SEL-787 Transformer Protection Relay
Major Features and Benefits
The SEL-787 Transformer Protection Relay provides unsurpassed protection, integration, and control features in a
flexible, compact, and cost-effective package.
➤ Standard Protection Features. Two-winding dual-slope differential protection with harmonic blocking and
restraint, and phase, negative-sequence, residual-ground, and neutral-ground overcurrent elements provide backup
protection. Breaker failure protection is included for two three-pole breakers.
➤ Optional Protection Features. Use the SEL-787 with optional voltage inputs to provide volts/hertz protection with
frequency tracking from 20 to 70 Hz for generator step-up and other variable frequency applications. Implement
load shedding and other control schemes with over- and underfrequency and over- and undervoltage elements. In
addition, use Sensitive Restricted Earth Fault (REF) protection for grounded-wye transformers.
➤ Transformer Monitoring. Use transformer through-fault monitoring to measure accumulated through-fault levels
of the transformer. Monitor ambient, load tap-changer (LTC), tank, and transformer oil temperature through the use
of optional 4–20 mA or RTD thermal inputs.
➤ Operator Controls. Four programmable front-panel pushbuttons each with two programmable LEDs allow for a
wide variety of uses including easy trip and close control and status indications for a breaker. Implement local and
remote operator control schemes through use of 32 local and 32 remote control bits.
➤ Relay and Logic Settings Software. ACSELERATOR QuickSet® SEL-5030 Software reduces engineering costs for
relay settings and logic programming. Tools in QuickSet make it easy to develop SELOGIC® control equations. Use
the built-in phasor display to verify proper CT polarity and phasing.
➤ Metering and Reporting. Built-in metering functions eliminate separately mounted metering devices. Analyze
Sequential Events Recorder (SER) reports and oscillographic event reports for rapid commissioning, testing, and
post-fault diagnostics. Unsolicited SER protocol allows station-wide collection of binary SER messages.
➤ Additional Standard Features. Includes Modbus RTU, Event Messenger support, MIRRORED BITS® communications,
load profile, support for 12 external RTDs (SEL-2600 series module), IRIG-B input, advanced SELOGIC, configurable labels,
IEEE C37.118-compliant synchrophasor protocol, and SEL-2812 compatible ST connectors fiber-optic serial port.
➤ Optional Features. Select from a wide offering of optional features, including IEC 61850. Modbus TCP/IP, Simple
Network Time Protocol (SNTP), DNP3 LAN/WAN, DNP3 Serial, 10 internal RTDs, expanded digital/analog I/O,
voltage inputs, additional EIA-232 or EIA-485 communications ports, and single or dual copper wire or fiber-optic
Ethernet ports.
Protection Features
The SEL-787 provides the same dual-slope differential
characteristic used in the popular SEL-387 and SEL-587
series of transformer differential relays. The SEL-787
includes a complete set of phase, negative-sequence, and
residual overcurrent elements for each winding, as well
as REF and neutral-overcurrent elements for grounded
wye transformers.
Use as many as 12 independent RTD driven thermal
elements with trip and alarm levels to monitor ambient
and equipment temperatures throughout the substation.
For the optional volts/hertz element, you can add three
phase voltage inputs that give the SEL-787 volts/hertz
protection with definite and time-delay characteristics,
along with directional power, over- and underfrequency and
voltage elements with two independent pickup levels.
Transformer Differential
The SEL-787 has three restrained differential elements
(87R). These elements use operate and restraint
quantities calculated from the winding input currents. Set
the differential elements with either single- or dual-slope
percentage differential characteristics. Figure2
illustrates a dual-slope setting. The percent-slope
characteristic helps prevent unwanted relay operation
because of possible unbalance between CTs during
external faults. CT unbalance can result from tap
changing in the power transformer and error difference
between the CTs on either side of a power transformer.
The relay allows you to choose harmonic blocking,
harmonic restraint, or both, providing a reliable
differential protection during transformer inrush
conditions. Even-numbered harmonics (second and
fourth) provide security during energization, while fifth
harmonic blocking provides security for overexcitation
conditions. Set second-, fourth-, and fifth-harmonic
thresholds independently.
An additional alarm function for the fifth-harmonic
current employs a separate threshold and an adjustable
timer to warn of overexcitation. This may be useful for
transformer applications in or near generating stations. A
set of unrestrained differential current elements simply
compares the differential operating current quantity to a
setting value, typically about 10 times the TAP setting.
This pickup setting is only exceeded for internal faults.
The three independent unrestrained differential elements
(87U) provide rapid assertion without delay when