DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

ABBDistributed busbar protection REB500 including line and transformer protection Product Guide

From:ABB | Author:LIAO | Time :2025-08-28 | 412 Browse: | Share:

Distributed busbar protection REB500

including line and transformer protection

Main features • Low-impedance busbar protection

• Stub and T-zone protection

• High functional reliability due to two independent measurement criteria:

- stabilized differential current algorithm

- directional current comparison algorithm

• Phase-by-phase measurement

• Reduced CT performance requirements

• High through-fault stability even in case of 

CT saturation

• Full solid-state busbar replica

• No switching of CT circuits

• Only one hardware version for 

- 1 and 5 A rated currents

- all auxiliary supply voltages between 

48 V DC and 250 V DC

- nominal frequencies of 50, 60 and 

16.7 Hz

• Short tripping times independent of the 

plant’s size or configuration

• Centralized layout: Installation of hardware 

in one or several cubicles

• Distributed layout: Bay units distributed 

and, in the case of location close to the 

feeders, with short connections to CTs, isolators, circuit breakers, etc.

• Connections between bay units and central 

unit by fiber-optic cables

- maximum permissible length 1200 m 

- for distributed and centralized layout

• fiber-optic connections mean interferenceproof data transfer even close to HV power 

cables

• Replacement of existing busbar protection 

schemes can be accomplished without restrictions (centralized layout) in the case of 

substation extensions e.g. by a mixture of 

centralized and distributed layout

• Easily extensible

• User-friendly, PC-based human machine 

interface (HMI)

• Fully numerical signal processing

• Comprehensive self-supervision

• Binary logic and timer in the bay unit

• Integrated event recording

• Integrated disturbance recording for power 

system currents

• A minimum of spare parts needed due to 

standardization and a low number of varying units

• Communication facilities for substation 

monitoring and control systems via 

IEC 61850-8-1, IEC 60870-5-103 and LON

• IEC 62439 standard redundant station bus 

communication

• IEC 61850-9-2 LE process bus communication

• Cyber security to support

- User Access Management

- User Activity Logging

Options

• Breaker failure protection (also separately 

operable without busbar protection)

• End fault protection

• Definite time overcurrent protection

• Breaker pole discrepancy

• Current and voltage release criteria

• Disturbance recording for power system 

voltages

• Separate I0 measurement for impedancegrounded networks

• Communication with substation monitoring 

and control system (IEC 61850-8-1 /

IEC 60870-5-103 / LON)

• Internal user-friendly human machine interface with display

• Redundant power supply for central units 

and/or bay units

Additional 

main features

REB500sys combines the well-proven numerical busbar and breaker failure protection 

REB500 of ABB with Main 2 or back-up protection for line or transformer feeders. The 

Main 2 / Group 1 or back-up protection is 

based on the well-proven protection function 

library of ABB line and transformer protection 

for 50, 60 and 16.7 Hz.

Main 2 / back-up bay protection

• Definite and inverse time over- and undercurrent protection

• Directional overcurrent definite and inverse 

time protection

• Inverse time earth fault overcurrent protection

• Definite time over- and undervoltage protection

Distributed busbar protection REB500

including line and transformer protection

Page 3 

• Three-phase current and three-phase voltage plausibility

Main 2 / back-up bay protection: 

Line protection

• High-speed distance protection

• Directional sensitive earth fault protection 

for grounded systems against high resistive faults in solidly grounded networks

• Directional sensitive earth fault protection 

for ungrounded or compensated systems

• Autoreclosure for 

- single-pole / three-pole reclosure

- up to four reclosure sequences

• Synchrocheck with 

- measurement of amplitudes, phase 

angles and frequency of two voltage 

vectors

- checks for dead line, dead bus, dead 

line and bus

Group 1 / back-up bay protection: 

Transformer protection

• High-speed transformer differential protection for 2- and 3-winding and auto-transformers

• Thermal overload

• Peak value over- and undercurrent protection

• Peak value over- and undervoltage protection

• Overfluxing protection

• Rate of change frequency protection

• Frequency protection

• Independent T-Zone protection with transformer differential protection

• Power protection

Application REB500

The numerical busbar protection REB500 is 

designed for the high-speed, selective protection of MV, HV and EHV busbar installations 

at a nominal frequency of 50, 60 and 16.7 Hz.

The structure of both hardware and software 

is modular enabling the protection to be easily 

configured to suit the layout of the primary 

system.

The flexibility of the system enables all configurations of busbars from single busbars to 

quadruple busbars with transfer buses, ring 

busbars and 1½ breaker schemes to be protected.

In 1½ breaker schemes the busbars and the 

entire diameters, including Stub/T-Zone can 

be protected. An integrated tripping scheme 

allows to save external logics as well as wiring.

The capacity is sufficient for up to 60 feeders 

(bay units) and a total of 32 busbar zones.

The numerical busbar protection REB500 

detects all phase and earth faults in solidly 

grounded and resistive-grounded power systems and phase faults in ungrounded systems 

and systems with Petersen coils.

The main CTs supplying the currents to the 

busbar protection have to fulfil only modest 

performance requirements (see page 18). The 

protection operates discriminatively for all 

faults inside the zone of protection and 

remains reliably stable for all faults outside the 

zone of protection.

REB500sys

The REB500sys is foreseen in MV, HV and 

EHV substations with nominal frequencies of 

16.7, 50 Hz or 60 Hz to protect the busbars 

and their feeders. The bay protection functions included in REB500sys are used as 

Main 2 / Group 1 - or back-up protection.

The system REB500sys is foreseen for all single or double busbar configurations (Line variants L-V1 to L-V7 and Transformer variant TV1 to T-V4). In 1½ breaker configurations, 

variant L-V5 can be used for the bay level 

functions autoreclosure and synchrocheck. 

The capacity is sufficient for up to 60 feeders 

(bay units) and a total of 32 busbar zones.

The REB500sys detects all bus faults in solidly and low resistive-grounded power systems, all kind of phase faults in ungrounded 

and compensated power systems as well as 

feeder faults in solidly, low resistive-grounded, 

compensated and ungrounded power systems.

