differential operate current levels exceed the 87U pickup
threshold that is set depending on the application.
Typical 87U pickup level settings are between 8 and 10
per unit of operate current.
Restricted Earth Fault (REF) Protection
Apply the REF protection feature to provide sensitive
detection of internal ground faults on grounded wye
connected transformer windings and autotransformers.
Order the SEL-787 with the Slot E card containing the
1A or 5A current input for REF protection. The single
phase 1A or 5A CT provided as a Slot E ordering option
is used for introduction of neutral CT operating current.
Polarizing current is derived from the residual current
calculated for the protected winding (Winding1.
Winding2. or both windings). A sensitive directional
element determines whether the fault is internal or
external. Zero-sequence current thresholds and selectable
CT saturation logic supervise tripping.
Overcurrent Protection
The SEL-787 provides complete overcurrent protection
for a two-winding transformer. Phase overcurrent
protection is provided for both three-phase winding
inputs. The following overcurrent elements are provided.
Instantaneous Overcurrent Elements
The following instantaneous overcurrent elements are
provided in the SEL-787 base configuration. All
instantaneous overcurrent elements provide torque control.
➤Four instantaneous phase overcurrent (50P) elements
for Windings 1 and 2 (eight total). These phase ele
ments operate on the maximum of the phase cur
rents. Level1 phase overcurrent elements also
include per-phase elements. Peak detection algo
rithms are used to enhance element sensitivity during
high fault current conditions, where severe CT satura
tion may occur.
➤Two instantaneous negative-sequence overcurrent
(50Q) elements for Windings 1 and 2 (four total).
These phase elements operate on negative-sequence
content for each three-phase winding.
➤Two residual overcurrent (50G) elements for wind
ings 1 and 2 (four total). These elements use calcu
lated residual (3I0) current levels from each winding
for ground fault detection.
When ordered with the optional current channel in
SlotE, the SEL-787 also provides two instantaneous
neutral-overcurrent elements (50N) with two levels of
neutral-overcurrent detection.
Time-Overcurrent Elements
The SEL-787 base configuration provides the following
time-overcurrent elements. The time-overcurrent
elements support the IEC and US (IEEE) time
overcurrent characteristics shown in Table1.
Electromechanical disc reset capabilities are provided for
all time-overcurrent elements.
➤Eight phase time-overcurrent (51P) elements are pro
vided. These phase elements operate on the individ
ual phases as well as the maximum of the phase
currents for each winding.
➤Two negative-sequence time-overcurrent (51Q) ele
ments are provided. These elements operate on the
calculated negative-sequence current for each set of
three-phase winding inputs of the transformer.
➤Two residual overcurrent (51G) elements are pro
vided. These elements use calculated residual (3I0) cur
rent levels from each winding for ground fault detection.
When ordered with the optional current channel in
SlotE, the SEL-787 also provides one neutral time
overcurrent element (51N)