EMERSON KJ3242X1-BK1 12P4711X042 S-Series H1 Card
KJ3242X1-BK1 S-Series H1 Card
Hazardous Atmosphere
II 3G Ex ec IIC Gc
FM19ATEX0173U
IECEx FMG 19.0019U
FM21UKEX0017U
II 3G Ex nA nL IIC Gc
Nemko 10ATEX3225U
IECEx NEM 10.0019U
CL. I Div. 2 GP. A,B,C,D
CL. I Zone 2 AEx/Ex ec IIC Gc
FM17US0286U
FM17CA0145U
Power Specifications
Local Bus Power
Fieldbus Power
12 VDC at 300 mA
9 to 32 VDC at 12 mA/Port
Environmental Specifications
Ambient
Temperature
Shock
Vibration
Airborne
Contaminants
Relative Humidity
Terminal Block key
Position -40°C to +70°C
10g ½ Sinewave for 11msec
1mm Peak to Peak from 2 to 13.2Hz;
0.7g from 13.2 to 150Hz
ISA-S71.04 –1985 Airborne
Contaminants Class G3
5 to 95% Non-Condensing

Note: Refer to the product label for serial number
and location and date of manufacture.
Warning: This product has specific instructions for
installation, removal and operation in hazardous
areas. Refer to document 12P5404 "DeltaV™ S
Series Digital Automation System Zone 2 Installation
Instructions". Other installation instructions are
available in the "DeltaV™ S-Series and CHARMs
Hardware Installation" manual.
Removal and Insertion
Field power supplied to this device, either at the field
terminal or as bussed field power through the
Carrier, must be removed before removing or
connecting the device.
This unit cannot be removed or inserted with system
power energized.
For “nL” installation, an I/O loop assessment must
be completed on all energy-limited nodes.
A rotary keying system ensures compatibility
between I/O cards and terminal blocks after
installation is complete. The terminal block must
have the keys set for the I/O card with which it is
used.
Maintenance and Adjustment
This unit contains no user serviceable parts and
should not be disassembled for any reason.
Calibration is not required.