DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

schneiderInstruction MI 021-390 February 2016 I/A Series® Magnetic Flow Transmitter Model IMT25 Operation, Configuration, and Calibration

From:schneider | Author:LIAO | Time :2025-08-22 | 558 Browse: | 🔊 Click to read aloud ❚❚ | Share:

1. Introduction

Description

An I/A Series Magnetic Flowmeter System consists of two major components: 

 IMT25 Magnetic Flow Transmitter with Version 2 Software

 Magnetic Flowtube

 8000A wafer body

 2800, 8300, 9100A, 9200A, or 9300A flanged body

A system may be specified with the transmitter integrally mounted with the flowtube or with a 

remote mounted transmitter, which can be mounted either on a pipe or a flat surface.

Your transmitter has one of three communication protocols.

One is a FoxCom communications protocol. The digital output signal in this version is used 

for flowmeters serving as a primary measuring device in an I/A Series system. You can 

communicate with this version via the I/A Series system, the PC-based Configurator, or the 

optional local keypad/display.

Another has HART communications capability. You can communicate with this version via a 

HART Communicator, PC-Based Configurator, or the optional local keypad/display. 

The third has FOUNDATION fieldbus communication capability. You can communicate with 

this version via a fieldbus host or the optional local keypad/display.

This document describes local operation, configuration, and calibration of an IMT25 Transmitter 

supplied with local keypad and display. For information on operation, configuration, and 

calibration from a PC-Based Configurator, a HART Communicator, or a FOUNDATION fieldbus 

host refer to the documents listed in “Reference Documents” on page 13.

Intended Audience

This document is intended for use by process operators, engineers, and instrument technicians. If 

you are interested only in operation, read the general information in the Introduction and the 

chapter titled Operation. If you are interested in calibration, read the Introduction and chapters 

titled Operation and Calibration. If you are concerned with configuration, read the entire manual, 

with special emphasis on the chapter titles Configuration and the structure diagrams in 

Appendix A and the configuration worksheets in Appendix B.

Functions

Using the IMT25 front panel keypad/display, the functions you can perform are:

Operating Functions

 Display Measurement Information: The current value of the flow rate in engineering 

units (EGU), flow rate in percent of upper range value (URV), the Forward Total, 

Reverse Total, Net Total, and Grand Total.

 Display the Status of the Transmitter: The current operating mode, Analog and Pulse 

Output values, Contact Input settings, Relay Output settings, noise reduction, 

AutoZeroLock information, and write protection as well as alarm and diagnostic 

status.

 Display Identity Information: Tag, description, and message plus identification data 

for the flowmeter, flowtube, and transmitter software.

 Acknowledge Alarms and Diagnostic Conditions.

 Reset Totals.

Calibration Functions

NOTE

These functions can be passcode protected from keypad changes.

 Adjust the 4 and 20 mA output signal (requires additional equipment)

 Preset outputs to calibrate control loop

 Calibrate the AutoZeroLock Detector

Configuration Functions

NOTE

These functions can be passcode protected from keypad changes.

 Display and modify all configuration parameters

 Assign passcodes and set levels of privilege

Reference Documents

This document addresses operation, configuration, and calibration using the local keypad/display 

panel. For remote communication with your transmitter and other details of the flowmeter, refer 

to the applicable documents listed in Table 1

2. Quick Start

FoxCom or HART Protocol

Your IMT25 Transmitter can be configured with a PC-Based Configurator or with the 

keypad/display option. With the keypad/display, two configuration menus exist, Quick Start and 

Setup. Most basic applications can be configured in Quick Start mode.

Quick Start mode can be used for applications requiring only:

 A 4-20 mA output based on a flow rate in (US) GPM

 The transmitter display to show a flow rate in (US) GPM

 A FoxCom digital or HART flow rate signal.

Use Setup mode that is fully described in “Configuration” on page 39, for applications involving:

 Transmitters powered from 50 Hz sources

 Pulse and frequency outputs

 Totalizer functions

 Flow units other than (US) GPM

 Alarm functions

 Multi-range or bi-directional flow configurations.

