• the relay is de-energized to indicate an alarm.
• The use of the VM function danger bypass is not allowed.
• The use of the VM function trip multiply is not allowed.
• The alarm must be defined as ‘latching’.
3.2 Valid Safety Configurations
The VM600 machinery protection system (MPS) can be configured in many different
arrangements. These configurations are described in more detail in the hardware manual
(see 1.5 - Applicable Documents). For example, the VM600 can be used to protect rotating
machines in a safety related system.
Monitored Signal Valid for SRS Reference in HW
Manual
Broad-Band Absolute Bearing Vibration Yes Section 7.1
Tracking No Section 7.2
Relative Shaft Vibration with Gap Monitoring Yes Section 7.3
Absolute Shaft Vibration Yes Section 7.4
Shaft Position Yes Section 7.5
Safety Inputs and Outputs
Monitored Signal Valid for SRS Reference in HW
Manual
Broad-Band Absolute Bearing Vibration Yes Section 7.1
Tracking No Section 7.2
Relative Shaft Vibration with Gap Monitoring Yes Section 7.3
Absolute Shaft Vibration Yes Section 7.4
Shaft Position Yes Section 7.5
Table 3-1 : Overview of valid safety configurations
Signal Comments Reference in HW
Manual
MPC4 CH1-CH4 (inputs) Ensure cabling follows the
guidelines Table 9-1 part 1
MPC4 relay contacts (outputs) Table 9-1 part 2
Safety Function
With reference to IEC 61508 the safety function for the system is defined below.
For the required safety function SF1, the following safety parameters (SP) are required in
accordance with IEC 61508.
SF
Number Description Safe State
Required
Safety
Parameters
SF1
If an input value (or values)
exceed(s) a predefined limit,
then a trip activation signal is
made.
De-energize to trip (open relay
contact).
That is, the EUC and the
VM600 interpret a
de-energized state as a safe
state.
See table
below
SP
Number Safety Parameter Requirement Comment
SP1 Safety integrity level SIL 1
SP2 Operational mode Low demand mode
SP3a Component type sensor Type B
Component type logic
(measuring logic) Type B
Component type
actuator (relay) Type A
SP4 Hardware fault tolerance
(HFT) 0
Single channel architecture
of an already existing
proven-in-use system
should be used for SIL 1
application without any
changes
SP5 Probability of failure on
demand (PFD) ≥ 10-2 to 10-1
PFD by proof test years
FMEDA
0.5 1.0 2.0 5.0
5.5e-3 1.1e-3 2.2e-2 5.0e-2
SP6
Safe failure fraction
(SFF) for Type A
subsystem
< 60% for SIL 1 and
HFT 0
Safe failure fraction
(SFF) for Type B
subsystem
60% to < 90% for SIL 1
and HFT 0
In practice, the output relay or relays are normally the ‘input’ to a safety related PLC that takes
this input together with other safety related signals.
3.5 ISO 13849-1 Performance Level
The table below shows the breakdown of performance level (PL) by diagnostic coverage and
mean time to dangerous failure (MTTFd).
Safety Time
After the defined safety level threshold has been exceeded, the VM600 system will open the
associated safety relay within 100 ms.
3.7 Protection of Relay Contacts
In a safety system it is important to protect against a relay contact becoming welded due to
excessive current being inadvertently passed. Therefore, the outputs must be protected by a
5A(T) fuse
nstallation
The system shall be installed following the procedures described in the MPS Hardware
Manual (Standard Version) MAMPS-HW/E (see 1.5 - Applicable Documents). Environmental
restrictions are described in Appendix A of the manual.
3.9 Configuring the System
It is important that the levels (vibration and so on) are adjusted to suit the system under
protection and that a manual verification is made of the parameters that are uploaded to the
system (MPC4 card).
Note that the procedures described should only be performed by competent and authorized
personnel following the plant specific guidelines in force at the installation site.
3.9.1 Define the levels
The choice of alarm levels must be made in consultation with the site manager. It is the end
user’s responsibility to ensure that the alarm levels are appropriate for the particular system
being protected.
The levels are defined using the MPS1 software (supplied) or the MPS2 software (optional).
Please refer to the appropriate documentation for complete information.
3.9.2 Define the alarm outputs
Any relay on the MPC4 or RLC16 cards can be configured to provide the safety function. As
previously noted, the alarms must be:
• configured as ‘latching’
• de-energized to ‘trip’.
3.9.3 Upload the levels and configuration
Once the system parameters have been correctly defined using the MPS software, the
configuration for each MPC4 card must be uploaded to the card. This procedure is described
in the MPS1 Software Manual MAMPS1-SW/E (see 1.5 - Applicable Documents).
3.9.4 Configuration verification
Whilst the actual upload of data is controlled by CRC verification and other techniques, in
order to fulfil the IEC 61508 requirements a manual verification of this upload is required. The
verification is made by downloading the configuration from the MPC4 card to the computer