G also
includes a pole slip counter (PSC) that counts the
number of pole slips a generator experienced
during an OOS condition.
➤ Over- and Underfrequency Protection (81). The
SEL-400G provides six levels of over- or
underfrequency protection with undervoltage
supervision. The protection can be configured for
two independent frequency zones (generator and
power system zone).
➤ Rate-of-Change-of-Frequency Protection (81R).
The SEL-400G provides six levels of over- or
under-rate-of change-of-frequency protection with
undervoltage supervision. The protection can be
configured for two independent frequency zones
(generator and power system zone).
➤ Frequency Accumulation Protection (81A). The
SEL-400G provides frequency accumulation
protection by measuring the time-of-operation in
as many as eight frequency bands. The relay also
supports continuous bands.
➤ Thermal Overload Protection (49). The SEL-400G
provides three independent general-purpose thermal
elements that conform to IEC 60255-149 standard.
➤ Breaker Failure Protection (50BF). The
SEL-400G provides high-speed breaker failure for
as many as four circuit breakers. The logic is
immune to subsidence current and complimented
with breaker flashover detection logic.
➤ System Backup Protection. The SEL-400G
provides phase distance (21P) elements, voltage
controlled time-overcurrent (51C) elements, and
voltage-restrained time-overcurrent (51V)
elements for system backup protection.
➤ Synchronism Check (25). The SEL-400G
provides a synchronism-check function for as
many as three breakers. The function provides
supervision for acceptable voltage window and
maximum percentage difference, maximum and
minimum allowable slip frequency, target closing
angle, and breaker closing delay.
➤ Autosynchronizer (25A). The SEL-400G provides
comprehensive automatic synchronization control
of governor and voltage regulators for as many as
three breakers through use of pulse width
modulated contact outputs.
➤ Loss of Potential (60). The SEL-400G provides
loss-of-potential (LOP) elements for the V and Z
terminals.
➤ Synchrophasors. The SEL-400G provides
synchrophasor measurement of all 18 currents and
6 voltage channels. The relay complies with IEC/
IEEE 60255-118-1:2018 (IEEE C37.118.1-2011. -2014a) and supports as many as five unique
synchrophasor data streams that are compliant with
IEEE C37.118.2-2011 via serial or Ethernet
communications ports. The relay can record
Synchrophasor data for as long as 120 seconds
based on user-settable triggers.