200-582-922-NHh
(d)
Two DC inputs with screw-terminal connectors that provide a common input to the
RPS6U power supplies.
Supports redundant external power-supply systems.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F900.
200-582-990-NHh
(e)
One AC input (120/230 VAC) with mains socket and on/off switch that provides a common
input to the RPS6U power supplies.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F100.
200-582-910-NHh
(f)
One AC input (120/230 VAC) with screw-terminal connector, on/off switch and rear-panel fuses
that provides a common input to the RPS6U power supplies.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F110.
200-582-911-NHh
(g)
One AC input (120/230 VAC) with screw-terminal connector and rear-panel fuses that provides
a common input to the RPS6U power supplies.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F120.
200-582-912-NHh
(h)
Two AC inputs (120 VAC only) with mains sockets and on/off switches that provide a common
input to the RPS6U power supplies.
Supports redundant external power-supply systems.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F620.
200-582-962-NHh
(i)
Two AC inputs (120/230 VAC) with mains sockets and on/off switches that provide individual
inputs to the RPS6U power supplies.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F630.
200-582-963-NHh
(j)
Two AC inputs (230 VAC only) with mains sockets and on/off switches that provide a common
input to the RPS6U power supplies.
Supports redundant external power-supply systems.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F600.
200-582-960-NHh
(k)
Two AC inputs (120/230 VAC) with screw-terminal connectors, on/off switches and rear-panel
fuses that provide individual inputs to the RPS6U power supplies.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F150.
200-582-915-NHh
(l)
Two AC inputs (120/230 VAC) with screw-terminal connectors and rear-panel fuses that
provide individual inputs to the RPS6U power supplies.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F160.
200-582-916-NHh
(m)
One AC input (120/230 VAC) with mains socket and on/off switch and one DC input with screwterminal connector that provide individual inputs to the RPS6U power supplies.
This rear panel is equivalent to Rear panel for RPS6U power supply order option code F700.
200-582-970-NHh
Rack power supply unit
RPS6U
14 / 15 © Meggitt SA / 268-011 / Version 9 / 23.04.2015 / E
Notes
All AC input rear panels are supplied with a mains power supply lead (no lead is supplied for the DC input versions). See Mains power
supply leads (power cords) on page 14.
AC input rear panels with mains sockets have an IEC type C14 connector (IEC 60320) that mates with the plug (type C13) used by the
supplied mains power supply leads.
Rear panels with one input – (a), (b), (c), (d), (e), (f) and (g) – are 2 slots wide / 8 HP (TE).
Most rear panels with two inputs – (h), (i), (j), (k) and (l) – are 4 slots wide / 16 HP (TE).
However, the rear panel with AC and DC inputs – (m) is 2 slots wide / 8 HP (TE).
(The width of 19″ rack is measured in horizontal pitch (HP) units of 5.08 mm (0.2″), also known as standard width (TE) units. For the
ABE04x rack, a one slot wide (one card position) blank panel corresponds to 4 HP (TE), a two slot wide blank panel corresponds to 8 HP (TE)
and a four slot wide blank panel corresponds to 16 HP (TE).)
Rear panels with two input connectors that provide a common input to the RPS6U power supplies – (d), (h) and (j) – installed in the rack can
be used with a redundant external power-supply system.
For additional information on the Rear panel for RPS6U power supply order option codes (Fxxx), refer to the ABE040 and ABE042 VM600
system rack and ABE056 VM600 slimline rack data sheets.
For the Ordering number:
“NHh” represents the hardware version.
“N” is either “0” for a rear panel according to (and marked) CE low voltage directive or “2” for a rear panel according to (and marked) CCSAUS.
“H” increments are for major modifications that can affect product interchangeability.
“h” increments are for minor modifications that have no effect on interchangeability
Mains power supply leads (power cords)
To order please specify the type (Mains power supply lead), designation and ordering number from the table below
Designation Ordering number
None – no mains cable.
This rear panel is equivalent to Mains power supply lead (power cord) order option code H00. ---
No plug – flying lead with wire-end ferrules.
This rear panel is equivalent to Mains power supply lead (power cord) order option code H01. 957.18.13.0020
J plug as per SEV 1011 (Switzerland).
This rear panel is equivalent to Mains power supply lead (power cord) order option code HCH. 957.18.13.0021
E+F plug as per CEE7/VII (Europe, Russia, Ukraine).
This rear panel is equivalent to Mains power supply lead (power cord) order option code HEU. 957.18.13.0022