The protection operates selectively for all 

faults inside the zone of protection and 

remains reliably stable for all faults outside the 

zone of protection.

REB500sys is perfectly suited for retrofit concepts and stepwise upgrades. The bay unit is 

used as a stand-alone unit for bay protection 

functions (e.g. line protection, autoreclosure 

and synchrocheck or 2- and 3 winding transformer protection or autonomous T-zone protection). The central unit can be added at a 

later stage for full busbar and breaker failure 

protection functionality.

Distributed busbar protection REB500

including line and transformer protection

Depending on the network voltage level and 

the protection philosophy the following protection concepts are generally applied:

• Two main protection schemes per bay 

and one busbar protection.

With REB500sys the protection concept 

can be simplified. Due to the higher integration of functionality one of the main protection equipment can be eliminated.

• One main protection and one back-up 

protection scheme per bay, no busbar 

protection.

With REB500sys a higher availability of the 

energy delivery can be reached, due to the 

implementation of busbar and breaker failure protection schemes where it hasn't 

been possible in the past because of economical reasons.

Nine standard options are defined for Main 2/ 

Group 1 or back-up bay level functions:

Line protection

- Line variant 1 (L-V1)

directional, non-directional overcurrent and 

directional earth fault protection

- Line variant 2 (L-V2)

as line variant L-V1 plus distance prot.

- Line variant 3 (L-V3)

as line variant L-V2 plus autoreclosure

- Line variant 4 (L-V4)

as line variant L-V3 plus synchrocheck

- Line variant 5 (L-V5)

as line variant L-V1 plus autoreclosure and 

synchrocheck.

- Line variant 6 (L-V6) for 16.7 Hz

non-directional overcurrent, distance protection, autoreclosure.

- Line variant 7 (L-V7) for 16.7 Hz

as line variant L-V6 plus directional earth 

fault protection for grounded systems

Transformer protection

- Transformer variant 1 (T-V1)

2- or 3 winding transformer differential protection, thermal overload, current functions; 

applicable also as autonomous T-zone protection.

- Transformer variant 2 (T-V2)

2-winding transformer differential protection, thermal overload, current functions, 

overfluxing protection, neutral overcurrent 

(EF).

- Transformer variant 3 (T-V3)

Distance protection for transformer back-up 

or 2-winding transformer differential protection, thermal overload, current functions, 

voltage functions, frequency functions, 

power function, overfluxing protection.

- Transformer variant 4 (T-V4)

Transformer oriented functions/ back-up 

functions -> thermal overload, current functions, voltage functions, frequency functions, power function, overfluxing protection.

Distributed busbar protection REB500

including line and transformer protection

Mode of 

installation

There are three versions of installing the numerical busbar protection REB500 and the numerical station protection REB500sys:

Distributed installation

In this case, the bay units (see Fig. 24) are 

installed in casings or cubicles in the individual switchgear bays distributed around the 

station and are connected to the central processing unit by optical fiber cables. The central processing unit is normally in a centrally 

located cubicle or in the central relay room.

Centralized installation

19" mounting plates with up to three bay units 

each, and the central processing unit are 

mounted according to the size of the busbar 

system in one or more cubicles (see Fig. 23). 

A centralized installation is the ideal solution 

for upgrading existing stations, since very

little additional wiring is required and compared with older kinds of busbar protection, 

much more functionality can be packed into 

the same space.

Combined centralized and distributed 

installation

Basically, the only difference between a distributed and a centralized scheme is the 

mounting location of the bay units and therefore it is possible to mix the two philosophies

Distributed busbar protection REB500

including line and transformer protection

Page 7 

System design Bay unit (500BU03)

The bay unit (see Fig. 4) is the interface 

between the protection and the primary system process comprising the main CTs, isolators and circuit-breaker and performs the 

associated data acquisition, pre-processing, 

control functions and bay level protection 

functions. It also provides the electrical insulation between the primary system and the 

internal electronics of the protection.

The input transformer module contains four 

input CTs for measuring phase and neutral 

currents with terminals for 1 A and 5 A. Additional interposing CTs are not required, 

because any differences between the CT 

ratios are compensated by appropriately configuring the software of the respective bay 

units.

Optional input transformer module also contains five input voltage transformers for the 

measurement of the three-phase voltages and 

two busbar voltages and recording of voltage 

disturbances or 6 current transformers for 

transformer differential protection. (see 

Fig. 12).

In the analog input and processing module, 

the analog current and voltage signals are 

converted to numerical signals at a sampling 

rate of 48 samples per period and then 

numerically preprocessed and filtered accordingly. Zero-sequence voltage and zero-current 

signals are also calculated internally. The Process data are transferred at regular intervals 

from the bay units to the central processing 

unit via the process bus.

Every bay unit has 20 binary inputs and 16 

relay outputs. The binary I/O module detects 

and processes the positions of isolators and 

couplers, blocking signals, starting signals, 

external resetting signals, etc. The binary 

input channels operate according to a patented pulse modulation principle in a nominal 

range of 48 to 250 V DC. The PC-based HMI 

program provides settings for the threshold 

voltage of the binary inputs. All the binary output channels are equipped with fast operating 

relays and can be used for either signaling or 

tripping purposes (see contact data in Table 

8).

A software logic enables the input and output 

channels to be assigned to the various functions. A time stamp is attached to all the data 

such as currents, voltages, binary inputs, 

events and diagnostic information acquired by 

a bay unit.

Where more binary and analog inputs are 

needed, several bay units can be combined to 

form a feeder/bus coupler bay (e.g. a bus coupler bay with CTs on both sides of the bus-tie 

breaker requires two bay units).

The bay unit is provided with local intelligence 

and performs local protection (e.g. breaker 

failure, end fault, breaker pole discrepancy), 

bay protection (Main 2 or back-up bay protections) as well as the event and disturbance 

recording. 

Distributed busbar protection REB500

including line and transformer protection

In the event that the central unit is out of operation or the optical fiber communication is disrupted an alarm is generated, the bay unit will 

continue to operate, and all local and bay protection as well as the recorders (event and 

disturbance) will remain fully functional 

(stand-alone operation).

The hardware structure is based on a closed, 

monolithic casing and presented in two 

mounting solutions:

• Without local HMI: ideal solution if convenient access to all information via the central unit or by an existing substation 

automation system is sufficient.

• With local HMI and 20 programmable LEDs 

(Fig. 5): ideal solution for distributed and 

kiosk mounting (AIS), since all information 

is available in the bay.

For the latter option it is possible to have the 

HMI either built in or connected via a flexible 

cable to a fixed mounting position (see

Fig. 28).

In the event of a failure, a bay unit can be easily replaced. The replacement of a bay unit 

can be handled in a simple way. During system start-up the new bay unit requests its 

address, this can be entered directly via its 

local HMI. The necessary setting values and 

configuration data are then downloaded automatically.

Additional plug-and-play functionality

Bay units can be added to an existing 

REB500 system in a simple way.

Fig. 5 Bay unit

Central unit (500CU03)

The hardware structure is based on standard 

racks and only a few different module types 

for the central unit (see Fig. 4).

The modules actually installed in a particular 

protection scheme depend on the size, complexity and functionality of the busbar system.

A parallel bus on a front-plate motherboard 

establishes the interconnections between the 

modules in a rack. The modules are inserted 

from the rear.

The central unit is the system manager, i.e. it 

configures the system, contains the busbar 

replica, assigns bays within the system, manages the sets of operating parameters, acts as 

process bus controller, assures synchronization of the system and controls communication with the station control system.

The variables for the busbar protection function are derived dynamically from the process 

data provided by the bay units.

The process data are transferred to the central processor via a star coupler module. Up to 

10 bay units can be connected to the first central processor and 10 to the others. Central 

processors and star coupler modules are 

added for protection systems that include 

more than 10 bay units. In the case of more 

than 30 bay units, additional casings are 

required for accommodating the additional 

central processors and star coupler modules 

required.

All modules of the central unit have a plugand-play functionality in order to minimize 

module configuration.

One or two binary I/O modules can be connected to a central processing unit.

The central unit comprises a local HMI with 20 

programmable LEDs (Fig. 6), a TCP/IP port 

for very fast HMI500 connection within the 

local area network.

Distributed busbar protection REB500

including line and transformer protection

Page 9 

Functionality Busbar protection 

The protection algorithms are based on two 

well-proven measuring principles which have 

been applied successfully in earlier ABB lowimpedance busbar protection systems:

• a stabilized differential current measurement

• the determination of the phase relationship 

between the feeder currents (phase comparison)

The algorithms process complex current vectors which are obtained by Fourier analysis 

and only contain the fundamental frequency 

component. Any DC component and harmonics are suppressed.

The first measuring principle uses a stabilized 

differential current algorithm.

The currents are evaluated individually for 

each of the phases and each section of busbar (protection zone).

where N is the number of feeders. The following two conditions have to be accomplished 

for the detection of an internal fault:

where

kst stabilizing factor

kst max stabilization factor limit. 

A typical value is kst max = 0.80

IK min differential current pick-up value

The above calculations and evaluations are 

performed by the central unit.

The second measuring principle determines 

the direction of energy flow and involves comparing the phases of the currents of all the 

feeders connected to a busbar section.

The fundamental frequency current phasors 

1..n (5) are compared. In the case of an internal fault, all of the feeder currents have almost the same phase angle, while in normal 

operation or during an external fault at least 

one current is approximately 180° out of 

phase with the others

The algorithm detects an internal fault when 

the difference between the phase angles of all 

the feeder currents lies within the tripping 

angle of the phase comparator (see Fig. 8).

Distributed busbar protection REB500

including line and transformer protection

The task of processing the algorithms is 

shared between the bay units and the central 

processing unit. Each of the bay units continuously monitors the currents of its own fee-der, 

preprocesses them accordingly and then filters the resulting data according to a Fourier 

function. The analog data filtered in this way 

are then transferred at regular intervals to the 

central processing unit running the busbar 

protection algorithms.

Depending on the phase-angle of the fault, 

the tripping time varies at Idiff/Ikmin5 between 20 and 30 ms including the auxiliary 

tripping relay.

Optionally, the tripping signal can be interlocked by a current or voltage release criteria 

in the bay unit that enables tripping only when 

a current above a certain minimum is flowing, 

respectively the voltage is below a certain 

value.

Breaker failure protection

The breaker failure functions in the bay units 

monitor both phase currents and neutral current independently of the busbar protection. 

They have two timers with individual settings.

Operation of the breaker failure function is 

enabled either:

• internally by the busbar protection algorithm (and, if configured, also by the internal line protection, overcurrent or pole 

discrepancy protection features) of the bay 

level

• externally via a binary input, e.g. by the line 

protection, transformer protection etc.

After the delay of the first timer has expired, a 

tripping command can be applied to a second

tripping coil on the circuit-breaker and a 

remote tripping signal transmitted to the station at the opposite end of the line.

This first timer operates in a stand-alone 

mode in the bay unit.

If the fault still persists at the end of the second time delay, the breaker failure function 

uses the busbar replica to trip all the other 

feeders supplying the same section of busbar 

via their bay units.

A remote tripping signal can be configured in 

the software to be transmitted after the first or 

second timer.

Phase-segregated measurements in each bay 

unit cope with evolving faults.

End fault protection

In order to protect the “dead zone” between 

an open circuit-breaker and the associated 

CTs, a signal derived from the breaker position and the close command is applied.

The end fault protection is enabled a certain 

time after the circuit-breaker has been opened. In the event of a short circuit in the dead 

zone the nearest circuit-breakers are tripped.

This function is performed in a stand-alone 

mode in the bay unit.

Overcurrent function

A definite time overcurrent back-up protection 

scheme can be integrated in each bay unit. 

(The operation of the function, if para-meterized, may start the local breaker failure protection scheme).

