KeConnect DI 240/B, DI 260/A
Digital input modules
Product features
• Up to 16 digital inputs
• 2 digital inputs with interrupt
• Electronic parameter chip
• Configurable input filter
Short description
The digital input module of the DI 2xx/x series enables the connection of 8 (DI 240/B) or 16 (DI 260/A) digital inputs.
24 V DC control signals are captured by the digital inputs and transmitted galvanically isolated to the higher-level automation device. In addition, two digital inputs can be used as interrupt inputs.
These modules are attached directly to a CPU module or can be operated with all KEBA controls by means of bus
couplers.
Digital inputs
DI 240/B DI 260/A
Number of inputs 8 16
Input type Type 1 (acc. to EN 61131-2)
Voltage range for "1" 15 V ≤ UH ≤ 30 V
Voltage range for "0" -3 V ≤ UL ≤ 5 V
Status display Green LED
Galvanic isolation Yes, electric strength 707 V with isolated ground connection
Cycle time 1 ms
Debouncing Configurable 1 ms, 100 ms
Interrupt inputs
Number of inputs 2 (DI0, DI1) of the digital inputs
Input type Type 1 (acc. to EN 61131-2)
Voltage range for "1" 15 V ≤ UH ≤ 30 V
Voltage range for "0" -3 V ≤ UL ≤ 5 V
Response time of the K-bus interrupt 100 μs with 5 kHz input filter
Status display Green LED
Galvanic isolation Yes
Dimensions, weight
Height 120 mm
Width 22.5 mm front plate / 32.5 mm incl. K-bus plug
Depth 100 mm
Weight 130 g
General
I/O supply voltage 24 V DC from K-bus
5 V DC from K-bus
Overvoltage category II
Protection class III acc. to EN 61131-2
Addressing on K-bus Via 16-digit address switch, on the side
Type of terminals Open - pitch 5.08 mm
Max. power consumption K-bus 24 V 1 W
Max. power consumption K-bus 5 V 0.4 W
Product features
• 8 or 14 digital outputs
• Short-circuit detection and diagnosis
• Permanently short-circuit proof
• Current load capacity 2 A at 50 % simultaneity
• Fast shutdown function for inductive loads
• Electronic parameter chip
Short description
Digital output modules DO 242/B and DO 272/A enable the connection of up to 14 digital outputs. The digital outputs
switch the 24 V DC control signals of a central module galvanically isolated from the connected actuators and are designed for a load of up to 2 A at 50 % simultaneity.
The modules are equipped with a fast shutdown function that enables a rapid shutdown of inductive loads, e.g., hydraulic valves. Machine processes can thereby be accelerated and productivity increased.
The operational safety is ensured by the permanent short-circuit protection of the outputs. Should a short circuit occur,
it is detected and reported to the control module.
These modules are attached directly to a CPU module or can be operated with all KEBA controls by means of bus
couplers
Digital outputs
DO 242/B DO 272/A
Number of outputs 8 14
Nominal voltage 24 V DC
Processing time 1 ms
Nominal current of digital outputs 2 A at 50 % simultaneity
Galvanic isolation Yes
Status display Orange LED
Protection facility Short-circuit protection
Max. inductive load 1 J at max 0.2 Hz
Dimensions, weight
Height 120 mm
Width 22.5 mm front plate / 32.5 mm incl. plug
Depth 100 mm
Weight 130 g
General
DO 242/B DO 272/A
Supply voltage 24 V DC from front (nominal voltage tolerance: 19.2 V … 30 V, acc. to EN 61131-2)
24 V DC from K-bus, 5 V DC from K-bus
Overvoltage category II
Protection class III acc. to EN 61131-2
Addressing on K-bus Via 16-digit address switch, on the side
Type of terminals Open - pitch 5.08 mm
Displays on the front plate 16 signal status LEDs
Max. power consumption K-bus 24 V 2.1 W 2.1 W
Max. power consumption K-bus 5 V 0.4 W 0.4 W
Environmental conditions
Operating temperature +5 °C … +55 °C
Storage temperature -40 °C … +70 °C
Relative air humidity 10 % to 95 % (non-condensing)
Vibration resistance / shock resistance Acc. to EN 61131-2
Product features
• Up to 8 digital inputs
• 8 digital 2 A outputs
• 2 digital inputs with interrupt
• Short-circuit detection
• Permanently short-circuit proof
• Electronic rating plate
Short description
The DM 27x/A series is a digital input/output module of the KeConnect C2 product line and enables the connection of 6
or 8 digital inputs and 8 digital outputs. 24 V DC control signals are captured by the digital inputs and transmitted galvanically isolated to the higher-level automation device. In addition, two of the digital inputs can be used as interrupt inputs.
The digital outputs switch the 24 V DC control signals of a CPU module galvanically isolated from the connected actuators. In addition to the short-circuit connection, outputs that cause short circuits can be switched off individually.
This module is attached directly to a CPU module or can be operated with all KEBA controls by means of a bus coupler.
Digital inputs
DM 272/A DM 276/A
Number / wiring of inputs 8x sink 6x source
Input type Type 1 (acc. to EN 61131-2)
Voltage range for "1" 15 V ≤ UH ≤ 30 V
Voltage range for "0" -3 V ≤ UL ≤ 5 V
Debouncing Configurable 1 ms, 100 ms
Cycle time 1 ms
Status display Green LED
Galvanic isolation Yes, electric strength 707 V with isolated ground connection
Interrupt inputs
Number of inputs Two of the digital inputs can be used as interrupt inputs