DCS Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

schneiderInstruction MI 021-390 February 2016 I/A Series® Magnetic Flow Transmitter Model IMT25 Operation, Configuration, and Calibration

From:schneider | Author:LIAO | Time :2025-08-22 | 645 Browse: | 🔊 Click to read aloud ❚❚ | Share:

1. Introduction

Description

An I/A Series Magnetic Flowmeter System consists of two major components: 

 IMT25 Magnetic Flow Transmitter with Version 2 Software

 Magnetic Flowtube

 8000A wafer body

 2800, 8300, 9100A, 9200A, or 9300A flanged body

A system may be specified with the transmitter integrally mounted with the flowtube or with a 

remote mounted transmitter, which can be mounted either on a pipe or a flat surface.

Your transmitter has one of three communication protocols.

One is a FoxCom communications protocol. The digital output signal in this version is used 

for flowmeters serving as a primary measuring device in an I/A Series system. You can 

communicate with this version via the I/A Series system, the PC-based Configurator, or the 

optional local keypad/display.

Another has HART communications capability. You can communicate with this version via a 

HART Communicator, PC-Based Configurator, or the optional local keypad/display. 

The third has FOUNDATION fieldbus communication capability. You can communicate with 

this version via a fieldbus host or the optional local keypad/display.

This document describes local operation, configuration, and calibration of an IMT25 Transmitter 

supplied with local keypad and display. For information on operation, configuration, and 

calibration from a PC-Based Configurator, a HART Communicator, or a FOUNDATION fieldbus 

host refer to the documents listed in “Reference Documents” on page 13.

Intended Audience

This document is intended for use by process operators, engineers, and instrument technicians. If 

you are interested only in operation, read the general information in the Introduction and the 

chapter titled Operation. If you are interested in calibration, read the Introduction and chapters 

titled Operation and Calibration. If you are concerned with configuration, read the entire manual, 

with special emphasis on the chapter titles Configuration and the structure diagrams in 

Appendix A and the configuration worksheets in Appendix B.

Functions

Using the IMT25 front panel keypad/display, the functions you can perform are:

Operating Functions

 Display Measurement Information: The current value of the flow rate in engineering 

units (EGU), flow rate in percent of upper range value (URV), the Forward Total, 

Reverse Total, Net Total, and Grand Total.

 Display the Status of the Transmitter: The current operating mode, Analog and Pulse 

Output values, Contact Input settings, Relay Output settings, noise reduction, 

AutoZeroLock information, and write protection as well as alarm and diagnostic 

status.

 Display Identity Information: Tag, description, and message plus identification data 

for the flowmeter, flowtube, and transmitter software.

 Acknowledge Alarms and Diagnostic Conditions.

 Reset Totals.

Calibration Functions

NOTE

These functions can be passcode protected from keypad changes.

 Adjust the 4 and 20 mA output signal (requires additional equipment)

 Preset outputs to calibrate control loop

 Calibrate the AutoZeroLock Detector

Configuration Functions

NOTE

These functions can be passcode protected from keypad changes.

 Display and modify all configuration parameters

 Assign passcodes and set levels of privilege

Reference Documents

This document addresses operation, configuration, and calibration using the local keypad/display 

panel. For remote communication with your transmitter and other details of the flowmeter, refer 

to the applicable documents listed in Table 1

2. Quick Start

FoxCom or HART Protocol

Your IMT25 Transmitter can be configured with a PC-Based Configurator or with the 

keypad/display option. With the keypad/display, two configuration menus exist, Quick Start and 

Setup. Most basic applications can be configured in Quick Start mode.

Quick Start mode can be used for applications requiring only:

 A 4-20 mA output based on a flow rate in (US) GPM

 The transmitter display to show a flow rate in (US) GPM

 A FoxCom digital or HART flow rate signal.

Use Setup mode that is fully described in “Configuration” on page 39, for applications involving:

 Transmitters powered from 50 Hz sources

 Pulse and frequency outputs

 Totalizer functions

 Flow units other than (US) GPM

 Alarm functions

 Multi-range or bi-directional flow configurations.