To make Quick Start changes to the configuration, go to 1 TOP LEVEL/Quick Start by 

pressing the Left arrow repeatedly until the display reads 1 TOP LEVEL. Then use the up/down 

arrow keys to go to 1 TOP LEVEL/Quick Start. The procedure to change your configuration is 

demonstrated by the following example: 

 Flowmeter factor of 18.22 (refer to “Determining the Meter Factor” on page 18)

 Forward direction of flow

 Flow Range 0 to 150 GPM

1. Use the Right arrow key to move to MFACTOR FORMAT? {###.######}. This format 

can be changed, if necessary, to accommodate the meter factor.

a. If no change is required, press the Right arrow key.

b. To change the format, press Shift + Change to enter Edit Mode. Then use the 

up/down arrow keys to step through the choices. When you reach the format you 

want, press the Right arrow key.

2. The display reads METER FACTOR? {###.######} (Default {012.000000}). Press 

Shift + Change to enter Edit Mode. Use the Right/Left arrow keys to move the 

cursor under the digits you want to change. Use the up/down arrow keys to change 

the digits to the desired values. In the case of this example, continue this procedure 

until the display reads [018.220000]. Use the Right arrow key to move the cursor 

out past the right bracket to save the setting. The display then reads METER FACTOR?

{018.219998}. Note that in some cases, as with this example, a slightly different

value will appear. The magnitude of this difference is insignificant. Press the Right 

arrow key again. 

NOTE

To determine the correct meter factor, refer to “Determining the Meter Factor” on 

page 18.

3. The display reads RATE FORMAT? {#####.#} This format can be changed, if 

necessary, to accommodate your flow rate.

a. If no change is required, press the Right arrow key.

b. To change the format, press Shift + Change to enter Edit Mode. Then use the 

up/down arrow keys to step through the choices. When you reach the format you 

want, press the Right arrow key.

4. The display reads FORWARD URV? {#####.#} (Default {00100.0}). Press Shift + 

Change to enter Edit Mode. Use the Right/Left arrow keys to move the cursor under 

the digits you want to change. Use the up/down arrow keys to change the digits to the 

desired values. In the case of this example, continue this procedure until the display 

reads [00150.0]. Use the Right arrow key to move the cursor out past the right 

bracket to save the setting. The display then reads FORWARD URV? {00150.0}.

5. Now that all changes have been made, press the Right arrow key. You are asked Go 

On-Line? Reply Yes by pressing the Right arrow key. Press the Right arrow key again 

to begin displaying flow measurements.

Foundation Fieldbus Protocol

Your transmitter has been preconfigured at the factory to the settings shown in Appendix B. 

Compare your needs to the factory configuration and note the changes to the configuration you 

must make.

If the transmitter is not connected to a flowtube or IMTSIM, it is necessary to put a jumper wire 

between terminals Coil 1 and Coil 2 and also to provide power to the transmitter.

This section describes the procedures to quick start the transmitter from the optional local 

keypad/display. Note that after you quick start the transmitter from the local keypad, you should 

use the fieldbus host to ensure that parameter values associated with the host are changed to agree 

with those changed from the local keypad/display. Otherwise, mismatch errors occur when you 

attempt to place the transmitter into Auto mode.

To make changes to the configuration using the local keypad/display, go to 1 TOP LEVEL/Setup

by pressing the Left arrow repeatedly until the display reads 1 TOP LEVEL. Then use the 

Up/Down arrow keys to go to 1 TOP LEVEL/Setup. The procedure to change your 

configuration is demonstrated by the following example: 

 Engineering units (EGUs) in GPM (factory default setting)

 Forward direction of flow (Unidir positive - factory default setting)

 Flow range 0 to 150 GPM

 Flowmeter factor of 18.22 (refer to “Determining the Meter Factor” on page 18)

  1. Note that the factory default engineering units is already configured as GPM, so no change is required. 2. Note that the factory Output mode is also already configured as UniDir positive, so no change in the direction is required. 3. You must enter your flow upper range value however. To do this: a. Go to Setup Level 2 by pressing the Right arrow key. Next move to 2 SETUP Outputs with the Down arrow key. Then move to 3 OUTPUTS Output Mode with the Right arrow key

b. Use the Down arrow key to go to 3 OUTPUTS Range Info and the Right arrow 

key to go to FORWARD URV? {#####.#} GPM (Default {00100.0}).

c. Press the Shift + Change keys to enter Edit mode. You are asked Go Offline?

