ABB UNS4684A-P,V.1 HIEE305114R00R0001 Overvoltage protection (OVP) and pulse coupling panel (PCP) module
The ABB UNS4684A-P, V.1 (Part Number: HIEE305114R0001) is a specialized Overvoltage Protection (OVP) and Pulse Coupling Panel (PCP) module.
It is a critical component within the UNITROL 6000 and UNITROL 5000 excitation systems, designed to protect the generator’s rotor and excitation circuit from transient overvoltages.
Introduction
In large power generation systems, the UNS4684A-P serves as a hardware guard.
It monitors the voltage levels in the excitation circuit and, upon detecting a dangerous surge or overvoltage (often caused by grid faults or load rejection),
triggers protection mechanisms—such as firing a "crowbar" circuit—to safely dissipate the energy and prevent damage to the thyristor bridges and generator rotor.
Technical Parameter Table
| Parameter | Specification |
| Model Number | UNS4684A-P, V.1 |
| Order Code | HIEE305114R0001 |
| Functional Role | Overvoltage Protection (OVP) / Pulse Coupling |
| System Family | UNITROL 6000 / UNITROL 5000 |
| Product Type | Printed Circuit Board Assembly (PCBA) |
| Weight | Approximately 0.31 kg (Net) |
| Dimensions | 320 mm x 230 mm x 37 mm (Standard Eurocard) |
| Country of Origin | Sweden |
| Mounting | Subrack-mounted / Plug-in module |
Galvanic Isolation: High-voltage isolation between the monitoring circuit and the control logic to ensure system safety.
Precision Coupling: Features pulse coupling capabilities to ensure that trigger pulses reach the protection thyristors (crowbar) reliably.
Mill-Duty Build: Engineered to survive the high-heat and high-electromagnetic interference (EMI) environments of power plant turbine halls.
Standardized Revision (V.1): High backward compatibility with established UNITROL 5000 and 6000 subracks.
Application Cases
Hydropower Plants: Protecting the excitation system during rapid load changes typical in hydro-governing.
Thermal/Nuclear Power: Serving as the final line of defense for the rotor circuit against "out-of-step" conditions.
Static Excitation Systems (SES): Integrated into high-current SES (up to 12.000A) where overvoltage events can be catastrophic.
Field Discharge Systems: Coordinates with the field breaker to ensure safe de-excitation of the generator during emergency trips.
Installation and Maintenance
Installation
Static Safety: This module is highly sensitive to Electrostatic Discharge (ESD). Use an grounded wrist strap and antistatic mat during handling.
Slot Alignment: Carefully align the PCB with the guide rails in the UNITROL rack. Forced insertion can damage the high-density backplane connector.
Tightening: Secure the front-panel captive screws to ensure a solid ground path and mechanical stability against vibration.
| ABB | EHDB280 |
| ABB | EI803F |
| ABB | FI830F |
| ABB | HK-11 |
| ABB | IMDSI14 |
| ABB | IMDSO14 |
| ABB | IMFEC12 |
| ABB | IMMFP12 |
| ABB | IMMPI01 |
| ABB | IMSED01 |
| ABB | IMSET01 |
| ABB | INNIS01 |
| ABB | INNPM12 |
| ABB | L110-24-1 |
Maintenance
Visual Inspection: During outages, check for signs of "thermal stress" (discoloration) on the board, especially near the high-voltage coupling components.
Testing: Use the UNITROL Service Tool (e.g., CMT6000) to verify that the OVP logic is communicating correctly with the Central Unit.
Cleaning: Use only dry, compressed air to remove dust; never use liquid cleaners on the PCB traces.
Other Models in the Same Series
Model Description
UNS 0890 A01 Snubber Control Interface (SCI)
UNS 2880 B-P Main Control Board (COB) for Unitrol 5000
UNS 2881 A-P Signal Measuring Unit (MUB)
UNS 0881 A-P Gate Driver Interface (GDI)
PVD164A Excitation Processor (often coordinates with the UNS4684A)
Peer Note: Because this module deals with Overvoltage Protection, a failure here often prevents the entire Excitation System from starting (Ready-to-Run interlock).
If you see an "OVP Fault" on the HMI, this board is the first place to look.