OPEN, SLIDE or LOCKED, which makes installation and removal of the base
plates very simple.
There are two ways of mounting the products concerned in cabinets, open rack or
other types of installations; aluminum profile with mounted DIN-rail, see Figure 14,
or DIN-rail mounted on a metal sheet of proper size, see Figure 15.

The aluminum profile or metal sheet shall be properly connected to protective earth.
DIN-rail type with height 7.5 mm shall be used. Refer to type NS 35/7.5 according
to standard EN 50022.
Figure 15. Mounted on Metal Sheet
It is not allowed to manipulate CEX bus base plates in a powered and running
system. Before changing or removing a base plate, all CEX modules on that
segment must be remove
The AC 800M and S800 I/O-units have protection class IP 20. If a higher IP class is
required, an additional enclosure is needed

Configuration
Using the Control Builder interface, it is possible to download controller firmware
and configure hardware (I/O and communication units). It is also possible to make
application programs with IEC61131-3 and compile and run programs off-line, as
an aid to process simulation, before finally downloading an application to the
controller.
The Control Builder interface is part of the Industrial IT 800xA System, which runs
on a PC and is normally connected to the AC 800M controller via the Control
Network, using the CN1 or CN2 port on the AC 800M controller. Alternatively, the
PC could be connected to the controller via the controller COM4 port (RS-232C). In
that case, use the tool cable TK212 and a serial port on the PC.
Note that a PM851/PM851A is restricted to one Ethernet (CN1) port, thus
redundant Ethernet is not available.
Note that Control Builder as standard does not support CI862. If CI862 is to be
used, suitable system extension must be installed.