interface will not add more than the values specified in Clause 5.7 of EN 60079-11: 2012 to the parameters of the circuit
into which it is connected.
When an external intrinsically safe source is connected to these terminals it should have a source resistance of Ui / Ii and
the capacitance and either the inductance or inductance to resistance ratio (L/R) ofthe hazardous area connections must not
exceed the values detailed in the certificate of the intrinsically safe source. Hazardous area terminal 2 must not be used
when the source is connected.
Hazardous Area Terminals 2 W.r.t. 3
22V
145mA
0.80W
o
o
Load Parameters
The capacitance and either the inductance or inductance to resistance ratio (L/R) ofthe hazardous area load connected
must not exceed the following values:
GROUP CAPACITANCE INDUCTANCE OR L/RRATIO
(J.lF) (mH) (J.lH/ohm)
Hazardous Area Terminals 2 w.r.t. 1
IIC 0.165 0.91 39
lIB* 1.14 5.5 147
IIA 4.20 10.7 322
I 6.00 16.4 517
* Group IIB parameters also applicable for associated apparatus [Ex ia Da] lIIC
Notes:
1) The above load parameters apply when one ofthe two conditions below is given:
- the total Li ofthe external circuit (excluding the cable) is < 1% ofthe Lo value or
- the total Cj ofthe external circuit (excluding the cable) is < 1% ofthe Co value.
2) The above parameters are reduced to 50% when both ofthe two conditions below are given:
- the total Li ofthe external circuit (excluding the cable) is 1% ofthe Lovalue and
- the total Cj ofthe external circuit (excluding the cable) is 1% ofthe Co value.
The reduced capacitance ofthe external circuit (including cable) shall not be greater than 11lF for Groups IIB, IIA
& I and 600nF for Group IIC.
16 Report Number
GB/BAS/ExTR16.0237/00
17 Specific Conditions of Use
None
18 Essential Health and Safety Requirements
In addition to the Essential Health and Safety Requirements (EHSRs) covered by the standards listed at item 9, the
following are considered relevant to this product, and conformity is demonstrated in the report:
Clause
1.2.7
1.2.8
1.4.1
1.4.2
Subject
Protection against other hazards (LVD type requirements, etc.)
Overloading of equipment (protection relays, etc.)
External effects
Aggressive substances, etc.
Compliance
Manufacturer responsibility
User/Installer responsibility
User/Installer responsibility
User/Installer responsibility
19 Drawings and Documents
New drawings submitted for this issue of certificate:
Number
CI4541-3
Sheet
80f8
Issue
4
Date
7.16
Description
MTL45541S, MTL4541T, MTL4544S, MTL4544D
Certification Label Details - Baseefa
The above drawing is associated and held with IECEx BAS 09.0070 Iss. 6
Current drawings which remain unaffected by this issue:
Certificate No.
Baseefa09ATEX0155/2
Baseefa09ATEXO155/3
Baseefa09ATEX0155/4
Baseefa09ATEXO 155/5
Date
31 January 2011
6 August 2012
4 March 2013
27 January 2014
Comments
i) To permit the alternative fitting of ISMB3EZ** zener diodes in
place of 15MB59**BT3 components currently fitted.
ii) An alternative method of applying the conformal coating to the
PCB fitted 10 the equipment not affecting the original
assessment.
The associated test and assessment is documented in Certification
Report No. GB/BAS/ExTR10.0298/00.
To confirm the current designs of the MTL4541S, MTL4544S &
MTL4544D Repeater Power Supplies, 4/20mA have been reviewed
against the requirements of IEC 60079-0: 2011 and
EN 60079-11: 2012 10 respect of the differences from
EN 60079-0: 2009, EN 60079-11: 2007 and EN 61241-11: 2006 and
none ofthe differences affect the equipment. In accordance with EN
60079-11: 2012, the Group I capacitive load parameters were
corrected and the associated load parameter notes were updated.
The associated assessment is documented in Certification Report
No. GB/BAS/ExTR12.0181/00.
i) To permit minor component changes to the current design to
form the MTL4541T Single Channel Repeater Power Supply,
4/20mA for 2 or 3-Wire Transmitters.
ii) To confirm the current designs ofthe MTL4541S, MTL4541T,
MTL4544S & MTL4544D Repeater Power Supplies, 4/20mA
have been reviewed against the requirements of EN 60079-0:
2012 in respect ofthe differences from IEC 60079-0: 2011 and
none ofthe differences affect the equipment.
The associated assessment is documented in Certification Report
No. GB/BAS/ExTR13.0022/00.
i) To permit minor component changes to the MTL4541 T Single
Channel Repeater Power Supply, 4/20mA for 2 or 3-Wire
Transmitters not affect the original assessment.
ii) To permit minor drawing changes not affecting the original
assessment.
The associated assessment is documented in Certification Report
No. GB/BAS/ExTR14.0019/00.
Baseefa09ATEXO 155 Issue 6 26
2016
September This issue of the certificate incorporates previously issued primary
& supplementary certificates into one certificate and confirms the
current designs meet the requirements of
EN 60079-0: 2012 + All: 2013 & EN 60079-11: 2012.
The certificate also permits the manufacturer's name to be changed
on page 1 ofthe certificate and on the equipment marking.
The associated assessment is documented in Certification Report
No. GB/BAS/ExTR16.0237/00.
For drawings applicable to each issue, see original ofthat issue