Reply Yes by pressing the Right arrow key. The display shows FORWARD URV?

[#####.#] GPM.

d. Use the Right/Left arrow keys to move the cursor under the digits you want to 

change. Use the Up/Down arrow keys to change the digits to the desired values. In 

the case of this example, continue this procedure until the display reads 

[00150.0].

e. Using the Right arrow key, move the cursor under the right bracket and press the 

key to enter the URV. The display reads FORWARD URV? {150.0} GPM. 

f. Press the key again to move back to 3 OUTPUTS Range Info.

4. Lastly, you have to enter your flowmeter factor. To do this:

a. Use the Left arrow key to move to the Level 2 menu, 2 SETUP Outputs.

b. Press the Down arrow key six times to move to 2 SETUP Calibration and the 

Right arrow key to move to the Level 3 menu, 3 CALIBRATION Meter Factor. 

See FIgure A-5.

c. Use the Right arrow key to move to MFACTOR FORMAT? {###.######}. This 

format can be changed, if necessary, to accommodate the meter factor.

d. Use the Right arrow key to move to METER FACTOR? {###.######} (Default 

{012.000000}. Then press Shift + Change to enter Edit mode.

e. Use the Right/Left arrow keys to move the cursor under the digits you want to 

change. Use the Up/Down arrow keys to change the digits to the desired values. In 

the case of this example, continue this procedure until the display reads 

[018.220000]. Use the Right arrow key to move the cursor out past the right 

bracket to save the setting. The display then reads METER FACTOR? 

{018.219998}. Note that in some cases, as with this example, a slightly different 

value appears. The magnitude of this difference is insignificant.

NOTE

To determine the correct meter factor, refer to “Determining the Meter Factor” on 

page 18.

f. Press the Right arrow key again. The display reads 3 CALIBRATION Meter 

Factor.

5. Now that all changes have been made, press the Left arrow key until you are asked Go 

On-Line? Reply Yes by pressing the Right arrow key. To display flow measurement, 

press the Right arrow key once more.

! CAUTION

If you change the upper range value or engineering units in the Transducer Block with 

the local display pushbuttons without making a corresponding change in the 

corresponding Analog Input Blocks from a fieldbus host, a mismatch error occurs and 

the Analog Input Block reverts to Out of Service mode.

Determining the Meter Factor

First find the “Cal Factor” or “IMT25 Cal Fact” on the flowtube data label.

If the flowtube data label has a “IMT25 Cal Fact.” listing, use that value as the “Meter Factor.”

If only a “Cal Factor” value is found on the flowtube data label, that value must be multiplied by 

the appropriate factor from Table 2 to calculate the “Meter Factor.”

Operation from Keypad/Display Panel

For local operation, configuration, and calibration, all operator entries are made through a 

5-button keypad and all data is presented on a 2-line x 16 character LCD display. The 

keypad/display of the IMT25 Transmitter is shown in Figure 1. Information on various types of 

display is shown in Figure . 

Figure 1. IMT25 Magnetic Flow Transmitter — Keypad/Display

All required functions are accomplished by using the four arrow keys alone and in combination 

with the Shift key. Table 4 explains the function of each key

Top Level Menu

The Top Level menu displays the following modes – Measurements, Status, Identity, Quick Start 

(in FoxCom and HART transmitters), Test Mode, and Setup. You can switch from one to another 

in sequence by using the Up/Down arrow keys. To enter the second level menu from a particular 

top level screen, press the Right arrow key. To return to the top level from a second level menu 

item, press the Left arrow key. The level of the first, second, third, and fourth level menus is 

indicated by the digit appearing as the first character in Line 1 of the display; a 1 indicates Level 1 

(Top Level), a 2 indicates Level 2, and a 3 indicates Level 3, etc.

