• IGP10 for compact light weight and direct-to-process
mounting (bracket optionally available)
• IGP20, bracket mounted, for lower ranges, more
material options, and vacuum service
• Field-proven silicon strain gauge technology
• Corrosion-resistant epoxy finish
• Accuracy to ± 0.07 % of span
• Ambient temperature effects to ± 0.2 % URL
per 55 °C (100 °F) change
• Intelligent FOXCOM & HART / 4 to 20 mA version
or economical 4 to 20 mA version
• LCD Indicator / Pushbutton Configurator
to set zero, span, display units, etc.
Optional on Digital / 4 to 20 mA version,
Standard on 4 to 20 mA version
These Intelligent, two-wire transmitters provide precise, reliable, measurement of gauge or absolute
pressure, and transmit a 4 to 20 mA output signal
with a superimposed HART/ FOXCOM digital signal for remote configuration and monitoring.
IGP10 Span, Range and Overrange Limits
IAP10 Span, Range and Overrange Limits
Span
Limits
Code
Span Limits Range Limits Maximum Overrange
kPa psi bar
(kg/cm²) kPa psi bar
(kg/cm²) kPa psi bar
(kg/cm²)
C 7 & 210 1 & 30 0.07 & 2.1 0 & 210 0 & 30 0 & 2.1 310 45 3.15
D 70 & 2100 10 & 300 0.7 & 21 0 & 2100 0 & 300 0 & 21 3100 450 31.5
E 700 & 21000 100 & 3000 7 & 210 0 & 21000 0 & 3000 0 & 210 31000 4500 315
IGP20 Span, Range and Overrange Limits
Span
Limits
Code
Span Limits Range Limits Maximum Overrange
kPa psi bar
(kg/cm²) kPa psi bar
(kg/cm²) kPa psi bar
(kg/cm²)
B 0.87 & 50 0.125 & 7 0.0087 & 0.5 –50 & 50 –7 & 7 –0.5 & 0.5 25000 3625 250
C 7 & 210 1 & 30 0.07 & 2.1 –100 & 210 –14.7 & 30 –1 & 2.1 25000 3625 250
D 70 & 2100 10 & 300 0.7 & 21 –100 & 2100 –14.7 & 300 –1 & 21 25000 3625 250
E 700 & 21000 100 & 3000 7 & 210 –100 & 21000 –14.7 & 3000 –1 & 210 25000 3625 250
Temperature Limits
Fill fluid
Flourinert
Fill fluid
Silicone
Ambient: –29 to 85 °C
(–20 to 185 °F)
–40 to 85 °C
(–40 to 185 °F)
Sensor: –29 to 121 °C
(–20 to 250 °F)
–46 to 121 °C
(–50 to 250 °F)
Gauge, Abs. and d/p Pressure
Accuracy (Includes Linearity, Hystersis, and
Repeatability)
Electronics
Version
Configured
Output Signal
Accuracy in %
of Calib. Span
-D & -T Digital
4 to 20 mA
± 0.07
± 0.1
-I 4 to 20 mA ± 0.2
Ambient Temperature Effect
Total effect for a 55 °C (100 °F) change within Normal Operating Conditions limit is:
Electronics -D, -T: ± 0.2 % of URL
Electronics -I: ± (0.2 % of URL + 0.1 % of span)
For complete specifications, refer to Product Specification
Sheet PSS 2A-1C13 B
Model Codes IGP10
Ambient Temperature Effect
Total effect for a 55 °C (100 °F) change within Normal Operating Conditions limit is:
Electronics -D, -T: ± 0.2 % of URL
Electronics -I: ± (0.2 % of URL + 0.1 % of span)
For complete specifications, refer to Product Specification
Sheet PSS 2A-1C13 B
Gauge, Abs. and d/p Pressure IGP10 - IGP20 - IAP10
CA 2A-1C13 B-(en) 09/1999
1-2
Intelligent Direct Connected Gauge Pressure Transmitter IGP10
Electronics Versions and Output Signal
Intelligent; Digital FoxCom and/or 4 to 20 mA dc, Configurable . . . . . . . . . . . . . . -D
Intelligent; Digital HART and 4 to 20 mA . . . . . . . . . . . . . . . . . . . . . . . . . -T
4 to 20 mA Analog Output, Explosionproof and Intrinsically Safe . . . . . . . . . . . . . -I
Structure Code - Process Connection, Sensor, and Fill Fluid
Process Connection Mat’l Sensor Fill Fluid
316L ss Co-Ni-Cr Silicone. . . . . . . . . . . . . . . . . . . . . . . . 20
316L ss Co-Ni-Cr Fluorinert . . . . . . . . . . . . . . . . . . . . . . . 21
316L ss 316L ss Silicone . . . . . . . . . . . . . . . . . . . . . . . 22
316L ss 316L ss Fluorinert. . . . . . . . . . . . . . . . . . . . . . . 23
Span Limits - Absolute or Gauge Pressure Units, as Applicable
MPa psi bar or kg/cm²
0.007 and 0.21 1 and 30 0.07 and 2.1..............................C
0.07 and 2.1 10 and 300 0.7 and 21 ..............................D
0.7 and 21 100 and 3000 7 and 210 .............................E
Conduit Connection
1/2 NPT Conduit Connection, Both Sides ...................................1
PG 13.5 Conduit Connection, Both Sides (available only with Electrical Safety CodesE&N .........2
Electrical Safety (See Electrical Safety Specifications Section)
CENELEC Certified Intrinsically Safe, ia ......................................E
CSA Certified ....................................................N
EUROPEAN Ex, N, IIC. Nonsparking ........................................C
FM Approved ....................................................F
SAA Certified, EEx, d, IIC ..............................................A
Options
Mounting Bracket Set
Painted Steel Bracket with Plated Steel Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M1
Stainless Steel Bracket with Stainless Steel Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M2
Digital Indicator with Pushbuttons (standard equipment on IGP10-I)
Digital Indicator, Pushbuttons, and Window Cover (for Electr VersionD&T only) . . . . . . . . . . . . . . . . . . . . . -L1
Vent Screw and Block & Bleed Valve
Vent Screw in Process Connection for IGP10/IAP10; or in High Side Process Cover for IGP20. . . . . . . . . . . . . . . V1