Woodward 8440-1855 Genset Control
The easYgen-2000 Series is a compact, affordable genset control and protection package for load sharing up
to 16 gensets in island operation, or parallel operation of a single unit with a utility. Its integrated load depend
ent start/stop programming allows you to define how gensets are brought on- and off-line to support changing
load demands. It equally works with a mix of different sized engines, so you can maintain the spinning reserve
you need while optimizing fuel efficiency.
The easYgen-2000 Series works with many common industrial interfaces: CANopen for peer-to-peer load shar
ing; J1939 for engine ECU; Modbus RTU for PLC, HMI, and SCADA; and modem for remote control and pro
gramming using Woodward ToolKit software.
FlexAppTM– This feature provides the tools to easily configure the number of operated breakers: None, GCB,
GCB and MCB.
LogicsManagerTM – Woodward's LogicsManager enables to change the operation sequences and adapt them
to specific needs. The LogicsManager accomplishes this by monitoring a range of measuring values and inter
nal states, which are combined logically with Boolean operators and programmable timers. This enables to cre
ate and/or modify control and relay functions.
FlexInTM– The analog inputs are configurable to operate with VDO, resistive, and/or 0 to 20 mA senders.
Flexible Outputs – Speed and voltage bias outputs are configurable to function with all speed governors and
voltage regulators. The outputs can also be used as freely scalable outputs (e.g. for driving external meters).
FlexCANTM– Flexible and isolated CAN bus providing different protocols: CANopen protocols; coupling of IKD 1
expansion cards (up to 16DIs/16DOs) as well as of 3rd party expansion cards (request more detailed infor
mation from our sales department). ECU 1939 communication with start/stop and alarm management.
Operation modes: Auto, Stop, Manual, and Load/No Load test modes via discrete input possible
• Breaker control: Slip frequency / phase matching synchronization, open-close control, breaker monitoring
• Load transfer features: open / closed transition, interchange, soft loading / soft unloading, mains parallel
• Remote control via interface and discrete/analog inputs for adjusting speed, frequency, voltage, power, reac
tive power, and power factor set points
• Active power and reactive power load sharing with up to 16 units including load-dependent start/stop
• Neutral interlocking function to ensure only one of the running generators is bridged to earth
• Operating hours/start/maintenance counters - Operating hours also available from a connected ECU via
J1939/CAN
• Supported ECU: Scania EMS/S6. Deutz EMR2. Volvo EMS2. MTU ADEC ECU7/8. Woodward EGS, MAN
EDC 7. SISU EEM2/3. Cummins, Perkins and J1939 standard messages
• Event recorder (300 events, FIFO) with real time clock (battery backed; min. 5 years)
• 128×64 dot graphical interactive LC display with soft keys
• Start/stop logic for Diesel/Gas engines
• Engine pre-glow or purge control
• Warm-up control via timer or coolant temperature
• PC and/or front panel configurable (ToolKit software)
• Multi-level password protection
• Discrete I/O expansion board connectivity (Woodward IKD 1 or Phoenix Contact IL series)
• Multi-lingual capability (11 languages in 1 unit configurable: English, German, French, Spanish, Chinese, Jap
anese, Italian, Portuguese, Turkish, Russian, Polish)
Power supply .......................................................... 12/24 Vdc (8 to 40 Vdc)
Intrinsic consumption .......................................max.~ 8 W (easYgen-2200)
......................................................................max..~ 12 W (easYgen-2500)
Ambient temperature (operation) ....................... -20 to 70 °C / -4 to 158 °F
Ambient temperature (storage) ........................ -30 to 80 °C / -22 to 176 °F
Ambient humidity...................................................... 95 %, non-condensing
Voltage .............................................................................................. ( /)
120 Vac [1] Rated (Vrated) ............................................ 69/120 Vac
Max. value (Vmax) ............................................ 86/150 Vac
Rated voltage phase – ground ............................ 150 Vac
Surge volt.(Vsurge) .................................................... 2.5 kV
and 480 Vac [4] Rated (Vrated) .......................................... 277/480 Vac
Max. value (Vmax) .......................................... 346/600 Vac
Rated voltage phase – ground ............................ 300 Vac
Surge volt.(Vsurge) .................................................... 4.0 kV
Accuracy .......................................................................................... Class 1
Linear measuring range .............................................................. 1.25×Vrated
Measuring frequency............................................... 50/60 Hz (40 to 85 Hz)
High Impedance Input; Resistance per path ....... [1] 0.498 M, [4] 2.0 M
Max. power consumption per path ................................................ < 0.15 W
Current (Isolated) Rated (Irated) .............................. [1] ../1 A or [5] ../5 A
Linear measuring range ........................................................ Igen = 3.0×Irated
Imains/ground = 1.5×Irated
Burden .......................................................................................... < 0.15 VA
Rated short-time current (1 s) .................................[1] 50×Irated, [5] 10×Irated
Discrete inputs .............................................................................. isolated
Input range ............................................................. 12/24 Vdc (8 to 40 Vdc)
Input resistance .............................................................. approx. 20 kOhms
Relay outputs ........................................................................ potential free
Contact material ............................................................................... AgCdO
Load (GP) ...................................................................... 2.00 Aac@250 Vac
2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Pilot duty (PD) ..............................................................................................
1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Analog inputs (none isolated)............................................ freely scalable
Type ................................................................. 0 to 500 Ohms / 0 to 20 mA
Resolution ........................................................................................... 11 Bit
Analog outputs (isolated) ................................................... freely scalable
Type ..................................................................... ± 10 V / ± 20 mA / PWM
Insulation voltage (continuously) ..................................................... 100 Vac
Insulation test voltage (≤ 5s) ......................................................... 1000 Vac
Resolution ................................................. 11/12 Bit (depending on output)
± 10 V (scalable) ........................................ internal resistance ~ 500 Ohms
± 20 mA (scalable) .............................................. maximum load 500 Ohms
Housing Front panel flush mounting ............Plastic housing
Dimensions WxHxD 219 × 171 × 61 mm (easYgen-2200/2300)
WxHxD .........219 × 171 × 98 mm (easYgen-2500)
Front cutout WxH ........................... 186 [+1.1] × 138 [+1.0] mm
Connection .................................................... screw/plug terminals 2.5 mm²
Front ................................................................................. insulating surface
Sealing Front ........................... IP65 (with screw fastening)
Front ........................... IP54 (with clamp fastening)
Back ............................................................... IP20
Weight ................................................ approx. 800 g (easYgen-2200/2300)
................................................................. approx. 1.100 g (easYgen-2500)
Listings....................................... UL, cUL, GOST-R (easYgen-2200/2500)
Marine .............................. LR (Type Approval), ABS (Design Assessment)
..........