Backplane : Proprietary VM600Mk2/VM600 rack buses (Tacho bus, Raw bus and
Open collector (OC) bus) for data/signal sharing between modules
(cards).
VME bus for communication between CPUx modules (cards) and
processing modules (cards).
Rack slots
(module (card) positions)
: Front of rack:
• 12 × slots – module (card) positions 03 to 14 – for processing
modules (cards) such as MPC4Mk2, XMx16, MPC4 and/or AMC8.
• 2 × slots – module (card) positions 00 to 01 – for rack controller
and communications interface modules (cards) such as CPUMMk2
or CPUx.
• 1 × slot – module (card) position 02 – reserved for applicationspecific modules (cards).
Rear of rack:
• Up to 19 × slots – module (card) positions 00 to 18 – for associated
input/output modules (cards) such as IOC4Mk2, XIO16T, IOC4T and/
or IOC8T, IOCNMk2 or IOCx, and relay modules (cards) such as
RLC16Mk2, RLC16 and/or IRC4.
• Up to 4 × slots – module (card) positions 17 to 20 – for associated
rear panels for inputs to the VM600Mk2/VM600 RPS6U rack power
supply or supplies.
See also Mechanical drawings – front and rear views on page 6.
Notes
In general, associated input/output modules (cards) are required
while relay modules (cards) are optional.
For safety reasons, any VM600Mk2/VM600 rack slot not populated
by a module (card) must be covered by a blank panel(s).
Rack slot number coding : For modules (cards) installed in the rear of an ABE04x rack, an
electronic keying mechanism known as slot number coding is used
to help ensure that the module (card) is installed in the correct slot,
as defined by the configuration (that is, by the VibroSight® or
VM600 MPSx software).
For ABE04x racks, the rack’s slot numbers are fixed (hard-wired) and
slot number coding requires that a module’s slot number is set to
match the rack slot (module (card) position) where it is installed.
Slot number coding range : 3 to 14
Slot number coding defaults : Fixed (hard-wired) as follows:
• Slot 03 = 3 (0011 binary)
• Slot 04 = 4 (0100 binary)
…
• Slot 13 = 13 (1101 binary)
• Slot 14 = 14 (1110 binary).
Galvanic separation : Galvanic separation units (GSIxxx) are available for accelerometer
and proximity systems mounted in explosive atmospheres. These
units cannot be supplied by the rack and require an external power
supply. They must be mounted outside the rack in a remote housing
or in a cabinet.
Power supply
VM600Mk2/VM600 RPS6U rack power
supplies
: A VM600Mk2/VM600 ABE04x system rack can have either one or
two RPS6U rack power supplies installed, as follows:
• 1 × RPS6U power supply (330 W) supports the power requirements
for a full rack of modules (cards) in applications with operating
temperatures up to 50°C (122°F).
• 2 × RPS6U power supplies (330 W) – operating redundantly –
supports the power requirements for a full rack of modules (cards)
in applications with operating temperatures up to 50°C (122°F).
With this rack power supply redundancy, if one RPS6U fails, the
other will provide 100% of the rack’s power requirements so that the
rack will continue to operate.
Note: This is known as a redundant RPS6U rack power supply
configuration.
• 2 × RPS6U power supplies (330 W) – operating non-redundantly –
supports the power requirements for a full rack of modules (cards)
in applications with operating temperatures above 50°C (122°F),
where RPS6U output power derating is required.
Note: Even though two RPS6U rack power supplies are installed in
the rack, this is not a redundant RPS6U rack power supply
configuration.
Refer to the VM600Mk2/VM600 RPS6U rack power supplies
data sheet and a VM600Mk2/VM600 machinery protection system
(MPS) hardware manual for further information.
Power supply check relay
Nominal switching capacity
(resistive load)
: 4 A / 250 VAC, 3 A / 30 VDC
Maximum switching power
(resistive load)
: 1000 VA, 90 W
Maximum switching voltage : ±30 VRMS / ±42.4 VAC(PEAK) or 60 VDC
Maximum switching current : 4 AAC, 3 ADC
Environmental
According to IEC 60068-2 recommendations
Temperature
• Operating : 0 to 70°C (32 to 158°F)
• Storage : −40 to 85°C (−40 to 185°F)
Humidity : 0 to 90%, non-condensing
Vibration : 10 to 55 Hz, 0.35 mm peak, 6 hours in each direction
Shock : 15 g peak, 11 ms, half-sine pulse
Indoor use : Limited to indoor use only
Approvals
Conformity : European Union (EU) declaration of conformity (CE marking).
CCSAUS certificate of compliance.
EAC marking, Eurasian Customs Union (EACU) certificate/
declaration of conformity.
Electromagnetic compatibility : IEC/EN 61000-6-2 and IEC/EN 61000-6-4.
TR CU 020/2011.
Electrical safety : IEC/EN 61010-1.
TR CU 004/2011.
Vibration : IEC 60255-21-1 (Class 2)
Environmental management : RoHS compliant
Russian federal agency for technical
regulation and metrology (Rosstandart)
: Pattern approval certificate OC.C.28.004.A N° 60224
Physical
Dimensions : See Mechanical drawings starting on page 4
Weight : 6.5 kg (14.3 lb) approx.
without RPS6U power supplies and modules (cards)
S

Type Designation Ordering number (PNR)
ABE040 Different versions of the VM600Mk2 ABE040 system rack: