or generate an alarm when the voltage
drops below a specified voltage setting for
a programmable time delay.
Overvoltage
An overvoltage on running motor with a
constant load results in decreased current.
However, iron and copper losses increase,
causing an increase in motor temperature.
The current overload relay will not pickup
this condition and provide adequate


protection. The overvoltage element may
be used for protecting the motor in the
event of a sustaine overvoltage condition.
Contactor Failure
The MM2 monitors the contactor while
performing start and stop commands. If
the contactor does not change status an
‘open control circuit’ or ‘welded contactor’
alarm is triggered.
Additional Alarms
The MM2 has programmable alarms to
warn of a number of abnormal conditions.
These include: acceleration time exceeded,
abnormal inverter starter, incomplete start,
motor greasing, contactor inspection,
motor stop time, analog input, and process
interlock switch open.
Starters
MM2 can be programmed to serve as the
following types of motor starters:
• Full Voltage non-reversing,
• Full Voltage reversing,
• Wye/Delta open or close transition
starter,
• Two speed starter,
• Inverter (VSD) starter,
• Slip ring (rotor resistors) and primary
resistance starters,
• Autotransformer open or close
transition starter,
• Duty/Standby starter,
• Soft starter
Undervoltage Auto Restart
The motor can be automatically restarted
after a momentary power loss when this
feature is enabled. When the control
voltage drops below the dropout voltage
the contactors are de-energized. The MM2
can initiate timers to restart selected drives
upon the return of supply voltage. If control
voltage is restored within the programmed
restart time, the motor will be restarted
immediately. If the control voltage takes
longer to be restored, the MM2 can be
programmed to attempt a restart after a
programmed time delay.
Outputs
The MM2 has one or two contactors (A
and B) which are used for motor starting.
There are also two auxiliary programmable
output relays available on the MM2,
which can be assigned to any one of 31
functions.
Switched Inputs
The MM2 has up to six fixed control inputs.
These are used for start A and B, stop, local
isolator, and contactor A and B status. The
MM2 also has up to 10 programmable
switch inputs. Each input can have one
of 33 interlock functions assigned to it. A
function can be assigned to one interlock
input only.
Analog Input
The analog input can be scaled to user
defined values. High and low alarm and trip
setpoints are recorded with time delays.
Monitoring and Metering
The MM2 offers advanced monitoring and
metering which includes:
Metering
The MM2 meters and displays:
• current of each phase
• Ground fault leakage current
• Motor load as a % of full load current
• Thermal capacity used (%)
• % Current unbalance
• Power (kW)
• Energy (kWh)
• Voltage
• Analog input
Trip Record
When the MM2 issues a trip command a
record is generated which includes the
cause and pre-trip actual values.
Statistics and Maintenance
The MM2 records statistical data about
relay and motor operation, allowing the
user to set the interval at which routine
maintenance tasks should be performed.
When the times are exceeded an alarm is
generated. These include:
• Motor greasing interval: number of
hours between bearing lubrication
• Contactor inspection: number of starts
after which the contactor contacts
must be inspected for wear

• Maximum motor stopped time: the
maximum number of hours the motor
can be left shut down
User Interfaces
When ordered with the Panel Mount
option, the MM2 comes equipped with a 40
character display, LED indicators, as well
programming and control push buttons.
Display and Keypad
The MM2 has a keypad and 40 character
display for local control and programming
without a computer. In the event of a
trip, alarm, or start block, the display will
automatically display a clear status
message.
In addition to the programming keys, the
panel mount option also provides 3 control
keys for starting and stopping the motor
locally.
Indicator LEDs
The panel mount MM2 has nine LED’s that
provide the status of the motor and relay
output contacts. Two additional LED’s
indicate whether the relay is in Auto or
Manual control mode.
Communications
The MM2 uses a ModBus® RTU RS485
connection for communication. Up to 32
MM2s can be daisy-chained together on a
single communication channel. The MM2
supports a number of baud rates, ranging
from at 1200 to 19,200 bps. A RS232/485
converter module may be used to connect
a personal computer to the MM2.
Software
The MM2 comes with a Windows®-based
configuration program called MM2PC. It
allows access to all the features of the
MM2 with easy to use, pull-down menus.