have a free port for connecting your local programming panel The second port on
the 385E and D is for the Modbus Plus network Connection..
Figure 3 illustrated the controller from the left side. The MEM/DEFAULT/MODEM
toggle switch enables your preset communications configuration for Modbus port
1. (For software configuration, refer to software configurator in Panel software
documentation.)
The DIP switch for setting Modbus Plus port parameters is shown at the bottom of
the illustration but access to the DIP switch is actually through the bottom of the
modules ’ case.
Central Processing Unit (CPU) Function
The Model “E” uses 24 bit memory architecture and a 16 bit CPU which is fully
compatible with the Modicon 984 PC instruction set, solves user logic at a nominal
rate of 2.5 ms per thousand nodes of user logic. For special applications, a timeof-day clock is provided on all “E” Models.
Mainframe Status Indicators
Status indicators on the CPU module are:
POWER OK
READY
RUN
BATTERY LOW
MODBUS Port 1
MODBUS Port 2
Green LED: When ON, indicates input power OK and voltage outputs OK. Your l/O power OK is indicated by the
READY LED.
Amber LED: When ON, indicates Controller passed powerup diagnostics. Remains ON in Stopped and Run modes
as long as health status is OK. Indicator is OFF when an
error condition is detected by diagnostics.
Green LED: When ON, indicates Controller is in the RUN
mode and solving logic. If memory checksum fails this light
will blink 3 times for 5 seconds followed by a rest period of
2.5 seconds then the pattern repeats. The controller is in
Kernal mode and needs the executive reloaded.
Red LED: When ON, indicates battery needs to be replaced (14 day holdup from initial indication).
Green LED: When ON, indicates communication processor
has unit address and communications are in progress.
Green LED: When ON, indicates communication processor
has unit address and communications are in progress.
(The port 2 indicator is labeled MODBUS PLUS on the 385E and 385D and
indicates status as:)
MODBUS PLUS Green LED This LED displays a flashing repetitive pattern to indicate the node status:
NORMAL flashes every 160 msec.
MONITOR NETWORK flashes at one
second intervals. Is in offline state receive only.
NOT RECEIVING TOKEN flashes two times then is off for
two seconds.
SOLE STATION flashes three times then is off for 1.7 seconds.
DUPLICATE NODE ADDRESS flashes four times then is
off for 1.4 seconds.
Overview
The 381 E/385E and 385D Controller is designed to work with your Modicon Modsoft programming panel; Modicon 800 series housings, interfaces and I/O modules.
The site planner must also consider the peripheral equipment (such as a Programming panel, CRT monitor, or printer) when preparing an installation plan for
the site. Refer to the appropriate Modicon publications for site preparation procedures for related equipment.
Space Requirements
For the primary module housing, allow 12 inch clearance to the left so installer can
see power supply connectors. Allow 6 inches on the top and side of the housing
for convection cooling in vertical mounting situations. Allow 12 inch of clearance
at the bottom of the Controller for cable access.
For all other housings, allow 6 inches on the top and sides of each housing for unobstructed cooling airflow in vertical mounting situations.
Also consider installation and physical access for removal of the modules as well
as subsequent service including the connection and detachment of signal and
power cables when required.
The primary housing may be separated up to 12 feet from the secondary housing
depending only on the on the cable length employed.
Primary Power Lines
In addition to service access, distance to power sources has to be considered in
planning your controller installation. In addition to cable routing considerations,
good practices dictate that the power lines be dedicated to the PC installation to
minimize problems that sometimes arise when sharing AC power with electrically
noisy equipment.
Finally, plan to install a service loop and a cable restraint as the primary power
cable as the connector is not locked in place.
Environmental Requirements
In planning for controller installation, consideration should be given to the environment around the controller. Although designed for a harsh industrial environment
and able to withstand factors that would harm other types of electronic equipment,
problems can be avoided by not placing the controller and its related equipment in
an operating area where there is high ambient temperature, acidic atmosphere, vibration, dust, and dirt if it can be avoided.
Mounting Hardware Requirements
After deciding on the final location of the Controller, its associated equipment and