This function is performed in a stand-alone 

mode in the bay unit.

Current release criteria

The current release criteria is only performed 

in the bay unit. It is effective for a busbar protection trip and for an intertripping signal 

(including end fault and breaker failure) and 

prevents those feeders from being tripped that 

are conducting currents lower than the setting 

of the current release criteria.

Voltage release criteria

The voltage criterion is measured in the bay 

unit. The function can be configured as 

release criterion per zone through internal 

linking in the central unit. This necessitates 

the existence of one set of voltage transformers per zone in one of the bay units. Tripping

Distributed busbar protection REB500

including line and transformer protection

is only possible if the voltage falls short of 

(U<) or exceeds (U0>) the set value.

Additionally this release criterion can be configured for each feeder (voltage transformers 

must be installed). For details see Table 22.

Check zone criterion

The check zone algorithm can be used as a 

release criterion for the zone-discriminating 

low-impedance busbar protection system. It is 

based on a stabilized differential current measurement, which only acquires the feeder currents of the complete busbar. The isolator / 

breaker positions are not relevant for this criterion.

Neutral current detection I0 

Earth fault currents in impedance-grounded 

systems may be too low for the stabilized differential current and phase comparison functions to detect. A function for detecting the 

neutral current is therefore also available, but 

only for single phase-to-earth faults.

Pole discrepancy

A pole discrepancy protection algorithm 

supervises that all three poles of a circuitbreakers open within a given time. 

This function monitors the discrepancy between the three-phase currents of the circuitbreaker.

When it picks up, the function does not send 

an intertripping signal to the central unit, but, if 

configured, it starts the local breaker failure 

protection (BFP logic 3).

This function is also performed in a standalone mode in the bay unit.

Event recording

The events are recorded in each bay unit. A 

time stamp with a resolution of 1ms is attached to every binary event. Events are divided 

into the three following groups:

• system events

• protection events

• test events

The events are stored locally in the bay unit or 

in the central unit.

Disturbance recording

This function registers the currents and the 

binary inputs and outputs in each bay. Voltages can also be optionally registered (see 

Table 14).

A disturbance record can be triggered by 

either the leading or lagging edges of all 

binary signals or by events generated by the 

internal protection algorithms. Up to 10 general-purpose binary inputs may be configured 

to enable external signals to trigger a disturbance record. In addition, there is a binary 

input in the central and the bay unit for starting 

the disturbance recorders of all bay units.

The number of analog channels that can be 

recorded, the sampling rate and the recording 

period are given in Table 14. A lower sampling 

rate enables a longer period to be recorded.

The total recording period can be divided into 

a maximum of 15 recording intervals per bay 

unit.

Each bay unit can record a maximum of 32 

binary signals, 12 of which can be configured 

as trigger signals.

The function can be configured to record the 

pre-disturbance and post-disturbance states 

of the signals.

The user can also determine whether the recorded data is retained or overwritten by the 

next disturbance (FIFO = First In, First Out).

This function is performed in a stand-alone 

mode in the bay unit (see page 7).

Note:

Stored disturbance data can be transferred via 

the central unit to other computer systems for 

evaluation by programs such as PSM505 [3]. 

Files are transferred in the COMTRADE format.

After retrieving the disturbance recorder data, 

it is possible to display them graphically with 

PSM505 directly.

Communication interface

Where the busbar protection has to communicate with a station automation system (SAS), 

a communication module is added to the central unit. The module supports the interbay 

bus protocols IEC 61850-8-1, IEC 60870-5-

103 and LON.

The IEC 61850-8-1 interbay bus transfers via 

either optical or electrical connection:

• differential current of each protection zone

• monitoring information from REB500 central unit and bay units

• binary events (signals, trips and diagnostic)

• trip reset command

Distributed busbar protection REB500

including line and transformer protection

• disturbance recording data (via MMS file 

transfer protocol)

• time synchronization with Simple Network 

Time Protocol (SNTP) 

• two independent time servers are supported. Server 2 as backup time

The LON interbay bus transfers via optical 

connection:

• differential currents of each protection zone

• binary events (signals, trips and diagnostic)

• trip reset command

• disturbance recording data (via HMI500)

• time synchronization

The IEC 60870-5-103 interbay bus transfers 

via either optical or electrical connection:

• time synchronization

• selected events listed in the public part

• all binary events assigned to a private part

• all binary events in the generic part

• trip reset command

Test generator

The HMI program (HMI500) which runs on a 

PC connected to either a bay unit or the central processing unit includes a test generator.

During commissioning and system maintenance, the test generator function enables the 

user to:

• activate binary input and output signals

• monitor system response.

• test the trip circuit up to and including the 

circuit-breaker 

• test the reclosure cycles

• establish and perform test sequences with 

virtual currents and voltages for the bay 

protection of the REB500sys

The test sequencer enables easy testing of 

the bay protection without the need to decommission the busbar protection. Up to seven 

se-quences per test stage can be started. The 

sequences can be saved and reactivated for 

future tests.

Isolator supervision

The isolator replica is a software feature without any mechanical switching elements. The 

software replica logic determines dynamically 

the boundaries of the protected busbar zones 

(protection zones). The system monitors any 

inconsistencies of the binary input circuits 

connected to the isolator auxiliary contacts 

and generates an alarm after a set time delay.

In the event of an isolator alarm, it is possible 

to select the behavior of the busbar protection:

• blocked

• zone-selective blocked

• remain in operation

Differential current supervision

The differential current is permanently supervised. Any differential current triggers a timedelayed alarm. In the event of a differential 

current alarm, it is possible to select the 

behavior of the busbar protection:

• blocked

• zone-selective blocked

• remain in operation

Trip redirection

A binary input channel can be provided to 

which the external signal monitoring the circuit-breaker air pressure is connected. Tripping is not possible without active signal. 

When it is inactive, a trip generated by the 

respective bay unit is automatically redirected 

to the station at the opposite end of the line 

and also to the intertripping logic to trip all the 

circuit-breakers connected to the same section of busbar.

