• The coaxial segment can be:
– 300 meters (1000 feet) with cable RG59 or
– 700 meters (2300 feet) with cable RG11.
• The optical media is only used in point-to-point communication, and it allows
the total length of a bus segment to be up to 1700 meters (5500 feet).
• If back-to-back coupled optical segments are used, it is possible to reach up to a
physical length of 13300 meters (43300 feet).
An Advant Fieldbus 100 may be installed with one or two physical bus lines (single
or redundant media). Two bus lines are chosen when increased availability is
required. The redundant bus line does not enhance the bus bandwidth when both the
bus cables are operating.
Advant Fieldbus 100 Redundancy Concept
The Advant Fieldbus 100 redundancy concept contains:
• Media redundancy
• Communication interface redundancy
• S800 I/O Field Communication Interface redundancy.
When redundant media is used, redundancy must be maintained through the whole
bus (this comprises of the bus lines as well as connections of the stations to the bus).
Media Redundancy
The Media redundancy includes redundant cable and redundant modems. A media
redundant AF 100 is configured and connected as in Figure 1.
The maximum difference in cable length between the redundant cables must be less
than 1200 meters between any two stations throughout the whole bus.

Figure 1. An Advant Fieldbus 100 configuration using redundant media
If the Advant Fieldbus 100 contains one or more of CI520, CI526, CI626, CI810
or PM810 (without the suffix Vx(1)
(1) V1, V2, V3, and so on
or y(2)
(2) y=A, B, and so on
), it is only possible to use redundant
coaxial media with a maximum difference of four meters in cable length, between
any two stations on the bus. A redundant Twisted Pair or Optical media cannot be
used in this case.
Communication Interface Redundancy Section 1 Introduction
28 3BSE000506-600
Communication Interface Redundancy
Communication interface redundancy is achieved by using a pair of CI522s, CI630s,
CI631s, CI869s or CI820s, connected to a media redundant bus. Communication
interface redundancy is available for Advant Controller 400 Series, Advant
Controller 160, AC 800M controller, and S800 I/O stations.
Two communication interfaces (CIs) can operate as a pair, where one is Primary and
the other is Backup in the controller configuration.
Functions of Primary CI
In a redundant configuration, the address of the primary CI is the configured station
address on the bus.
The primary CI:
• Sends all output CDPs.
• Receives all input CDPs.
• Sends the time synchronization message if the station is configured as time
synchronization master.
• Handles the normal Service Data communication for the station.
• Supervises that the backup can send on the bus. This is done at a low frequency
using the service data protocol.
• Must be configured as bus master if the module is CI522/CI630 or CI631, so
that the bus master responsibilities are performed
Functions of Backup CI
In a redundant configuration, the address of the backup CI on the bus is the
configured station address + 80.
The backup CI:
• Supervises that the primary CI sends its output CDPs properly.
• Sends signal to the controller if the primary CI does not send its output CDPs.
• Receives all input CDPs.
• Responds to Service Data communication with the Primary.
• Must be configured as bus master if the module is CI522, CI630 or CI631. If
the station number is less than or equal to 47, the backup module performs the
bus master responsibilities, otherwise it does not.
Communication Interface Redundancy in Advant Controller 400 Series
To connect the CI522 redundant communication interfaces to a twisted pair bus, two
TC516 modems (or four TC512 modems) are used. See Figure 2.
To connect the CI522 redundant communication interfaces to a coaxial cable bus,
four TC625 modems are required.
The TC516 modem has two connections, one for each redundant CI522 and a
connection to one twisted pair bus cable. TC516 can be used for two redundant
CI522s as well as for one single CI520V1/CI522/CI526V1.

If communication interface redundancy is used, set the DB-element for
double time-out. See Double CDP Time-out on page 88.
Communication Interface Redundancy in Advant Controller 160
For configurations with one Advant Fieldbus 100, the communication interface
CI630/CI631 must be placed at position 2 (non redundant interface) or in position 1
and 2 (redundant interface) in the Basic Station.
A second and third Advant Fieldbus 100 can be used with AC 160. These can use
single or redundant communication interfaces. The communication interfaces can
be placed at position 9 and 10, or 11 and 12, and so on.

S800 I/O Field Communication Interface Redundancy
The redundancy in the S800 I/O Stations is achieved with redundant Field
Communication Interfaces (FCIs) connected to a media redundant
Advant Fieldbus 100. In the S800 I/O station, redundancy is achieved with
redundant S800 communication interfaces sharing the same I/O modules. This