The top level menu is shown in Figure 3. For a complete presentation of all menu structures, refer 

to Appendix A.

Measurements Mode

The Measurements mode, which is your main operating mode, is displayed upon startup. 

Depending on the transmitter configuration, it has up to seven displays, any of which may be set 

as the startup default. All screens can be scrolled with the Up/Down arrow keys.

 Rate (EGU) — Shows current flow rate (forward or reverse) in the selected 

engineering units. 

 Rate (% Range) — Shows current flow rate (forward or reverse) as a percentage of full 

scale URV.

 Fwd Tot — Shows current value of the forward totalized flow in engineering units. 

Use the Net Tot display to reset.

 Rev Tot — Shows current value of the reverse totalized flow in engineering units. Use 

the Net Tot display to reset.

 Net Tot — Shows current value of the net totalized flow (forward total - reverse total) 

in selected engineering units. Press Shift + Reset to reset the displayed total to 

zero. Resetting Net Tot also resets Fwd Tot and Rev Tot. It does not reset Gr Tot. 

If Reset Totals is passcode protected, the message Enter Passcode appears.

 Grand Tot — Shows current value of the grand total flow in engineering units. Press 

Shift + Reset to reset the displayed total to zero. Resetting Gr Tot does not reset 

Fwd Tot, Rev Tot, and Net Tot. If Reset Totals is passcode protected, the message 

Enter Passcode appears.

If the Dual Display feature is configured On, a combination of two of these parameters can be 

displayed at once. A typical dual display, in which Line 1 shows flow rate and Line 2 shows the 

present forward total, is shown below. Units may not be displayed or may be truncated. 

You may step through the displays of each of these parameters with the Up and Down arrow keys. 

However, unless you specifically do so, the display defaults to that configured in Setup mode. The 

engineering units and formats used in the displays are also configured in Setup mode.

Status Mode

The Status mode enables you to view fourteen system parameters and thus assess the performance 

of the loop. You may not edit them in this mode. To step through the displays of the following 

parameters, use the up/down arrow keys: 

 Mode — Shows the present operating mode: On-Line, Off-Line, Override, or 

Calibrate. This will normally display On-Line. The other modes will only be 

displayed if someone else has changed the mode with an I/A Series Workstation,

PC-Based Configurator, HART Communicator, or fieldbus host. Off-Line means

that it has been taken off-line; Override, that the measurements cannot be relied 

upon because one or more of the outputs is at a preset value; and Calibrate, that the 

transmitter is in Calibration mode.

 Alarm — Shows the most current active alarm. If there are no active alarms but 

something is in the history buffer, the display reads Alarms In Buffer. If there are 

no active alarms and nothing in the buffer, display reads No Alarms. 

 Diagnostics — Shows No Diag, Diag Existed, or Diag Exists. If a diagnostic 

problem exists, the second line identifies the problem. Help is available with the 

Shift + Help keys. An active diagnostic problem cannot be cleared; the problem 

must be corrected. Diag Existed means a diagnostic error did occur, but the 

condition has cleared and the transmitter is working correctly. However, the Diag icon 

will remain on the display until the diagnostic has been acknowledged. To clear, the 

transmitter must be in the Status mode with the diag window displayed. Then use the 

Shift + Ack keys.

 Digital Output — If the transmitter output is in Digital Output mode, the display 

shows whether the transmitter is configured for Unidirectional or BiDirectional flow. 

If the transmitter is not in Digital Output mode, the screen is not displayed.

NOTE

Digital and Analog Output are mutually exclusive. Only one of the two are displayed 

at any one time.

 Analog Output — If the transmitter output is in Analog Output mode, the display 

shows whether the transmitter is configured for U (unidirectional), U/M1

(unidirectional multirange-range 1), U/M2 (unidirectional multirange-range 2, U/M3

(unidirectional multirange-range 3), B/D (bidirectional dual range), or B/S

(bidirectional split range). If the transmitter is not in Analog Output mode, the screen 

is not displayed.

