SEL-T400L Time-Domain Line Protection
Ultra-High-Speed Transmission Line Relay
Traveling-Wave Fault Locator
High-Resolution Event Recorder
Major Features and Benefits
The SEL-T400L is a state-of-the-art time-domain line protective relay operating within a few milliseconds for a wide
range of fault and system conditions. Available in both 5 A and 1 A models, the SEL-T400L incorporates fault locating
with accuracy typically within one tower span. With only a handful of settings and preconfigured protection logic, the
SEL-T400L is simple to apply, yet it supports a variety of applications and protection philosophies.
➤ Ultra-High-Speed Line Protection. Apply a traveling-wave line current differential scheme with a point-to-point
fiber-optic channel to trip faults in 1–5 ms depending on the line length. Apply an incremental-quantity Zone 1
element with a 2–5 ms operating time without communication. Apply a permissive overreaching transfer trip
scheme with any standard teleprotection channel using traveling-wave and incremental-quantity directional
elements operating in 0.1–3 ms.
➤ Versatile Applications. Apply the SEL-T400L to two-terminal overhead transmission lines, including series
compensation, single- and dual-breaker terminations, and three-pole and single-pole tripping.
➤ Simple Configuration. Use preconfigured relay logic and set only a few protection settings without the need for
extensive short-circuit studies.
➤ Accurate Fault Locating. Locate faults to the nearest tower.
➤ Line Monitoring. Monitor the line for incipient faults, recurring faults, or incipient cable faults.
➤ High-Resolution Oscillography. Record line currents and voltages with a 1 MHz sampling rate, storage for as
many as 50 events, and a duration of 1.2 seconds per event
Traveling-Wave Differential
Protection Scheme
The traveling-wave differential (TW87) protection
scheme uses current traveling waves (TWs) and a point
to-point fiber-optic channel to detect in-zone faults with
operating times in the range of 1–5ms depending on the
line length. The TW87 scheme is independent from
external time sources and provides internal synchroniza
tion of data over the communications channel. The
TW87 scheme is suitable for series-compensated lines
and can be used for single-pole tripping applications.
The TW87 scheme uses traditional CTs and wiring. It
uses voltage signals and works well with capacitively
coupled voltage transformers (CCVTs). The TW87
scheme can be applied on two-terminal tapped lines
owing to its first-ever location-dependent supervision.
Protection Element
The incremental-quantity distance (TD21) protection
element uses incremental voltages and currents to pro
vide underreaching distance protection. The element can
be set as high as 80 percent of the line length, has a tran
sient overreach below 10 percent, and operates between
2–5ms depending on the fault location, system short
circuit level, fault resistance, and point on wave. The
TD21 element is suitable for series-compensated lines
and can be set using the line impedance, neglecting the
in-line capacitors. The element is suitable for single-pole
tripping applications