To make Quick Start changes to the configuration, go to 1 TOP LEVEL/Quick Start by 

pressing the Left arrow repeatedly until the display reads 1 TOP LEVEL. Then use the up/down 

arrow keys to go to 1 TOP LEVEL/Quick Start. The procedure to change your configuration is 

demonstrated by the following example: 

 Flowmeter factor of 18.22 (refer to “Determining the Meter Factor” on page 18)

 Forward direction of flow

 Flow Range 0 to 150 GPM

1. Use the Right arrow key to move to MFACTOR FORMAT? {###.######}. This format 

can be changed, if necessary, to accommodate the meter factor.

a. If no change is required, press the Right arrow key.

b. To change the format, press Shift + Change to enter Edit Mode. Then use the 

up/down arrow keys to step through the choices. When you reach the format you 

want, press the Right arrow key.

2. The display reads METER FACTOR? {###.######} (Default {012.000000}). Press 

Shift + Change to enter Edit Mode. Use the Right/Left arrow keys to move the 

cursor under the digits you want to change. Use the up/down arrow keys to change 

the digits to the desired values. In the case of this example, continue this procedure 

until the display reads [018.220000]. Use the Right arrow key to move the cursor 

out past the right bracket to save the setting. The display then reads METER FACTOR?

{018.219998}. Note that in some cases, as with this example, a slightly different

value will appear. The magnitude of this difference is insignificant. Press the Right 

arrow key again. 

NOTE

To determine the correct meter factor, refer to “Determining the Meter Factor” on 

page 18.

3. The display reads RATE FORMAT? {#####.#} This format can be changed, if 

necessary, to accommodate your flow rate.

a. If no change is required, press the Right arrow key.

b. To change the format, press Shift + Change to enter Edit Mode. Then use the 

up/down arrow keys to step through the choices. When you reach the format you 

want, press the Right arrow key.

4. The display reads FORWARD URV? {#####.#} (Default {00100.0}). Press Shift + 

Change to enter Edit Mode. Use the Right/Left arrow keys to move the cursor under 

the digits you want to change. Use the up/down arrow keys to change the digits to the 

desired values. In the case of this example, continue this procedure until the display 

reads [00150.0]. Use the Right arrow key to move the cursor out past the right 

bracket to save the setting. The display then reads FORWARD URV? {00150.0}.

5. Now that all changes have been made, press the Right arrow key. You are asked Go 

On-Line? Reply Yes by pressing the Right arrow key. Press the Right arrow key again 

to begin displaying flow measurements.

Foundation Fieldbus Protocol

Your transmitter has been preconfigured at the factory to the settings shown in Appendix B. 

Compare your needs to the factory configuration and note the changes to the configuration you 

must make.

If the transmitter is not connected to a flowtube or IMTSIM, it is necessary to put a jumper wire 

between terminals Coil 1 and Coil 2 and also to provide power to the transmitter.

This section describes the procedures to quick start the transmitter from the optional local 

keypad/display. Note that after you quick start the transmitter from the local keypad, you should 

use the fieldbus host to ensure that parameter values associated with the host are changed to agree 

with those changed from the local keypad/display. Otherwise, mismatch errors occur when you 

attempt to place the transmitter into Auto mode.

To make changes to the configuration using the local keypad/display, go to 1 TOP LEVEL/Setup

by pressing the Left arrow repeatedly until the display reads 1 TOP LEVEL. Then use the 

Up/Down arrow keys to go to 1 TOP LEVEL/Setup. The procedure to change your 

configuration is demonstrated by the following example: 

 Engineering units (EGUs) in GPM (factory default setting)

 Forward direction of flow (Unidir positive - factory default setting)

 Flow range 0 to 150 GPM

 Flowmeter factor of 18.22 (refer to “Determining the Meter Factor” on page 18)