The trip redirection can also be configured 

with a current criterion (current release criteria).

Distributed busbar protection REB500

including line and transformer protection

Page 13 

Human machine interface (HMI)

The busbar protection is configured and maintained with the aid of human machine interfaces at three levels.

Local HMI

The local display interface installed in the central unit and in the bay units comprises:

• a four-line LCD with 16 characters each for 

displaying system data and error messages

• keys for entering and display as well as 3 

LEDs for the display of trips, alarms and 

normal operation.

• in addition 20 freely programmable LEDs 

for user-specific displays on the bay unit 

500BU03 and central unit 500CU03.

The following information can be displayed:

• measured input currents and voltages 

• measured differential currents (for the busbar protection)

• system status, alarms

• switchgear and isolator positions (within 

the busbar protection function)

• starting and tripping signals of protection 

functions

External HMI (HMI500)

More comprehensive and convenient control 

is provided by the external HMI software running on a PC connected to an optical interface 

on the front of either the central unit or a bay 

unit. The optical interface is completely 

immune to electrical interference. The PC 

software facilitates configuration of the entire 

busbar protection, the set-ting of parameters 

and full functional checking and testing. The 

HMI500 can also be operated via the LON 

Bus on MicroSCADA for example, thus eliminating a separate serial connection to the central unit.

The HMI runs under MS WINDOWS NT, WINDOWS 98, WINDOWS 2000 and WINDOWS 

XP. The HMI500 is equipped with a comfortable on-line help function. A data base comparison function enables a detailed 

comparison between two configuration files 

(e.g. between the PC and the central unit or 

between two files on the PC).

Remote HMI

A second serial interface at the rear of the 

central unit provides facility for connecting a 

PC remotely via either an optical fiber, TCP/IP 

or modem link. The operation and function of 

HMI500 is the same whether the PC is connected locally or remotely.

Additional 

functionalities

Bay level functions

These functions are based on the well established and well-proven functions built in the 

ABB line and transformer protection. The bay 

level functions contain all the relevant additional functions, which are normally requested 

of a line and transformer protection scheme.

The line protection functions (L-V1 - L-V7) are 

used as Main 2 or back-up for lines as well as 

for transformer bays. The transformer protection functions (T-V1 - T-V4) are used as Group 

2 or back-up bay protection for transformer 

bays or as an independent T-Zone protection.

Distributed busbar protection REB500

including line and transformer protection

High-speed distance protection

• Overcurrent or underimpedance starters 

with polygonal characteristic

• Five distance zones (polygon for forwards 

and reverse measurement)

• Load-compensated measurement

• Definite time overcurrent back-up protection (short-zone protection)

• System logic

- switch-onto-fault

- overreach zone

• Voltage transformer circuit supervision

• Power swing blocking function

• HF teleprotection. The carrier-aided 

schemes include:

- permissive underreaching transfer tripping

- permissive overreaching transfer tripping

- blocking scheme with echo and transient blocking functions

• Load-compensated measurement

- fixed reactance slope

- reactance slope dependent on load 

value and direction (ZHV<)

• Parallel line compensation

• Phase-selective tripping for single and 

three-pole autoreclosure

• Four independent, user-selectable setting 

groups.

In the supervision mode the active and reactive power with the respective energy direction 

is displayed by the HMI500.

Autoreclosure

The autoreclosure function permits up to four 

three-phase autoreclosure cycles. The first 

cycle can be single phase or three-phase.

If the REB500sys autoreclosure function is 

employed, it can be used as a back-up for the 

autoreclosure realized externally (separate 

equipment or in the Main 1 protection).

When the autoreclosure function is realized 

outside of REB500sys, all input and output 

signals required by the external autoreclosure 

equipment are available in order to guarantee 

correct functionality.

Synchrocheck

The synchrocheck function determines the difference between the amplitudes, phase 

angles and frequencies of two voltage vectors. The synchrocheck function also contains 

checks for dead line and dead bus.

Transformer differential protection 

• For two- and three-winding transformers

• Auto transformers

• Three-phase function

• Current-adaptive characteristic

• High stability for external faults and current 

transformer saturation

• No auxiliary transformers necessary 

because of vector group and CT ratio compensation

• Inrush restraint using 2nd harmonic

The transformer differential protection function 

can also be used as an autonomous T-zone 

protection in a 1½ breaker scheme.

Thermal overload

This function protects the insulation against 

thermal stress. This protection function is normally equipped with two independently set 

levels and is used when oil overtemperature 

detectors are not installed.

Peak value over- and undercurrent protection

These functions are used for current monitoring with instantaneous response and where 

insensitivity to frequency is required.

Peak value over- and undervoltage protection

This function is used for voltage monitoring 

with instantaneous response and where insensitivity to frequency is required.

Frequency function

The function is used either as an over-/ underfrequency protection, or for load-shedding in 

the event of an overload. Several stages of 

the frequency protection are often needed. 

This can be achieved by configuring the frequency function several times.

Rate of change frequency protection df/dt

This function is used for the static, dynamic 

and adaptive load-shedding in power utilities 

and industrial distribution systems. The function supervises the rate-of-change df/dt of one 

voltage input channel. Several stages of the 

rate-of-change frequency protection are often 

Distributed busbar protection REB500

including line and transformer protection

Page 15 

needed. This can be achieved by configuring 

the rate-of-change frequency function several 

times.

Definite time overfluxing protection

This function is primarily intended to protect 

the iron cores of transformers against excessive flux. The function works with a definite 

time delay. The magnetic flux is not measured 

directly. Instead the voltage/frequency-ratio, 

which is proportional to the flux is monitored.

Inverse time overfluxing protection

This function is primarily intended to protect 

the iron cores of transformer against excessive flux. The function works with an inverse 

time delay. The inverse curve ca be set by a 

table of 10 values and the times t-min and tmax. The magnetic flux is not measured directly. Instead the voltage/frequency-ratio, 

which is proportional to the flux is monitored.

Power function

This function provides single, or three phase 

measurement of the real or apparent power. 

