YOKOGAWA AVR10D-A22010 Bus Converter
The Yokogawa AVR10D-A22010 is a Duplexed V net Router (Bus Converter) used in the CENTUM VP Distributed Control System (DCS).
Its primary role is to bridge the gap between different network architectures, specifically connecting modern Vnet/IP domains to legacy V net or VL net domains.
1. Introduction
The AVR10D-A22010 acts as a "translator" and traffic manager between two generations of Yokogawa control networks.
It allows the latest Human Interface Stations (HIS) and Engineering Stations (ENG) residing on a high-speed Vnet/IP (Ethernet-based) network to monitor and control Field Control Stations (FCS) located on an older V net (Coaxial-based) or VL net network.
The "Duplexed" designation means it features redundant communication modules and power supplies for continuous operation.
2. Technical Parameter Table (A22010 Suffix)
| Feature | Specification |
| Model | AVR10D-A22010 |
| Communication (Vnet/IP Side) | 100 Mbps (Full Duplex) via RJ45 (CAT5e or higher) |
| Communication (V net Side) | 10 Mbps via Coaxial (BNC) |
| Suffix Code Breakdown | -A2: Dual-redundant VL net / 2: Dual Power Supply / 0: Fixed / 1: 100-120V AC Power / 0: Basic type |
| Input Power | 100 to 120 V AC (50/60 Hz) |
| Power Consumption | 80 VA |
| Max Distance (Vnet/IP) | 100 meters (to Layer 2 Switch) |
| Mounting | 19-inch Rack Mountable (Standard) |
| Weight | Approximately 2.5 kg (depending on configuration) |
3. Product Advantages and Features
Seamless Integration: Allows users to upgrade their operator consoles to CENTUM VP without having to replace their existing, functioning field controllers on the older V net.
Full Redundancy: Equipped with duplexed communication modules and duplexed power supplies. It supports "hot-swapping," meaning a module can be replaced while the router is online.
Deterministic Bridging: Ensures that the high-speed Vnet/IP data is properly synchronized with the 10 Mbps V net timing to maintain control integrity.
Diagnostic Transparency: Status and health information for both sides of the network are visible directly on the DCS monitoring screens.
Environmental Durability: Typically includes conformal coating (ISA G3) to withstand corrosive industrial gases.
4. Application Cases
Plant Modernization (Migration): A factory running an older CENTUM CS 3000 system wants to upgrade to CENTUM VP but wants to keep its existing wiring and controllers in place.
Multi-Domain Connectivity: Large facilities that have multiple "islands" of automation—some on modern Ethernet and some on legacy coaxial—need a central point to unify the data.
Geographical Expansion: Linking a newer plant extension (Vnet/IP) to an existing central control room that still uses the original V net backbone.
5. Related Models & Same Series
The AVR10D series varies primarily by its network interface and power requirements.
Other Models in the Same Series
AVR10D-Q22010: The version specifically for Dual-Redundant V net (10BASE-2 coaxial) instead of VL net.
AVR10D-A22020: The 220-240V AC version of the A22010.
AVR10D-A22040: The 24V DC power version, used in sites with battery backup systems.
Related System Components
VI451: Vnet/IP interface module for the controller side.
VC401: Vnet/IP interface card for the PC/HIS side.
YCB141: The specialized V net coaxial cable (10BASE-2) used to connect to the router.
| BALDOR | 803.93.00C |
| BALDOR | FD2A02TR-RN20 |
| BALZERS | IKR020 |
| BASEUS | CHBX01L |
| BASLER | SCA640-120GM |
| BASLER | A404KM-RT |
| Basler | DECS-200-2L |
| Basler | DECS-200-2L |
| BASLER ELECTRIC | BE3-25A |
| BAUMER | FHDK 14P5101/S35A |
| BAUMER | OADM 20I6572/S14F |
| BAUMER | UNDK30P3712/S14 |
| BAUMULLER | BUR622-16-2 |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|