  1. Note that the factory default engineering units is already configured as GPM, so no change is required. 2. Note that the factory Output mode is also already configured as UniDir positive, so no change in the direction is required. 3. You must enter your flow upper range value however. To do this: a. Go to Setup Level 2 by pressing the Right arrow key. Next move to 2 SETUP Outputs with the Down arrow key. Then move to 3 OUTPUTS Output Mode with the Right arrow key

b. Use the Down arrow key to go to 3 OUTPUTS Range Info and the Right arrow 

key to go to FORWARD URV? {#####.#} GPM (Default {00100.0}).

c. Press the Shift + Change keys to enter Edit mode. You are asked Go Offline?

Reply Yes by pressing the Right arrow key. The display shows FORWARD URV?

[#####.#] GPM.

d. Use the Right/Left arrow keys to move the cursor under the digits you want to 

change. Use the Up/Down arrow keys to change the digits to the desired values. In 

the case of this example, continue this procedure until the display reads 

[00150.0].

e. Using the Right arrow key, move the cursor under the right bracket and press the 

key to enter the URV. The display reads FORWARD URV? {150.0} GPM. 

f. Press the key again to move back to 3 OUTPUTS Range Info.

4. Lastly, you have to enter your flowmeter factor. To do this:

a. Use the Left arrow key to move to the Level 2 menu, 2 SETUP Outputs.

b. Press the Down arrow key six times to move to 2 SETUP Calibration and the 

Right arrow key to move to the Level 3 menu, 3 CALIBRATION Meter Factor. 

See FIgure A-5.

c. Use the Right arrow key to move to MFACTOR FORMAT? {###.######}. This 

format can be changed, if necessary, to accommodate the meter factor.

d. Use the Right arrow key to move to METER FACTOR? {###.######} (Default 

{012.000000}. Then press Shift + Change to enter Edit mode.

e. Use the Right/Left arrow keys to move the cursor under the digits you want to 

change. Use the Up/Down arrow keys to change the digits to the desired values. In 

the case of this example, continue this procedure until the display reads 

[018.220000]. Use the Right arrow key to move the cursor out past the right 

bracket to save the setting. The display then reads METER FACTOR? 

{018.219998}. Note that in some cases, as with this example, a slightly different 

value appears. The magnitude of this difference is insignificant.

NOTE

To determine the correct meter factor, refer to “Determining the Meter Factor” on 

page 18.

f. Press the Right arrow key again. The display reads 3 CALIBRATION Meter 

Factor.

5. Now that all changes have been made, press the Left arrow key until you are asked Go 

On-Line? Reply Yes by pressing the Right arrow key. To display flow measurement, 

press the Right arrow key once more.

! CAUTION

If you change the upper range value or engineering units in the Transducer Block with 

the local display pushbuttons without making a corresponding change in the 

corresponding Analog Input Blocks from a fieldbus host, a mismatch error occurs and 

the Analog Input Block reverts to Out of Service mode.

Determining the Meter Factor

First find the “Cal Factor” or “IMT25 Cal Fact” on the flowtube data label.

If the flowtube data label has a “IMT25 Cal Fact.” listing, use that value as the “Meter Factor.”

If only a “Cal Factor” value is found on the flowtube data label, that value must be multiplied by 

the appropriate factor from Table 2 to calculate the “Meter Factor.”

Operation from Keypad/Display Panel

For local operation, configuration, and calibration, all operator entries are made through a 

5-button keypad and all data is presented on a 2-line x 16 character LCD display. The 

keypad/display of the IMT25 Transmitter is shown in Figure 1. Information on various types of 

display is shown in Figure . 