The function can be configured for monitoring 

reverse, active or reactive power (power 

direction setting). Phase angle errors of the 

CT/VT inputs can be compensated by setting. 

The operating mode can be configured either 

to underpower or to overpower protection.

Logics and delay/integrator

These functions allow the user the engineering of some easily programmable logical functions and are available as standard also in the 

REB500 functionality.

Directional sensitive earth fault protection 

for grounded systems

A sensitive directional ground fault function 

based on the measurement of neutral current 

and voltage is provided for the detection of 

high-resistance ground faults in solidly or lowresistance grounded systems. The scheme 

operates either in a permissive or blocking 

mode and can be used in conjunction with an 

inverse time earth fault overcurrent function. 

In both cases the neutral current and voltage 

can be derived either externally or internally. 

This function works either with the same communication channel as the distance protection 

scheme or with an independent channel.

Directional sensitive earth fault protection 

for ungrounded or compensated systems

The sensitive earth fault protection function for 

ungrounded systems and compensated systems with Petersen coils can be set for either 

forwards or reverse measurement. The characteristic angle is set to ±90° 

(U0 · I0 · sin ) in ungrounded systems and to 

0° or 180° (U0 · I0 · cos ) for systems with 

Petersen coils. The neutral current is always 

used for measurement in the case of systems 

with Petersen coils, but in ungrounded systems its use is determined by the value of the 

capacitive current and measurement is performed by a measuring CT to achieve the 

required sensitivity. To perform this function 

the BU03 with 3I, 1MT and 5U is required.

Definite time over- and undercurrent protection 

This function is used as Main 2 or as back-up 

function respectively for line, transformer or 

bus-tie bays. This function can be activated in 

the phase- and/or the neutral current circuit.

Inverse time overcurrent protection

The operating time of the inverse time overcurrent function reduces as the fault current 

increases and it can therefore achieve shorter 

operating times for fault locations closer to the 

source. Four different characteristics according to British Standard 142 designated normal 

inverse, very inverse, extremely inverse and 

long time inverse but with an extended setting 

range are provided. The function can be configured for single phase measurement or a 

combined three-phase measurement with 

detection of the highest phase current.

Inverse time earth fault overcurrent protection 

The inverse time earth fault overcurrent function monitors the neutral current of the system. Four different characteristics according 

to British Standard 142 designated normal 

inverse, very inverse, extremely inverse and 

long time inverse but with an extended setting 

range are provided.

Directional overcurrent definite / inverse 

time protection 

The directional overcurrent definite time function is available either with inverse time or definite time overcurrent characteristic. This 

function comprises a voltage memory for 

faults close to the relay location. The function 

response after the memory time has elapsed 

can be selected (trip or block).

Definite time over- and undervoltage protection 

This function works with a definite time delay 

with either single or three-phase measurement.

Distributed busbar protection REB500

including line and transformer protection

Additional functionalities (cont’d)

Three-phase current plausibility

This function is used for checking the sum and 

the phase sequence of the three-phase currents.

Three-phase voltage plausibility

This function is used for checking the sum and 

the phase sequence of the three-phase voltages.

Additional

features

Self-supervision 

All the system functions are continuously 

monitored to ensure the maximum reliability 

and availability of the protection. In the event 

of a failure, incorrect response or inconsistency, the corresponding action is taken to 

establish a safe status, an alarm is given and 

an event is registered for subsequent diagnostic analysis.

Important items of hardware (e.g. auxiliary 

supplies, A/D converters and main and program memories) are subjected to various 

tests when the system is switched on and also 

during operation. A watchdog continuously 

monitors the integrity of the software functions 

and the exchange of data via the process bus 

is also continuously supervised.

The processing of tripping commands is one 

of the most important functions from the reliability and dependability point of view. Accordingly, every output channel comprises two 

redundant commands, which have to be 

enabled at regular intervals by a watchdog. If 

the watchdog condition is not satisfied, the 

channels are blocked.

Extension of the system

The system functions are determined by software, configured using the software configuration tool.

The system can be completely engineered in 

advance to correspond to the final state of the 

station. The software modules for new bays or 

features can be activated using the HMI500 

when the primary plant is installed or the features are needed.

Additional system functions, e.g. breaker failure, end fault protection or bay level 

back-up / Main 2 functions can be easily activated at any time without extra hardware.

Resetting the trip commands/-signals

The following resetting modes can be selected for each binary output (tripping or signal 

outputs):

• Latches until manually reset

• Resets automatically after a delay

Inspection/maintenance

A binary input is provided that excludes a bay 

unit from evaluation by the protection system. 

It is used while performing maintenance 

respectively inspection activities on the primary equipment.

Redundant power supplies (Option)

Two power supply modules can be fitted in a 

redundant arrangement, e.g. to facilitate 

maintenance of station batteries. This is an 

option for the central unit as well as for the 

bay unit.

Time synchronization

The absolute time accuracy with respect to an 

external time reference depends on the 

method of synchronization used:

• no external time synchronization:

accuracy approx. 1 min. per month

• periodic time telegram with minute pulse 

(radio or satellite clock or station control 

system): accuracy typically ±10 ms

• periodic time telegram as above with second pulse: accuracy typically ±1 ms

• a direct connection of a GPS or DCF77 to 

the central unit is possible: accuracy typically ±1 ms

• Furthermore, the time synchronization can 

be done, if available, via the interbay bus 

IEC103, LON or SNTP (in case IEC61850-

8-1 is used)

The system time may also be synchronized by 

a minute pulse applied to a binary input on the 

central unit.

Distributed busbar protection REB500

including line and transformer protection

Page 17 

Requirements Optical fiber cables

A distributed busbar protection layout requires optical fiber cables and connectors with 

the following characteristics:

• 2 optical fiber cores per bay unit

• glass fibers with gradient index 

• diameter of core and sheath 62.5, 

respectively 125 m

• maximum permissible attenuation 5 dB

• FST connector (for 62.5 m optical fibers)

• rodent protected and longitudinally waterproof if in cable ducts 

Isolator auxiliary contact

Auxiliary contacts on the isolators are connected to binary inputs on the bay units and 

control the status of the busbar replica in the 

numerical busbar protection.

