DCS Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

CLS200 and MLS300 Cascade Control Setup and Tuning of CascadeFunctions

From:WATLOW | Author:LIAO | Time :2025-08-25 | 659 Browse: | 🔊 Click to read aloud ❚❚ ▶ | Share:

This paper describes the use of cascade control utilized for processes with long lag times between a change in the 

control output level and a change in the process variable such as temperature. A lag time period of 10 to 30 minutes 

or longer would be suitable conditions for considering cascade control. A commonly used process that is described 

as needing cascade control is the water tank example. Another common process that uses cascade control is 

aluminum melt furnaces. 

It is not the type of process; rather the qualifying condition is the long lag time of a slow process that is always out 

of control. The PV will be lagging so far behind the change in the output so that no amount of PID tuning will 

correct the condition. The water tank example is using the input (cold) water temperature and looking at the outlet 

(hot) water temperature that is the controlling point. The outlet temperature may always lag behind the heating of the 

inlet water thus providing a variance of the outlet water temperature that is out of tolerance no matter the PID 

settings. 

The aluminum melt furnace has a problem in the melting of cold aluminum bars as the bars are introduced into the 

melt furnace. The temperature of the heating zone will rise so high due to a “cooler” condition of the melt pot and to 

the long lag time that it will overheat the melt furnace. Cycling will be very severe and the melt pot will be out of 

control. 

The use of two TC or other types of temperature sensors at two different locations can provide for control of long 

lag time response process. By placing one sensor to measure the outlet of the process temperature and another one to 

measure the process product inlet temperature, we can now measure the process for cascade control. 

The outlet sensor as it measures the process product outlet temperature will provide for the desired product 

temperature. This is known as the temperature Setpoint Control and has other labels as well such as Outer Loop. 

This loop will provide the SP level for the temperature Heat Control zone also known as the Inner Loop. 

The inlet sensor will measure the process product inlet temperature and using the SP level from the Setpoint Control 

of the outlet sensor provide the heat control required for controlling the inlet temperature to meet the desired 

temperature for the outlet temperature. It does this by using the control output level of the SP Control Loop to set the 

SP level of the Control Loop. 

As the outlet temperature decreases it will increase the SP level for control of the inlet temperature control zone. As 

the outlet temperature increases it will decrease the SP level for control of the inlet temperature control zone. In 

providing this cascade of control it overcomes the long lag time of the process. By looking at the difference between 

the two sensors and making corrections as to the heat control level, the output level can be maintained at a closer 

level of control. 

CLS200 and MLS300 Cascade Control Terms

Nominal heat only control cascade has two parameters for adjustments. Dual heat and cool control would have four 

parameters. 

The Control Loop Setpoint (Inner Loop) for heat or cool outputs has a parameter for setting the desired SP value 

when the SP Control Loop (Outer Loop) output level is at 0%. It also has a parameter for setting the desired SP 

value when the SP Control output level is at 100%. Full PID control modes of the Control Loop will be used for 

controlling the control output level. 

Watlow Winona OH 07/28/06 

1241 Bundy Blvd 

Winona, MN 55987 

Telephone (507) 494-5656 

1

© 2005 Watlow Electric Manufacturing Company 

CLS200 and MLS300 Cascade Control 

 Setup and Tuning of Cascade Functions 

The Setpoint Loop will use the loop’s SP as set by the operator for the desired temperature of the product or process. 

The Setpoint Loop PID control modes will only use P and I control modes. 

There is a possibly of six parameters that will need to be set for using cascade control when using the CLS200 or 

MLS300 Dual Control Outputs. There are five when only using the Heating Control Output. 

Follow User Guide instructions for changing parameters from the front panel keys. 

First, the assignment as to which loop will be the temperature SP control loop (Primary Loop) and which loop will 

be the cascade temperature Control Loop (Secondary Loop). 

In the front panel display, select the Cascade Menu while in the loop number that the inlet sensor is connected to, 

which is the heat control loop or Secondary Loop. For instance if Loop 2 is the heat control loop with an output to 

the heat control device, the display should show Loop 2 before going into the Cascade Menu. 

