Analog
Current output control (0 to 100 %)
Time proportioning cycle time
1.0 to 300.0 s, programmable in increments of 0.1 s
Pulse frequency
1 to 120 pulses per minute, programmable in increments
of 1 pulse per minute
Controller action
Direct or reverse
Proportional band
0.1 to 999.9 %, programmable in increments of 0.1 %
Integral action time (Integral reset)
1 to 7200 s, programmable in increments of 1 s (0 = Off)
Derivative
0.1 to 999.9 s in increments of 0.1 s – only available for
single set point control
Auto / Manual
User-programmable
…Specification
Access to functions
Direct keypad access
• Measurement, maintenance, configuration,
diagnostics or service functions
• Performed without external equipment
or internal jumpers
Sensor cleaning function – AX416 only
Configurable cleaning action relay contact
• Continuous
• Pulse in 1 s on and off times
Frequency
5 minutes to 24 hours, programmable in 15 minute
increments up to 1 hour then in 1 hour increments
for 1 to 24 hours
Duration
15 s to 10 minutes, programmable in 15 s increments up to
1 minute then in 1 minute increments up to 10 minutes
Recovery period
30 s to 5 minutes, programmable in 30 s increments
Mechanical data
Wall- / Pipe-mount versions
• IP65 (not evaluated under UL certification)
• Dimensions 192 mm high x 230 mm wide x 94 mm deep
(7.56 in. high x 9.06 in. wide x 3.7 in. deep)
• Weight 1 kg (2.2 lb.)
Panel-mount versions
• IP65 (front only)
• Dimensions 96 mm x 96 mm x 162 mm deep
(3.78 in. x 3.78 in. x 6.38 in. deep)
• Weight 0.6 kg (1.32 lb.)
Cable entry types
Standard
5 or 7 x M20 cable glands
North American 7 x knockouts suitable
for 1/2 in. Hubble gland
Power supply
Voltage requirements
• 100 to 240 V AC, 50 / 60 Hz (90 V min. to 264 V max. AC)
• 12 to 30 V DC
Power consumption
10 W
Insulation
Mains to earth (line to ground) 2 kV RMS
Environmental data
Operating temperature limits–20 to 55 °C (–4 to 131 °F)
Storage temperature limits–25 to 75 °C (–13 to 167 °F)
Operating humidity limits
Up to 95 %RH non condensing
EMC
Emissions and immunity
Meets requirements of:
• EN61326 (for an industrial environment)
• EN50081-2
• EN50082-2
Approvals, certification and safety
Safety approval
UL
CE mark
Covers EMC & LV Directives
(including latest version EN 61010)
General safety
• EN61010-1
• Overvoltage Class II on inputs and outputs
• Pollution category 2
Languages
Languages configurable:
• English
• French
• German
• Italian
• Spanish