One potentially-free N/O and N/C contact are 

required on each isolator. The N/O contact 

signals that the isolator is “CLOSED” and the 

N/C contact that the isolator is “OPEN”. During the closing movement, the N/O contact 

must close before the isolator main contact 

gap reaches its flashover point.

Conversely, during the opening movement, 

the N/O contact must not open before the isolator main contact gap exceeds its flashover 

point.

If this is not the case, i.e. the contact signals 

‘no longer closed’ beforehand, then the N/C 

contact may not signal “OPEN” before the 

flashover point has been exceeded.

Distributed busbar protection REB500

including line and transformer protection

Circuit-breaker replica

When the circuit-breaker replica is read in the 

feeder or the bus-tie breaker, the circuitbreaker CLOSE command must also be connected. 

Main current transformer

The algorithms and stabilization features used 

make the busbar protection largely insensitive 

to CT saturation phenomena. Main CTs types 

TPS (B.S. class x), TPX, TPY, 5P.. or 10P.. are 

permissible. 

TPX, TPY and TPZ CTs may be mixed within 

one substation in phase-fault schemes. The 

relatively low CT performance needed for the 

busbar protection makes it possible for it to 

share protection cores with other protection 

devices.

Current transformer requirements for stability during external faults (Busbar protection)

The minimum CT requirements for 3-phase 

systems are determined by the maximum fault 

current. 

The effective accuracy limit factor (n') must be 

checked to ensure the stability of the busbar 

protection during external faults.

The rated accuracy limit factor is given by the 

CT manufacturer. Taking account of the burden and the CT losses, the effective accuracy 

limit factor n' becomes:

where:

n = rated accuracy limit factor 

PN = rated CT power

PE = CT losses

PB = burden at rated current

In the case of schemes with phase-by-phase 

measurement, n' must satisfy the following 

two relationships: 

where:

IKmax = max. primary through-fault current

I1N = rated primary CT current

Taking the DC time constant of the feeder into 

account, the effective n' becomes:

(2) n' 10 for TN 120 ms, or

n' 20 for 120 ms <TN 300 ms.

where: 

TN = DC time constant

Example: IKmax = 30000 A

I1N = 1000 A

TN  120 ms

Applying relationships (1) and (2): 

(2) n' 10

Selected: n' 10

The current transformer requirements for 

REB500sys for Line and Transformer protection are described in a separate publication 

[1].

Pick-up for internal faults

In the case of internal busbar faults, CT saturation is less likely, because each CT only 

conducts the current of its own feeder.

Should nevertheless CT saturation be possible, it is important to check that the minimum 

fault current exceeds the setting for Ikmin.

Note:

For systems that measure I0, the REB500 

questionnaire 1MRB520371-Ken should be 

filled in and submitted to ABB, so that the CT 

requirements can be checked in order to 

ensure proper I0 measurement.