Figure 1. IMT25 Magnetic Flow Transmitter — Keypad/Display

All required functions are accomplished by using the four arrow keys alone and in combination 

with the Shift key. Table 4 explains the function of each key

Top Level Menu

The Top Level menu displays the following modes – Measurements, Status, Identity, Quick Start 

(in FoxCom and HART transmitters), Test Mode, and Setup. You can switch from one to another 

in sequence by using the Up/Down arrow keys. To enter the second level menu from a particular 

top level screen, press the Right arrow key. To return to the top level from a second level menu 

item, press the Left arrow key. The level of the first, second, third, and fourth level menus is 

indicated by the digit appearing as the first character in Line 1 of the display; a 1 indicates Level 1 

(Top Level), a 2 indicates Level 2, and a 3 indicates Level 3, etc.

The top level menu is shown in Figure 3. For a complete presentation of all menu structures, refer 

to Appendix A.

Measurements Mode

The Measurements mode, which is your main operating mode, is displayed upon startup. 

Depending on the transmitter configuration, it has up to seven displays, any of which may be set 

as the startup default. All screens can be scrolled with the Up/Down arrow keys.

 Rate (EGU) — Shows current flow rate (forward or reverse) in the selected 

engineering units. 

 Rate (% Range) — Shows current flow rate (forward or reverse) as a percentage of full 

scale URV.

 Fwd Tot — Shows current value of the forward totalized flow in engineering units. 

Use the Net Tot display to reset.

 Rev Tot — Shows current value of the reverse totalized flow in engineering units. Use 

the Net Tot display to reset.

 Net Tot — Shows current value of the net totalized flow (forward total - reverse total) 

in selected engineering units. Press Shift + Reset to reset the displayed total to 

zero. Resetting Net Tot also resets Fwd Tot and Rev Tot. It does not reset Gr Tot. 

If Reset Totals is passcode protected, the message Enter Passcode appears.

 Grand Tot — Shows current value of the grand total flow in engineering units. Press 

Shift + Reset to reset the displayed total to zero. Resetting Gr Tot does not reset 

Fwd Tot, Rev Tot, and Net Tot. If Reset Totals is passcode protected, the message 

Enter Passcode appears.

If the Dual Display feature is configured On, a combination of two of these parameters can be 

displayed at once. A typical dual display, in which Line 1 shows flow rate and Line 2 shows the 

present forward total, is shown below. Units may not be displayed or may be truncated. 

You may step through the displays of each of these parameters with the Up and Down arrow keys. 

However, unless you specifically do so, the display defaults to that configured in Setup mode. The 

engineering units and formats used in the displays are also configured in Setup mode.

Status Mode

The Status mode enables you to view fourteen system parameters and thus assess the performance 

of the loop. You may not edit them in this mode. To step through the displays of the following 

parameters, use the up/down arrow keys: 

 Mode — Shows the present operating mode: On-Line, Off-Line, Override, or 

Calibrate. This will normally display On-Line. The other modes will only be 

displayed if someone else has changed the mode with an I/A Series Workstation,

PC-Based Configurator, HART Communicator, or fieldbus host. Off-Line means

that it has been taken off-line; Override, that the measurements cannot be relied 

upon because one or more of the outputs is at a preset value; and Calibrate, that the 

transmitter is in Calibration mode.

 Alarm — Shows the most current active alarm. If there are no active alarms but 

something is in the history buffer, the display reads Alarms In Buffer. If there are 

no active alarms and nothing in the buffer, display reads No Alarms. 

 Diagnostics — Shows No Diag, Diag Existed, or Diag Exists. If a diagnostic 

problem exists, the second line identifies the problem. Help is available with the 

Shift + Help keys. An active diagnostic problem cannot be cleared; the problem 

must be corrected. Diag Existed means a diagnostic error did occur, but the 

condition has cleared and the transmitter is working correctly. However, the Diag icon 

will remain on the display until the diagnostic has been acknowledged. To clear, the 

transmitter must be in the Status mode with the diag window displayed. Then use the 

Shift + Ack keys.

 Digital Output — If the transmitter output is in Digital Output mode, the display 

shows whether the transmitter is configured for Unidirectional or BiDirectional flow. 

If the transmitter is not in Digital Output mode, the screen is not displayed.

NOTE

Digital and Analog Output are mutually exclusive. Only one of the two are displayed 

at any one time.

