Watlow’s SERIES CLS200 is a powerful line of controllers,
combining performance and flexibility with compact design.
The 4, 8 and 16 loop versions provide complete controller
solutions for a broad range of applications. Support for
multiple types of sensor inputs is available, including
thermocouples, RTDs, linear voltage, current and frequency.
Each controller can operate as a stand-alone system, and
includes built-in serial communications for computer interface
and data acquisition. Optional programmable ramp and soak
features allow complex batch processing and sequencing.
An enhanced feature option offers cascade control, ratio
control, differential control, process variable retransmit and
remote analog set point.
The SERIES CLS200 controllers are UL® and C-UL® listed and
meet the requirements of the European Community EMC
Directive and carry the CE mark.
Features and Benefits
PID control of up to 16 heat and cool loops
• Minimizes panel space per loop
• Reduces installation time
• Increases reliability: fewer parts means fewer failures
Auto-tune
• Requires less time tuning
• Achieves excellent control with less expertise
Menu-guided operation with full text display
• Allows quick setup of the controller
• Simplifies operation
Eight jobs stored and recalled
• Changes quickly from one process to another
Multiple and mixed inputs
• Accepts combinations of thermocouples, RTDs, linear
dc voltage and linear dc current sensors
• Reduces learning curve and inventory
Sensor failure detection
• Reduces time troubleshooting reversed, shorted and
open sensors
High/low process and deviation alarms for each input
• Integrates as needed to integrate with PLC and other
control elements
34 digital outputs
• Provides flexible configuration
• Allows use of outputs as needed for control and alarms
EIA/TIA-232 and 485 communications
• Connects to software for easy configuration and operation
• Allows integration with controllers and software
DAC and SDAC Modules
The optional DAC and SDAC modules are available for
Watlow SERIES CLS200 controllers.
DAC
The DAC (digital to analog converter) converts one or two
of the controller’s distributed zero crossing (DZC) output
signals to analog signals. Each output is field configurable
for 4-20mA(dc), 0-5VDC or 0-10VDC.
SDAC
The SDAC (serial digital to analog converter) converts
one controller output to a precise analog voltage or
current signal. The unit is typically used for process variable
retransmit, open-loop control, motor or belt speed control,
or phase-angle fired SCR power controllers. The SDAC bears
the CE mark and is UL® and C-UL® listed.
Firmware Options
Choose firmware with the features needed for the
application:
• Standard—includes closed-loop PID control, auto-tune,
alarms, job memory and failed sensor detection.
• Ramp and soak—includes the standard firmware
features with the addition of ramp and soak and process
variable retransmit. Each channel can be configured for
standard PID control or ramp and soak operation. Unused
control outputs on any channel can be configured for
retransmition.
• Enhanced features— includes the standard firmware
features with the addition of process variable retransmit,
remote analog set point, cascade control, ratio control
and differential control algorithms. Each channel can be
configured for standard PID controller or one of the other
control algorithms. Each channel of cascade control or
remote analog set point requires two controller channels.
Unused control outputs on any channel can be
configured for retransmit.
Because the SERIES CLS200 has no onboard analog
outputs, applications that use process variable retransmit
typically require one SDAC module per retransmitted
signal.


CLS200 Specifications
Operator Interface
• 32-character vacuum fluorescent display
• 8-key keypad to access guided menus and prompts,
enter passkey sequence, set values, switch between
single channel and multiple channel displays
• Controller configuration can be loaded through the
standard serial port
Analog Inputs
• CLS204 4 differential
• CLS208 8 differential
• CLS216 16 single-ended
Noise Rejection
• 120dB at 60Hz
Temperature Coefficient
• 40ppm/°C
Sensors/Inputs
• Thermocouples: user-selectable type, direct connection,
linearization, reference junction compensation, reversed
and shorted thermocouple detection and upscale break
protection with output averaging
• RTD: (CLS204 and CLS208 only) 2- or 3-wire, platinum,
100Ω @ 0°C, DIN 0.003850Ω/Ω/°C curve, user-selectable
range. Two user-selectable ranges offer different
resolutions. Requires scaling resistors. See special/linear
inputs in ordering information.
• Linear: current and voltage signals from linear transmitters
• Pulse input
Input Range and Accuracy
Sensor Range (°F) Range (°C) Accuracy
Type B 150 to 3200°F 66 to 1760°C ±4.0°C
Type E -328 to 1448°F -200 to 787°C ±1.0°C