• 16-loop model: 16 single-ended inputs
Analog Over Voltage Protection
• ±20V referenced to digital ground
Maximum Common Mode Voltage
• 5V input to input or input to analog common
(4- and 8-loop models)
Common Mode Rejection (CMR)
• For inputs that do not exceed ±5V, >60dB dc to 1kHz and
120dB at selected line frequency
Noise Rejection
• 120dB at 60Hz
Sensors/Inputs
• Thermocouples: user-selectable type, direct connection,
linearization, reference junction compensation, reversed
and shorted thermocouple detection and upscale break
protection with output averaging
• RTD: (4 and 8 loop models only) 2- or 3-wire, platinum,
100Ω @ 0°C, DIN 0.003850Ω/Ω/°C curve, user-selectable
range. Two ranges offer different resolutions. Requires
scaling resistors. See ordering information.
• Linear: current and voltage signals from linear transmitters
• Pulse input
Input Range and Accuracy
Sensor Range (°C) Range (°F) Accuracy
Type B 66 to 1760°C 150 to 3200°F ±4.0°C
Type E -200 to 787°C -328 to 1448°F ±1.0°C
Type J -212 to 760°C -350 to 1400°F ±1.2°C
Type K -268 to 1371°C -450 to 2500°F ±1.3°C
Type R -18 to 1766°C 0 to 3210°F ±2.8°C
Type S -18 to 1760°C 0 to 3200°F ±2.8°C
Type T -268 to 399°C -450 to 750°F ±1.6°C
RTDs available on CLS204 and CLS208 only.
Sensor Range (°C) Range (°F) Accuracy
RTD1 -100 to 275˚C -148 to 527˚F ±1.1˚C
RTD2 -120 to 840˚C -184 to 1544˚F ±1.6˚C
Note: Accuracy @ 25˚C ambient. Valid for 10 to 100 percent
of span except Type B, which is specified for 800˚F to
3200˚F. RTD.
Linear Voltage and Current Inputs
Requires scaling resistors. See ordering information.
0-20mAVDC/4-20mAVDC
0-5VDC
0-10VDC
Temperature coefficient: 40ppm/°C
Other ranges available. Contact factory.
Pulse Input
• One TTL-level square wave input up to 2kHz
Input Sampling Rate at 60Hz
Each channel has the following scans per second:
• 4-loop model: 6 samples per second,
(update time: 0.167 sec.)
• 8-loop model: 3 samples per second,
(update time: 0.333 sec.)
• 16-loop model: 1.5 samples per second,
(update time: 0.667 sec.)
Internal Measurement Resolution
• 0.006 percent, greater than 14 bits
Calibration
• Automatic zero and full scale
Digital Inputs
• TTL-level used for selecting recipes or jobs, or R/S triggers
• 8 digital inputs and 1 pulse input with mass termination
(SCSI) digital I/O termination and TB50 terminal board
options
• 2 digital inputs and 1 pulse input with screw terminal
(TB18) digital I/O termination option
Digital Outputs
• 34 digital outputs with mass termination (SCSI) digital I/O
termination and TB50 terminal board options
• 11 control and alarm outputs with screw terminal (TB18)
digital I/O termination option
• 1 or 2 control outputs are user assigned for each loop
• Each control output can be configured for on-off time
proportioning, or distributed zero crossing
• Outputs sink up to 60mA each at 5VDC
• 350mA at 5VDC available from on-board supply
Alarm Outputs
• Independent process and deviation alarms for each
channel
• Alarms can operate any output not used for control
• User-programmable deadband, delay and startup
suppression
• Global alarm output activates when any alarm occurs
• Watchdog output indicates controller is functioning
correctly
Serial Interface
• EIA/TIA-232 or EIA/TIA-485
Baud Rate
• 2400, 9600 or 19200, user-selectable
Communications Protocols
• Form of ANSI X3.28-1976, (D1, F1) compatible with
Allen-Bradley PLC/2
• Modbus® RTU
Line Voltage/Power
• 15 to 24VDC ± 3VDC @ 1A (maximum),
300mA (no load)
Agency Approvals
• UL®, C-UL® listed: UL®61010-1 safety requirements for
measurement, control and laboratory equipment
• CE Mark: See Declaration of Conformity for details
• RoHS by design
Ordering Information
Instructions: Choose one option for each feature

Note: To obtain a part number for your choice of options, communicate your selections to your Watlow sales representative who
will provide a part number to you.