 Analog Output — If the transmitter output is in Analog Output mode, the display 

shows whether the transmitter is configured for U (unidirectional), U/M1

(unidirectional multirange-range 1), U/M2 (unidirectional multirange-range 2, U/M3

(unidirectional multirange-range 3), B/D (bidirectional dual range), or B/S

(bidirectional split range). If the transmitter is not in Analog Output mode, the screen 

is not displayed.

NOTE

Digital and Analog Output are mutually exclusive. Only one of the two are displayed 

at any one time.

Table 5. Analog Output Configuration

Display Interpretation

U UniDirectional Flow Single Range

U/M1 UniDirectional Flow Multi-Range

Range 1 Active

U/M2 UniDirectional Flow Multi-Range

Range 2 Active

U/M3 UniDirectional Flow Multi-Range

Range 3 Active

B/D BiDirectional Flow Dual Range

B/S BiDirectional Flow Split Range

(mA reading less than 12 indicates reverse flow, greater than 12, 

positive flow)

**UNKNOWN** Multi-Range is configured, but both contact inputs used to select 

the active range are in inactive state

 AZL Detect (Empty Pipe Det) — The intent of the AutoZeroLock Detection 

(Empty Pipe Detection) feature is explained in “AutoZeroLock (Empty Pipe)” on 

page 53. 

If the AutoZeroLock (Empty Pipe) detector is configured On, the display shows:

EPD Inactive, EPD Active, or EPD Needs Setpnt (FoxCom)

AZL Inactive, AZL Active, or AZL Needs Setpnt (HART)

Inactive, Active, or AZL Needs Cal (Fieldbus).

When AZL (EPD) is active, the outputs are locked at zero. If AZL (EPD) is 

configured Off, the status display shows Off.

! WARNING

Do not take any action that can cause danger to personnel or damage to equipment 

based on the assumption that a pipe is empty or full because of an AutoZeroLock 

(Empty Pipe Detection) indication.

 AZL Count (Empty Pipe Cnt) — Shows the cumulative count (maximum of 255) of 

AZL (empty pipe) conditions that have occurred since the last reset. To reset the 

count to zero, press Shift + Reset Note that in some cases several counts may 

occur for one emptying of the pipeline.

 Noise Reduction — Shows whether the noise reduction function is configured On or 

Off.

Write Protection — Shows whether the Write Protection dip switch is in the On position so that 

no Setup (configuration) changes may be made. This feature is usually only used in custody 

transfer applications or for another reason that you want to assure that the configuration is not 

changed. For the procedure to change the setting of this switch, see MI 021-387.