NOTE

Digital and Analog Output are mutually exclusive. Only one of the two are displayed 

at any one time.

Table 5. Analog Output Configuration

Display Interpretation

U UniDirectional Flow Single Range

U/M1 UniDirectional Flow Multi-Range

Range 1 Active

U/M2 UniDirectional Flow Multi-Range

Range 2 Active

U/M3 UniDirectional Flow Multi-Range

Range 3 Active

B/D BiDirectional Flow Dual Range

B/S BiDirectional Flow Split Range

(mA reading less than 12 indicates reverse flow, greater than 12, 

positive flow)

**UNKNOWN** Multi-Range is configured, but both contact inputs used to select 

the active range are in inactive state

 AZL Detect (Empty Pipe Det) — The intent of the AutoZeroLock Detection 

(Empty Pipe Detection) feature is explained in “AutoZeroLock (Empty Pipe)” on 

page 53. 

If the AutoZeroLock (Empty Pipe) detector is configured On, the display shows:

EPD Inactive, EPD Active, or EPD Needs Setpnt (FoxCom)

AZL Inactive, AZL Active, or AZL Needs Setpnt (HART)

Inactive, Active, or AZL Needs Cal (Fieldbus).

When AZL (EPD) is active, the outputs are locked at zero. If AZL (EPD) is 

configured Off, the status display shows Off.

! WARNING

Do not take any action that can cause danger to personnel or damage to equipment 

based on the assumption that a pipe is empty or full because of an AutoZeroLock 

(Empty Pipe Detection) indication.

 AZL Count (Empty Pipe Cnt) — Shows the cumulative count (maximum of 255) of 

AZL (empty pipe) conditions that have occurred since the last reset. To reset the 

count to zero, press Shift + Reset Note that in some cases several counts may 

occur for one emptying of the pipeline.

 Noise Reduction — Shows whether the noise reduction function is configured On or 

Off.

Write Protection — Shows whether the Write Protection dip switch is in the On position so that 

no Setup (configuration) changes may be made. This feature is usually only used in custody 

transfer applications or for another reason that you want to assure that the configuration is not 

changed. For the procedure to change the setting of this switch, see MI 021-387.


