AC 800M
The AC 800M controller is connected to the Advant Fieldbus 100 through single or
redundant CI869 communication interfaces. The CI869 has integrated twisted pair
modems.
The CI869 module along with AC 800M controller does not function as
bus administrator on the AF 100 bus. If this station is used, the AF 100 bus requires
another station type that functions as bus administrator.
S800 I/O Station
The S800 I/O Station has integrated Twisted Pair modems for connection to
Advant Fieldbus 100.
AdvaSoft for Windows
AdvaSoft for Windows is connected to Advant Fieldbus 100 through a CI526
communication interface and a modem – TC625 (for coaxial media) or
TC512/TC516 (for twisted pair media).
Advant OPC Server for Advant Fieldbus 100 and AC 100 OPC Server
The OPC Server is connected to Advant Fieldbus 100 through a CI526 or a CI527
communication interface.
When using CI526, one or two TC625 modems (for coaxial media) or
TC512/TC516 modems (for twisted pair media) are required.
The CI527 has two integrated Twisted Pair modems. When CI527 is to be connected
to coaxial media, a TC513 repeater modem for each bus line is used for media
conversion.
CI626/CI6301 Communication Interface
The Advant Controller 110 is connected to the Advant Fieldbus 100 through a
CI626 communication interface. The Advant Controller 160 is connected to Advant
Fieldbus 100 through a CI626 or CI630 communication interface (see Figure 11 and
Figure 12).