Different coded applications are handled and supported from local ABB organizations.
The software of the units series DCS 600 is divided into two parts which are handled
by processors integrated in the respective boards SDCS-CON-2 (Software 15.2xx) and
SDCS-AMC-DC (Software 15.6xx).
The upload of signals from SDCS-CON-2 to SDCS-AMC-DC board are operated by:
• 6 automatic channels
• 11 programmable channels, selectable in group 94 (see Software description - chapter
31)
The 6 automatic channels are used by the functions:
• Display signals at control panel CDP 312
• Monitor signals at DriveWindow Tool
• Data Logger at DriveWindow Tool
If
• more than 6 signals of the SDCS-CON-2 board are selected, or
• the function Signals and Parameter of DriveWindow, or
• the overriding control (AC 80, AC 70…)
is used for monitoring, the signals should be selected in group 94.xx
Note: In the below mentioned tables AMC / CON-2 will be used as type designations
instead of SDCS-AMC-DC / SDCS-CON-2.
• Fixed (defined) values
Cyclic transmission is used for fixed values. Fixed values are:
Cyclic transmission Parameter Function Cyclic transfrom --> to mission time
AMC --> CON-2 Internal Control Word 2 ms
AMC --> CON-2 Reserved 2 ms
AMC --> CON-2 2.13 Torque reference value 2 ms
AMC --> CON-2 5.06 Analogue output 1 2 ms
AMC --> CON-2 5.07 Analogue output 2 2 ms
AMC --> CON-2 Local reference 3 8 ms
CON-2 --> AMC Internal Status Word 2 ms
CON-2 --> AMC 1.02 Actual speed value 2 ms
(speed_act)
CON-2 --> AMC 1.08 Actual torque value 2 ms
(torque_act)
CON-2 --> AMC 5.02 Analogue input 1 4 ms
CON-2 --> AMC 5.03 Analogue input 2 4 ms
CON-2 --> AMC 5.04 Analogue input 3 4 ms
CON-2 --> AMC 5.05 Analogue input 4 4 ms
CON-2 --> AMC 5.08 Analogue input 5 4 ms
CON-2 --> AMC 5.09 Analogue input 6 4 ms
CON-2 --> AMC 2.17 Calculated positive limit 8 ms
of torque value
(tc_torqmax)
CON-2 --> AMC 2.18 Calculated negative limit 8 ms
of torque value
(tc_torqmin)
CON-2 --> AMC 6.05 Packed signals from 8 ms
CON-2 (con2_bits)
CON-2 --> AMC 8.05 Packed binary inputs 8 ms
(di_status_word)
• Programmable values (can be changed for monitoring of other signals)
Cyclic transmission time for the first three programmable values is every 2 ms, for all
other values every 8 ms:
Cyclic transmission Enter pa- Cyclic trans- Default
from --> to rameter in mission time
AMC --> CON-2 95.01 2 ms 3.11 CURRENT REF
AMC --> CON-2 95.02 2 ms 45.01 FLUX REF
AMC --> CON-2 95.03 2 ms 45.03 EMF REF
AMC --> CON-2 95.04 8 ms 0
AMC --> CON-2 95.05 8 ms 0
AMC --> CON-2 95.06 8 ms 0
AMC --> CON-2 95.07 8 ms 0
AMC --> CON-2 95.08 8 ms 0
AMC --> CON-2 95.09 8 ms 0
AMC --> CON-2 95.10 8 ms 0
AMC --> CON-2 95.11 8 ms 0
AMC --> CON-2 95.12 8 ms 0
AMC --> CON-2 95.13 8 ms 0
CON-2 --> AMC 94.01 2 ms 3.13 ARM ALPHA
CON-2 --> AMC 94.02 2 ms 1.15 CONV CUR
CON-2 --> AMC 94.03 2 ms 3.12 CUR REF3
CON-2 --> AMC 94.04 8 ms 1.11 RL MAINS VOLT ACT
CON-2 --> AMC 94.05 8 ms 1.13 RL ARM VOLT ACT
CON-2 --> AMC 94.06 8 ms 1.28 LOAD CUR ACT FILT
CON-2 --> AMC 94.07 8 ms 1.17 RL EMF VOLT ACT
CON-2 --> AMC 94.08 8 ms 1.24 HEATSINK TEMP
CON-2 --> AMC 94.09 8 ms 1.20 MOT1 CALC TEMP
CON-2 --> AMC 94.10 8 ms 3.17 FIELD CUR REF M1
CON-2 --> AMC 94.11 8 ms 3.19 REL FIELD CUR M1
For example: Display of actual field current value 3.19 in 8 ms ⇒ 94.11 = 3.19.
Then call for display of Parameter 3.19
Symbols for switching the electronics or the power section ON and OFF
Check the unit for damage in transit or other damage.
Install and wire unit; connect all inputs and outputs required.
Proceed in the same way for the field supply unit as well.
Check whether protective measures, earthing, screening, etc. have been taken in
accordance with the system conditions involved.
Check the rated value of the supply voltage for the electronics and the fan:
• matching transformer necessary when:
- electronics supply is not equal to 115 V/230 V
- single-phase-fan supply is not equal to 230 V
- three-phase-fan supply is not within the range of 400 V .... 690 V (star/delta
connection).
Check the rated value of the supply voltage for the armature-circuit converter’s
power section; the particulars given on the rating plate must be > than the rated
line voltage.
If this condition is not satisfied, then the following applies:
- use an isolating transformer, or
- use a suitable unit.
Check the rated value of the supply voltage for the field supply unit.
(Particulars on rating plate > rated line voltage?
Is an auxiliary transformer or perhaps a series resistor necessary?)
Check the wiring, fusing, the cross-sectional areas of the cables.
Check the system’s EMERGENCY STOP for proper functioning! Set the system-side
monitoring functions, and activate them. Check whether auxiliaries, such as motor fans
or unit fans, function properly; while doing this, also check for correct direction of rotation and voltage level as well!
2.2 Scaling intra-unit signals
Make sure that the existing electronics supply voltage has been set on the SDCSPOW-1 power supply board as well, using the SW1 switch.
If an encoder is being used as the speed feedback device, make sure that the correct