  • AMAT 0190-17964 Etch DPS Interlock Module
  • AMAT 0190-17894 Interlock Module Conductor HART
  • AMAT 0190-17081 2U CompactPCI System Host Processor
  • AMAT 0190-16926 and 0190-16928 Based on Compact PCI
  • AMAT 0190-15915 Intelligent I/O Control Module
  • AMAT 0190-15840 4-Port UPA DeviceNet Interface Module
  • AMAT 0190-15384 Advanced Digital Signal Interface Module
  • AMAT 0190-14027 Wafer Flat Finder PCB
  • AMAT 0190-12695 SBS CL7 3U CompactPCI Single Board Computer
  • AMAT 0190-11817 CP3-SER16-TTL 16-Port Serial Interface Card
  • AMAT 0190-11524 CDN500-25 Interlock Module
  • AMAT 0190-07450 CompactPCI 48-Channel Digital I/O Interface Board
  • AMAT 0190-05990-001 Maglev Rotation System Controller (300mm)
  • AMAT 0190-05647 LK3710 Serial Module Transition Card
  • AMAT 0190-04457 High-Performance Integrated Circuit Control Module
  • Applied Materials (AMAT) 0190-04098 | 5.X Factory Interface I/O Distribution Board
  • Applied Materials (AMAT) 0190-03705 | MF Producer SE/E Interlock Module
  • Applied Materials (AMAT) 0190-02748 | Flex Scanner Transition Module
  • Applied Materials (AMAT) 0190-02362 | Mainframe Interlock 1 Relay Module
  • Applied Materials (AMAT) 0190-01227 | Intelligent Motor Control OMS Board
  • Applied Materials (AMAT) 0190-00318 | VME 486 Video Controller
  • Applied Materials (AMAT) 0130-14007 | Advanced RF Signal Assembly
  • Applied Materials (AMAT) 0130-14005 | RF Cable/Interface Assembly
  • Applied Materials (AMAT) 0130-01218 | High-Efficiency RF Interface Controller
  • Applied Materials (AMAT) 0110-77040 | Head Pneumatic Controller
  • Applied Materials (AMAT) 0110-00077 | Precision Control Module
  • AMAT 0101-57015 high-performance Next-Generation Deflection Amplifier Board
  • AMAT 0100-77040 critical Head Pneumatic Controller Board
  • AMAT 0100-76291 Data Buffer / Memory Expansion Interface
  • AMAT 0100-76290 Advanced I/O Interface Board
  • AMAT 0100-76269 Control Board / Interface Module
  • AMAT 0100-71462-01 high-performance Process Controller PCB
  • AMAT 0100-71171 Chamber Interlock Control PCB
  • AMAT 0100-71154 Semiconductor Circuit Board / Electronic Group Card
  • AMAT 0100-70034 PCB Assembly (PCBA) for Endpoint VGA I/O Interconnect.
  • AMAT 0100-38032 ESC (Electrostatic Chuck) Controller PCB
  • AMAT 0100-36035 DPS Source Match / Seriplex I/O Distribution PCB
  • AMAT 0100-35231 Seriplex I/O Distribution Module
  • AMAT 0100-35217 TC Amp Interlock PCB Module
  • AMAT 0100-35065 High-Precision Serial Isolator PCB
  • AMAT 0100-35054 Advanced Chamber Interface Module
  • AMAT 0100-20453 DeviceNet Digital I/O Interface Board
  • AMAT 0100-20100 High-Performance Semiconductor Component
  • AMAT 0100-20068 Precision CCD Image Control Board
  • AMAT 0100-20064 Advanced Semiconductor Control Module
  • Applied Materials (AMAT) 0100-20018 Advanced Communication Interface Module
  • Applied Materials (AMAT) 0100-20016 High-Performance Interface and Control Module
  • Applied Materials (AMAT) 0100-20003 Digital I/O (DI/DO) Interface Board
  • Applied Materials (AMAT) 0100-20001 System Electronics Interface (SEI) / PCB Assembly
  • Applied Materials (AMAT) 0100-11030 Chamber Hardware / Gas Distribution Component
  • Applied Materials (AMAT) 0100-11022 Semiconductor Board Card
  • Applied Materials (AMAT) 0100-11018 Advanced Interface Control Module
  • Applied Materials (AMAT) 0100-11001 Precision Analog Output Board
  • ​Applied Materials (AMAT) 0100-11000 High-Precision Analog Input Board
  • Applied Materials (AMAT) 0100-09237 Advanced Signal Interface Module
  • Applied Materials (AMAT) 0100-09204 Advanced Digital Interface Control Board
  • Applied Materials (AMAT) 0100-09172 High-Density Digital I/O Control Board
  • Applied Materials (AMAT) 0100-09137 High-Performance VME Control Module