  • ENTERASYS A4H254-8F8T Ethernet switch
  • ENTERASYS C2RPS-CHAS2 SecureStack c2 Redundant power supply chassis
  • ENTERASYS A2H124-24 Ethernet edge switch
  • EMG LID43.03 Reference voltage source
  • EMERSON PR6426010-110+C0N021916-240 32mm Eddy Current Sensor
  • EMERSON PR6423/011-110+C0N021 Eddy Current Signal Converter
  • EMERSON VE4003S2B1 DeltaV™ M-series Traditional I/O
  • EMERSON 2500M/AI4UNIV analog input module
  • EMERSON PMCspan PMC Expansion Mezzanine
  • EMERSON PR6424/011-140 16mm Eddy Current Sensor
  • EMERSON KJ3242X1-BK1 12P4711X042 S-Series H1 Card
  • EMERSON 960132-01 FX-316 Positioning Servo Drive 230 VAC
  • EMERSON KJ4006X1-BD1 Interface Terminal Block
  • EMERSON 1C31181G01 module
  • EMERSON CE4003S2B6 I/O Termination Block
  • EMERSON KJ4001X1-CK1 40-Pin Mass Termination Block
  • EMERSON VE4012S2B1 Module
  • EMERSON KL4103X1-BA1 CHARMs Smart Logic Solver Carrier
  • EMERSON A6370D/DP Overspeed Protection Monitor
  • EMERSON P188.R2 Industrial interface module
  • EMERSON VE3008 CE3008 KJ2005X1-MQ1 12P6381X042 MQ Controller
  • EMERSON TPMC917 4MB SRAM with Battery Backup and 4 Channel RS232
  • EMERSON P152.R4 Multifunctional module
  • EMERSON DA7281520 P152 Processor board
  • EMERSON PR6423/008-110 8mm Eddy Current Sensor
  • EMERSON PR6423/000-131 8mm Eddy Current Sensor
  • EMERSON MVME61006E-0163R VMEbus Single-Board Computer
  • EMERSON Ovation 5X00453G01 Remote I/O Node Controller Module
  • EMERSON 5X00070G04 Analog input
  • EMERSON Ovation 5X00070G01 Analog Input Module
  • EMERSON Ovation 5X00790G01 Compact Controller Module
  • EMERSON 5X00846G01 HART analog output module
  • EMERSON 1C31113G01 Digital output module (5-60VDC)
  • EMERSON KJ4110X1-BA1 I/O terminal module
  • EMERSON CSI3125 A3125/022-020 Shaft-Vibration Monitor
  • EMERSON 5X00273G01 Digital output module
  • EMERSON KJ4001X1-NB1 12P3368X012 REV:E 1-Wide I/O Carrier Extender Left
  • EMERSON KJ4001X1-NA1 12P3373X012 REV:C 1-Wide I/O Carrier Extender Right
  • EMERSON A6312/06 Speed and Key Monitor
  • EMERSON KJ4001X1-BE1 8-Wide I/O Carrier
  • EMERSON KJ2005X1-MQ1 KJ2005X1-MQ2 13P0072X082 MQ Controller
  • EMERSON 5X00226G03 - Ovation™ I/O Interface Controller, Electronics Module
  • EMERSON PR6423/00R-010+CON031 Vibration sensor
  • EMERSON 9199-00002 A6120 Control Module
  • Emerson Ovation 1C31234G01 - Ovation™ 16 Channel Compact Digital Input
  • Emerson Ovation KJ3002X1-BF1 12P1732X042 Controller module
  • Emerson Ovation 5X00226G01 I/O Interface Module
  • Emerson Ovation™ Controller Model OCR1100(5X00481G04/5X00226G04)
  • Emerson Ovation 5X00499G01 Digital Input 24Vdc Single 32CH
  • Emerson Ovation 5X00500G01 32-Channel Digital Output Module
  • Emerson ovation VE4001S2T2B4 Analog output card
  • Emerson ovation 5X00501G01 5X00502G01 Ethernet link controller
  • EMERSON A6824R 9199-00098-13 Module
  • EMERSON A6140 9199-00058 Industrial Control Module
  • EMERSON 1C31194G03 Industrial Control Module
  • EMERSON DB1-1 Industrial Control Module
  • EMERSON PMC-IO-ADAPTER I/O module
  • EMERSON L0115012 L0115032 Control module
  • EMERSON PMC-IO-PROZESSOR Process control module
  • EMERSON PMC PROFINET Manage Gigabit Ethernet switches
  • EMERSON A3120022-000 CSI3120 Bearing-Vibration Monitor
  • EMERSON SE3008 KJ2005X1-SQ1 12P6383X032 Controller
  • EMERSON 1000554 Printed circuit board
  • EMERSON PR6423/002-041 Sensor module
  • EMERSON 1C31232G02 Westinghouse control module
  • Abaco TRRM940 Switch
  • Abaco SWE440A Switch
  • Abaco NETernity™ RM984RC Ethernet Switch
  • Abaco NETernity™ GBX411 Ethernet Switch
  • Abaco NETernity™ GBX25
  • Abaco NETernity SWE540A
  • Abaco CP3-GESW8-TM8 Ethernet switch
  • Abaco SWE440S Ethernet switch
  • Abaco SWE450S 100GbE 3U VPX Switch Aligned to SOSA™ Standard
  • Abaco SWE550S 100GbE 6U VPX Switch Aligned to SOSA™ Standard
  • Abaco SPR870A Wideband Digital Receiver/Exciter
  • Abaco SPR507B Serial FPDP XMC/PMC
  • Abaco ICS-1572A Transceiver Module
  • Abaco daq8580 FMV Compression System
  • Abaco VP868 FPGA Card
  • Abaco HPC2812 Rugged 6U VPX High Performance Computer with Dual Intel
  • Abaco VSR347D 3U VPX Rugged Virtual Secure Router
  • Abaco VSR8000 Fully Rugged, COTS System Secure Router
  • Abaco RES3000 Compact, Rugged Ethernet Switches
  • Abaco PMC238 Expansion Card
  • Abaco EXP238 PMC/XMC Expansion Card for XVB603 VME Single Board Computer
  • Abaco VME-REPEAT-A-L VMEbus Repeater Link
  • Abaco VME-4514A VME Analog I/O Input/Output Board
  • Abaco VME-3128A Analog I/O
  • Abaco VME-3125A analog-to-digital Conversion board
  • Abaco VME-3123A VME Analog I/O Input Boards
  • Abaco PMC239/F Analog input/output board
  • Abaco PEX431 Multi-fabric Switch
  • Abaco CPCI-100A-BP 2-slot IndustryPack carrier for 3U CompactPCI
  • Abaco PMC522 Serial Controller
  • Abaco PMC522/FP Serial Controller
  • Abaco VME-2170A Digital Output 32-bit optically isolated
  • Abaco VME-1129 Digital Input Board 128-bit high voltage
  • Abaco IP-OCTALPLUS232 Eight EIA-232 asynchronous serial ports
  • Abaco IP-DIGITAL482 Digital I/O with 48 TTL Channels
  • Abaco PMC523 16-Port Serial Controller
  • EMERSON CE4003S2B1 M-series Traditional I/O
  • EMERSON SE3008 DeltaV™ SQ Controller
  • EMERSON 1C31227G01 - Ovation™ 8 Channel Analog Input
  • EMERSON 1C31224G01 - Ovation™ 8 Channel Analog Input
  • ABB UNS0119A-P,V101 3BHE029154P3 3BHE029153R0101 Digital input
  • ABB 3BDH000050R1 AM811F Battery Module
  • ABB 3ASC25H705-7 Digital output board
  • ABB UDD406A 3BHE041465P201 control board
  • ABB 3BHE014967R0002 UNS 2880B-P,V2: COB PCB Assembled
  • ABB PPC380AE02 HIEE300885R0102 module
  • ABB NU8976A99 HIER466665R0099 Processor Module
  • ABB DIS0006 2RAA005802A0003G Digital Input Module
  • ABB Bailey IMDS003 infi 90 Digital Output Slave Module
  • ABB XO08R1-B4.0 Expand the output relay module
  • ABB VA-MC15-05 Controller module
  • ABB VA-3180-10 Controller module
  • ABB 72395-4-0399123 Excitation module
  • ABB PU516A 3BSE032402R1 Engineering Board - PCI
  • ABB 3BHE044481R0101 3BHE044477P3 PPE091A101 Module
  • ABB UCD224A102 Control unit
  • ABB SNAT603CNT SNAT 603 CNT Motor Control Board
  • ABB SNAT634PAC Drive board
  • ABB UAD149A0011 Servo controller
  • ABB UCD224A103 Industrial controller module
  • ABB 3BHE029154P3/3BHE029153R0101 UNS0119A-P,V101 Processor Module
  • ABB ARCOL 0338 ARCOL 0346 Solid-state motor starter
  • ABB ARCOL 0339 Solid-state motor controller