Loop 1, select Loop 1.
Second, the Base SP, Min SP, Max SP, and Heat Span, and Cool Span parameters need to be set. All parameters are
in the engineering units of the Control Loop or Secondary Loop.
If the process is controlling a process with a SP at 140°F and at -22°F while not wanting any control output at
ambient, which is consider to be 75°F, the following will apply.
BASE SP = 75, this is the base value at which all other values will be referenced from. This value must be set
whenever using heat, cool, or heat and cooling control outputs.
Min SP = -35, this is the value at which the lower SP value cannot exceed and must be greater than the cooling SP
of -30. This value can be set to the input range lowest value, if desired so that it would not need to be included in
any future resetting of cascade parameters.
Max SP = 145, this is the value at which the higher SP value cannot exceed and must be greater than the heating SP
of 140. This value can be set to the input range highest value, if desired so that it would not need to be included in
any future resetting of cascade parameters.
Heat Span = 65, this is the value which is the span between the Base SP and the desired heat SP. i.e. 140 – 75 = 65.
This is the value that must be set if using heat only or heat and cooling outputs as well as the Base SP.
Cool Span = 105, this is the value which is the span between the Base SP and the desired cool SP i.e. -75 + -30 =
105. This value must be set when using heat and cooling or cooling only outputs as well as the Base SP.
Heat only example: Low SP = 1200 and High SP =1600.
Base SP = 1200 and Heat Span = 400.
Cool only example: High SP = 50 and Low SP = 30.
Base SP = 50 and Cool Span = 20
Watlow Winona OH 07/28/06
1241 Bundy Blvd
Winona, MN 55987
Telephone (507) 494-5656
2
© 2005 Watlow Electric Manufacturing Company
CLS200 and MLS300 Cascade Control
Setup and Tuning of Cascade Functions
Tuning Cascade Loops
The proper procedure for tuning cascade control loops is to first tune the secondary (inner) heat or cool control loop
using all three of the PID modes. This loop must first be tuned to good PID control parameters before doing any
tuning of the SP temperature control loop. Do not try tuning both loops at the same time unless you are an expert in
tuning PID loops and have experience with cascade control systems.
If cooling is in use and there is a proportional component to the cooling control such as using a TP output with a
solenoid valve, then the PID modes can be tune as well.
The use of autotuning or adaptive tuning can be used to achieve the PID control parameters. If these tuning
functions are not available then use manual PID tuning methods. After a satisfactory control is achieved with the
heat control loop, take note of the P and I values.
To tune the primary (outer) SP control loop, first check the actual range of the SP of the secondary loop by placing
the SP loop control into manual mode. With a heat output of 0%, the SP of the heat control loop should be at the low
SP value as set in the cascade menu. Change the output to 100%, the SP of the heat control loop should be at the
high SP value as set in the cascade menu. If using cooling control do the same thing with the heat output at 0% and
then changing the cooling output to achieve the same values as set in the cascade menu.
Use the values as noted in the PB mode and TI or RM of the Integral/Reset mode of the heat control loop and place
them in the PID parameters of the heat control output. If PID values are obtained for the cooling, use them for the
cooling PID parameters. DO NOT USE THE DERIVATIVE MODE. IT MUST BE TURNED OFF.
Place the control mode of the SP loop into Auto control mode. The SP loop control output should start changing
which in turn will be changing the SP of the secondary or heat control loop. Allow the process to settle down. If
there is any unwanted cycling of the temperature, use and change the PID parameters of the SP control loop for
changing any unwanted control deviations from SP. Do not use the heat control loop for making any changing to the
PID parameters.
A slow process will take time to see how the tuning is doing so don’t be in a hurry. A space of 20 to 30 minutes is
not too long in most cases.
If you are not knowledgeable or trained and have experience with PID and tuning be sure to see the instructions on
PID and PID tuning before attempting to tune cascade loops.
Watlow TRU-TUNE+ can do the tuning for you. First, perform an auto tune of the heat control loop by placing the
control mode into Tune. After the adaptive mode has been active for a while such as 1 or 2 hours, use the P and I
values as obtained in the adaptive mode for the P and I values of the SP loop. Place the SP loop directly into
Adaptive Mode for final tuning of the SP PID values.