  • Applied Materials (AMAT) 0100-09054 Precision Analog Input Board
  • Applied Materials (AMAT) 0100-09029 Turbo Interconnect Interface Module
  • AMAT 0100-03391 Precision Semiconductor Control
  • AMAT 0100-01984 | VME System Interface & Logic Controller Board
  • AMAT 0100-01363 | VME Intelligent System Control & I/O Board
  • AMAT 0100-01321 | VME DeviceNet Scanner / Interface Board
  • AMAT 0100-00793 | VME Multi-Channel Interface & Logic Board
  • AMAT 0100-00689 | VME PCB Power Module
  • AMAT 0100-00580 | VME Intelligent System Controller Board
  • AMAT 0100-00523 | VME Multi-Channel Analog-to-Digital (A/D) Board
  • AMAT 0100-00493 | VME Multi-Function System Controller Board
  • AMAT 0100-00398 | VME Interface System Control Board
  • AMAT 0100-00369 | VME 12-Channel High-Speed Stepper Motor Controller
  • ​AMAT 0100-00196 | VME System Mainframe CPU Controller Board
  • AMAT 0100-00169 | VME 12-Channel Stepper Motor Controller Board
  • AMAT 0100-00162 | VME Dual Channel Serial Communication Board
  • AMAT 0100-00137 | VME Stepper Motor Controller Interface Board
  • AMAT 0100-00075 | VME Digital Input/Output (DI/O) Interface Board
  • AMAT 0100-00007 VME Analog Input/Output Interface Board
  • AMAT 0100-00002 | VME Slave I/O Interface PCB
  • AMAT 0090-05596 High-Voltage DC Power Cable Assembly
  • AMAT 0090-01809 | High-Performance RF Power Cable Assembly
  • AMAT 0010-29958 | CCM HART 3 Mainframe Control Assembly
  • AMAT 0010-20003 System Controller Card Cage Assembly
  • AMAT 0010-11239 PVD High-Voltage Power Interface Assembly
  • AMAT 0010-09416 RF Matching Network Assembly
  • AMAT 0010-00019 Analog Power Supply Assembly
  • AMAT AS00009-02 (31-000-00940) | Precision Semiconductor Component
  • AMAT 0010-00028 Power Supply Module
  • AMAT 0330-1586A Serial Communication PCB
  • AMAT 0190-09690 Seriplex SENSORbus SPX-MUXADIO-001
  • AMAT 0190-04397 DeviceNet I/O Interface Board
  • AMAT 0190-02506 DeviceNet I/O Interface Card
  • AMAT 0090-00475 Seriplex 210 MUXADIO
  • AMAT 410-0198-1 Multi-Output Switching Power Supply
  • AMAT 0100-20458 high-reliability Configurable Interlock Personality Board
  • AMAT VAS104350-0415 Gasline Heater Control Unit
  • AMAT VME6U1V2 VMEbus Backplane Interface Module
  • AMAT 0920-01070 high-performance RF Power Generator
  • AMAT 0090-76133A VME Single Board Computer (SBC)
  • AMAT 0190-24115 DeviceNet I/O Interface Card
  • AMAT 0190-37607 Backplane / Base Board Assembly
  • AMAT 0190-32372 Analog Input/Output (I/O) Board
  • AMAT 0190-09956 Loadlock Interface PCB Base Assembly
  • AMAT 0190-07908 four-channel DeviceNet Interface Card
  • AMAT 0190-07905 (UPS) control board
  • AMAT 0190-07502 Precision Controller / Interface Board
  • AMAT 0190-03680 I/O Backplane
  • AMAT 0190-02200 Water Leak Detection Control Board
  • AMAT 0100-76124 Digital I/O Board Assembly
  • AMAT 0100-35563 Leak Detector Configuration PCB
  • AMAT 0100-35250 Chamber Interface DPS Centura PCB
  • AMAT 0100-35124 Seriplex I/O Distribution Board
  • AMAT 0100-35058 Loadlock Interlocks PCB
  • AMAT 0100-20213 RF Match Detector PCB
  • AMAT 0100-20063 Interface PCB Assembly
  • AMAT 0100-09225 TC AMP/INTERLOCK PCB
  • AMAT 0100-09153 Gas Panel Interface PCB
  • AMAT 0100-09127 Loader Interconnect Board
  • AMAT 0100-09009 Buffer I/O PCB Card
  • AMAT 0100-02813 Signal Conditioning Board
  • AMAT 0100-01911 AC Gas Heater Control Board
  • AMAT 0100-01708 Pedestal Integration PCB
  • AMAT 0100-00658 300mm RTP Controller Distribution PCB
  • AMAT 0100-00582 Gas Panel Controller Backplane
  • AMAT 0100-00049 Analog Signal Conditioner
  • AMAT 0100-00008 Control Interface Module
  • AMAT 0090-03402 DC Power Supply / Power Module
  • AMAT 0090-01248 DC Power Supply / Power Module
  • AMAT 0090-76109 RF Matching / Capacitor Assembly