EMERSON KL4103X1-BA1 CHARMs Smart Logic Solver Carrier
KL4103X1-BA1 CHARMs Smart Logic Solver
Carrier
Hazardous Atmosphere
II 3G Ex ec IIC Gc
FM19ATEX0173U
IECEx FMG 19.0019U
FM21UKEX0017U
CL. I Div. 2 GP. A,B,C,D
CL. I Zone 2 AEx/Ex ec IIC Gc
FM17CA0145U
FM17US0286U
Power Specifications
Input power redundant
Output power to
CHARMS
+24 VDC at 12.5 A
+24 VDC at 10 A
+6.3 VDC at 4 A
Environmental Specifications
Ambient Temperature -40 °C to +70 °C
Shock
Vibration
Airborne
Contaminants
Relative Humidity
10g ½ Sinewave for 11msec
1mm Peak to Peak from 2 to
13.2Hz; 0.7g from 13.2 to 150Hz
ISA-S71.04 –1985 Airborne
Contaminants Class G3
5 to 95% Non-Condensing
Note: Refer to the product label for serial number
and location and date of manufacture.
Warning: This product has specific instructions for
installation, removal and operation in hazardous
areas. Refer to document 12P5403 "DeltaV
Electronic Marshalling Digital Automation System
(CHARM I/O Subsystem) Zone 2 Installation
Instructions". Other installation instructions are
available in the " DeltaV S-series and CHARMs
Hardware Installation" manual.
Removal and Insertion
This unit cannot be removed or inserted with system
power energized unless the area is known to be
non-hazardous.
Maintenance and Adjustment
This unit contains no user serviceable parts and
should not be disassembled for any reason.
Calibration is not required.