FBM202 Thermocouple/mV Input Module
he FBM202 Thermocouple/mV Input contains eight thermocouple input channels, and one isolated RTD
reference junction compensation channel.

OVERVIEW
The FBM202 Thermocouple/mV Input contains eight
thermocouple input channels, and one isolated RTD
reference junction compensation channel (for terminal
temperature sensing). Each thermocouple/mV
channel accepts standard thermocouples for various
temperature ranges, and each provides
thermocouple burnout detection (up-scale). The
inputs are galvanically isolated from other channels
and ground.
The module performs the signal conversion required
to interface the electrical input signals from the field
sensors to the optionally redundant Fieldbus. It
executes an Analog Input application program, which
provides integration time and Rate of Change Limits
configurable options
When connected to the appropriate TAs, the
FBM202 module provides functionality formerly
provided by the 100 Series FBM I/O subsystem. TAs
are available which support the functionality of the
100 Series FBM02.

FEATURES
Key features of the FBM202 are:
Eight channels for input of thermocouple signals
One isolated RTD reference junction
compensation channel (for terminal temperature
sensing)
Each input channel is galvanically isolated
Rugged design suitable for enclosure in Class G3
(harsh) environments
Execution of an analog input application program
that provides conversion time and configurable
options for Rate of Change Limits
High accuracy achieved by sigma-delta data
conversions for each channel
Termination Assemblies (TAs) for locally or
remotely connecting field wiring to the FBM202
HIGH ACCURACY
For high accuracy, the module incorporates Sigma
Delta data conversion on a per-channel basis, which
can provide new analog input readings every 25 ms,
and a configurable integration period to remove any
process noise and power line frequencies.
Each time period, the FBM converts each analog
input to a digital value, averages these values over
the time period and provides the averaged value to
the controller.
STANDARD DESIGN
FBM202 has a rugged extruded aluminum exterior
for physical protection of the circuits. Enclosures
specially designed for mounting the FBMs provide
various levels of environmental protection, up to
harsh environments, per ISA Standard S71.04.
VISUAL INDICATORS
Red and green light-emitting diodes (LEDs)
incorporated into the front of the module provide
visual status indications of the FBM operational
status.
EASY REMOVAL/REPLACEMENT
The module can be removed/replaced without
removing field device termination cabling, power, or
communications cabling.
FIELDBUS COMMUNICATION
A Fieldbus Communications Module or a Control
Processor interfaces to the redundant 2 Mbps
module Fieldbus used by the FBMs. The FBM
accepts communication from either path (A or B) of
the 2 Mbps Fieldbus — should one path fail or be
switched at the system level, the module continues
communication over the active path.
MODULAR BASEPLATE MOUNTING
The module mounts on a DIN rail mounted
baseplate, which accommodates up to four or eight
Fieldbus Modules. The Modular baseplate is either
DIN rail mounted or rack mounted, and includes
signal connectors for redundant Fieldbus, redundant
independent dc power, and termination cables.
TERMINATION ASSEMBLIES
Field I/O signals connect to the FBM subsystem via

DIN rail mounted TA, or
Baseplate-mounted TA.
The TAs used with the FBM202 are described in
“FUNCTIONAL SPECIFICATIONS – TERMINATION
ASSEMBLIES” on page 8.
FUNCTIONAL SPECIFICATIONS
Input Channels
Eight isolated and independent thermocouple/mV
input channels. One isolated reference junction
temperature compensation channel.
Input Range–10.5 to +69.5 mV dc (–10.5 to +69.5 mV dc equals
0 to 64000 raw counts. Input of 71.419 mV equals
65535 raw counts (full range of module))
Reference Junction
Reference junction temperature compensation is
provided by a 4-wire 100 ohm platinum RTD
(IEC 751. Class B) at the termination assembly.
Accuracy
MILLIVOLT INPUT
±0.03% of span (±24 µV) at 25°C
RTD CHANNEL
±0.03% of span
RTD REFERENCE JUNCTION CONFORMITY
±0.25°C
THERMOCOUPLE CONFORMITY
±0.25°C
ACCURACY TEMPERATURE COEFFICIENT
±50 ppm/°C
Input Signal A/D Conversion
Each channel performs A/D signal conversion using
an independent Sigma-Delta converter.
Typical Thermocouple Types
B, E, J, K, N, R, S, T and other millivolt signals
Thermocouple Burnout Detection
Full upscale value
Input Channel Isolation
Each channel is galvanically isolated from all other
channels and earth (ground). The module withstands,
without damage, a potential of 600 V ac applied for
one minute between any channel and ground, or
between a given channel and any other channel.
CAUTION
This does not imply that these channels are
intended for permanent connection to
hazardous voltage circuits. Connection of
thes

FUNCTIONAL SPECIFICATIONS (CONTINUED)
Regulatory Compliance
ELECTROMAGNETIC COMPATIBILITY (EMC)
Eur
PHYSICAL SPECIFICATION (CONTINUED)
Termination Cables
CABLE LENGTHS
Up to 30 m (98 ft)
CABLE MATERIALS
Polyurethane or Low Smoke Zero Halogen
(LSZH)
TERMINATION CABLE TYPE
Type 2 - Refer to Table 2.
CABLE CONNECTION