  • Beckhoff Nail Operating Terminal CP7032-1031-0010
  • Beckhoff AM8042-0EH1-0000 Servomotor 4.10 Nm (M0), F4 (87 mm)
  • Beckhoff EK9300 Beckhoff CPU Module
  • Beckhoff CP3224-0020 Multitouch-Panel-PC
  • Beckhoff CP2712-0000 12.1" 24VDC Touch Screen WMD0
  • BECKHOFF CX5240-0195 / 0000289234 Embedded PC 40 GB CFast Card
  • Beckhoff CP6932-1000-0000 Control Panel
  • BECKHOFF CX5120-0121 PLC Module
  • Beckhoff EL3218 | EtherCAT Terminal, 8-channel analog input
  • Beckhoff C6640-0050 | Control cabinet Industrial PC
  • Beckhoff Cx5130-0120/4GB Embedded-PC
  • BECKHOFF CX2030-0122 PLC PROCESSOR
  • BECKHOFF CX5020-0122 Controller Module
  • Beckhoff CP3915-0000 Multitouch Panel
  • BECKHOFF EL3014 | EtherCAT Terminal
  • BECKHOFF Industrial Computer c6920-1057-0030
  • Beckhoff CX5130-0141/4GB CX5130-0141 Embedded PC
  • Beckhoff C6240-1052-0040 4-086-06-3073 Industrial Computer
  • Beckhoff CX5140-0135 /4GB High-Performance Embedded Industrial PC
  • Beckhoff C6515-1001-0000 Industrial PC
  • Beckhoff AX5103-0000-0200 - Digital Compact Servo Drives
  • Beckhoff CX2030-0130-1003/4GB Basic CPU module
  • Beckhoff AX8620-0000 Power Supply Module
  • Beckhoff CX9020-0111 module with
  • Beckhoff EL7332 PLC Module
  • BECKHOFF CP7709-0001-0020 HMI
  • Beckhoff CX5120-0155/2GB Embedded PC
  • BECKHOFF CP7037-1037-0010 OPERATOR INTERFACE TOUCHSCREEN
  • Beckhoff EK9000 | ModbusTCP/UDP Bus Coupler
  • Beckhoff Touch Panel Screen CP6020 -0000-0000
  • Beckhoff CX2020-0121 Module FAST Shipping
  • Beckhoff CX2030-0125 Basic CPU Module
  • Beckhoff CP3918-0000 Multi-Touch 18.5" Control Panel
  • Automotion LC4A00010 DC BL Motor Control, ATS, Sub Assy, SCP, 115VAC,
  • 500T-115VAC - VAS ENGINEERING - DORIC 500 SERIES DIGITAL TEMP INDICATOR
  • Honeywell X-DCS2000/EN Digital Integrated System Manager 50/60Hz 100-240V #4
  • Kollmorgen S60600 Servostar600 606-Fan 4 kVA, 6 A, 3 X 230 - 480 V
  • ABB XZ C828 A101 Didt Dioder Snubber 3BHE039453R0101
  • ABB 3BHB027232R0001 1-Phase Charging Transformer
  • ABB 3BHE006412R0101 Circuit Board UFC762AE101
  • ABB XVC770BE101 3BHE021083R0101 Circuit Board
  • ABB 3BHE021887R0101 (Model: UBCC717BE101 / UBC717BE101) is an advanced
  • ABB 3BHE032593R0001 Isolated Power Supply
  • ABB 3BSC610023R0001 POWER SUPPLY SD812
  • Beckhoff C6650-0060 | Control cabinet Industrial PC
  • Beckhoff CP2916-0000 Industrial HMI Display Panel
  • Beckhoff AM8053-0L2B-0000 Servomotor 15.4 Nm (M0), F5 (104 mm)
  • Beckhoff CP6202-0001-0020 Industrial Panel PC
  • Beckhoff CX2020-0120 Plc Module
  • Beckhoff CX1010-0111 BASIC CPU MODULE
  • Beckhoff C6017-0010 | Ultra-compact Industrial PC
  • BECKHOFF CX2040-0155 Plc Module
  • Beckhoff CX5120-0125 Embedded PC
  • BECKHOFF C6930-0040 INDUSTRIAL CONTROL COMPUTER
  • Beckhoff CP6907-0001-0000 Economy Built-in Control Panel
  • Beckhoff CP2912-0000 Multi-Touch Built-In Control Panel
  • Beckhoff C6015-0010 Ultra-Compact Industrial PC
  • Beckhoff CX5130 | Embedded PC with Intel Atom® E3827
  • Beckhoff C6030-0060 Ultra-Compact Industrial PC
  • OMRON 3G3XV-A2007 3G3XV-A2007-NEV2
  • Omron NJ1019000 NJ1 programable logic controller
  • OMRON C120-LK202-EV1/C120LK202EV1
  • OMRON C200H-AD003 PLC
  • OMRON C200H-CPU23-E COIL 24VDC PLC
  • Omron C200HG - C200H-ID212- C200H-OC226 C200HW-BC101 PLC Base Unit
  • OMRON C200H-OC222(Output Unit),C200H-PS211(Power Supply Unit),SP001 Module Rack
  • OMRON C200H-RT201 PROGRAMMABLE CONTROLLER
  • OMRON C200HS-CPU01-E SYSMAC PROGRAMMABLE CONTROLLER
  • OMRON C200H-SNT31 C200H Programmable Controllers
  • OMRON C200HW-MC402-E Motion control unit
  • OMRON C200PC-ISA02-DRM-E PLC ISA bus compatible board card
  • OMRON C500-CT012 PLC
  • OMRON C500-NC103-E PLC
  • OMRON C500-NC222-E PLC
  • OMRON C500-PRW05-V1 PLC
  • OMRON C500-PRW06 PROGRAMMABLE CONTROLLER
  • OMRON C500-PS223-E 3G2A5-PS223-E PLC SYSMAC PROGRAMMABLE CONTROLLER
  • OMRON C500-TU001 3G2A5-TU001 PLC PLC
  • OMRON C60H-C1DR-DE-V1 Programmable Controllers
  • OMRON C60H-C5DR-DE-V1 Programmable Controllers
  • OMRON C60H-C6DR-DE-V1 Programmable Controllers
  • OMRON CJ1G-CPU44H CPU module
  • OMRON CJ1G-CPU45H PLC
  • OMRON CJ1M-CPU13-ETN V4.0 PLC PLC
  • OMRON CJ1W-AD041-V1 Analog input uni
  • OMRON CJ1W-CORT21 PLC module
  • OMRON CJ1W-IDP01 Input unit
  • OMRON CJ1W-MCH71 - MECHATROLINK-II
  • OMRON CJ1W-MD261 Digital I/O
  • OMRON CJ1W-NC413 Position control unit
  • OMRON CJ1W-NCF71 Position Control Units
  • OMRON CJ1W-PTS51 Process Simulation I/O Module
  • OMRON CJ1W-PTS52 Process Simulation I/O Module
  • OMRON CJ1W-SCU21-V1 PLC
  • Omron CJ1W-SCU22 Serial Communication Unit
  • OMRON CJ1W-TC001 CJ Series Temperature Control Unit
  • Omron CK3W-AX1515N Motion Controller
  • Omron CP1E-N60DR-D Compact PLC CPU
  • OMRON CP1E-NA20DT1-D PLC PLC
  • OMRON CP1H-X40DT-D plc PLC
  • OMRON CPM2C-S110C-DRT Interface module
  • OMRON CQM1-AD041 PLC
  • SAACKE F‑GDSA‑1 / F‑GDSA‑2 Feuerungsautomaten
  • SAACKE F-GDSA 143303 Controller SHIPS UPS
  • ICS Triplex T8270 Trusted 24 Vdc FanAssembly
  • SCHNEIDER M522220000 SA SM_DO16R 16 DIGITAL OUTPUTS MODULE
  • LENZ EPL10200-W EPZ-10203 CANPT010W3E
  • OMRON CQM1H-ADB21 PLC
  • OMRON CQM1H-CPU61 PLC
  • OMRON CQM1H-MAB42 PLC
  • OMRON CQM1-TC102 CQM1-TC101 PLC
  • OMRON CS1G-CPU44-EV1 PLC
  • OMRON CS1G-CPU44H CPU
  • OMRON CS1H-CPU63-EV1 PLC
  • OMRON CS1H-CPU66-V1 PLC
  • OMRON CS1W-CLK13 PLC communication module
  • OMRON CS1W-EIP21 PLC
  • OMRON CS1W-MAD44 PLC PLC
  • OMRON CS1W-SCU31-V1 CVM1-BC103 PLC
  • Omron CVM1-CPU21-V2 CPU Unit
  • OMRON F150-C10E-2 Vision Controller
  • OMRON F150-C15E-3 Vision Controller
  • OMRON F160-C15E VISION MATE CONTROLLER
  • OMRON F500-C10-ETN F500-C15-ETN Vision Sensor
  • OMRON F500-VS F500-S1
  • OMRON FH-3050 FH Vision Controller
  • Omron FQ2-S25050F PLC Smart Camera
  • Omron FQM1-MMA22 Motion Module