While in the Cascade Menu and using the keys select the PRIM. Loop or the SP Control Loop. Select any number, 

but number 2. The number selected should be the output sensor loop. For instance if the outlet sensor is connected to 

Loop 1, select Loop 1. 

Second, the Base SP, Min SP, Max SP, and Heat Span, and Cool Span parameters need to be set. All parameters are

in the engineering units of the Control Loop or Secondary Loop.

If the process is controlling a process with a SP at 140°F and at -22°F while not wanting any control output at 

ambient, which is consider to be 75°F, the following will apply. 

BASE SP = 75, this is the base value at which all other values will be referenced from. This value must be set 

whenever using heat, cool, or heat and cooling control outputs. 

Min SP = -35, this is the value at which the lower SP value cannot exceed and must be greater than the cooling SP 

of -30. This value can be set to the input range lowest value, if desired so that it would not need to be included in 

any future resetting of cascade parameters. 

Max SP = 145, this is the value at which the higher SP value cannot exceed and must be greater than the heating SP 

of 140. This value can be set to the input range highest value, if desired so that it would not need to be included in 

any future resetting of cascade parameters. 

Heat Span = 65, this is the value which is the span between the Base SP and the desired heat SP. i.e. 140 – 75 = 65. 

This is the value that must be set if using heat only or heat and cooling outputs as well as the Base SP. 

Cool Span = 105, this is the value which is the span between the Base SP and the desired cool SP i.e. -75 + -30 = 

105. This value must be set when using heat and cooling or cooling only outputs as well as the Base SP. 

Heat only example: Low SP = 1200 and High SP =1600. 

Base SP = 1200 and Heat Span = 400. 

Cool only example: High SP = 50 and Low SP = 30. 

Base SP = 50 and Cool Span = 20 

 

Watlow Winona OH 07/28/06 

1241 Bundy Blvd 

Winona, MN 55987 

Telephone (507) 494-5656 

2

© 2005 Watlow Electric Manufacturing Company 

CLS200 and MLS300 Cascade Control 

 Setup and Tuning of Cascade Functions 

Tuning Cascade Loops

The proper procedure for tuning cascade control loops is to first tune the secondary (inner) heat or cool control loop 

using all three of the PID modes. This loop must first be tuned to good PID control parameters before doing any 

tuning of the SP temperature control loop. Do not try tuning both loops at the same time unless you are an expert in 

tuning PID loops and have experience with cascade control systems. 

If cooling is in use and there is a proportional component to the cooling control such as using a TP output with a 

solenoid valve, then the PID modes can be tune as well. 

The use of autotuning or adaptive tuning can be used to achieve the PID control parameters. If these tuning 

functions are not available then use manual PID tuning methods. After a satisfactory control is achieved with the 

heat control loop, take note of the P and I values. 

To tune the primary (outer) SP control loop, first check the actual range of the SP of the secondary loop by placing 

the SP loop control into manual mode. With a heat output of 0%, the SP of the heat control loop should be at the low 

SP value as set in the cascade menu. Change the output to 100%, the SP of the heat control loop should be at the 

high SP value as set in the cascade menu. If using cooling control do the same thing with the heat output at 0% and 

then changing the cooling output to achieve the same values as set in the cascade menu. 

Use the values as noted in the PB mode and TI or RM of the Integral/Reset mode of the heat control loop and place 

them in the PID parameters of the heat control output. If PID values are obtained for the cooling, use them for the 

cooling PID parameters. DO NOT USE THE DERIVATIVE MODE. IT MUST BE TURNED OFF. 

Place the control mode of the SP loop into Auto control mode. The SP loop control output should start changing 

which in turn will be changing the SP of the secondary or heat control loop. Allow the process to settle down. If 

there is any unwanted cycling of the temperature, use and change the PID parameters of the SP control loop for 

changing any unwanted control deviations from SP. Do not use the heat control loop for making any changing to the 

PID parameters. 

A slow process will take time to see how the tuning is doing so don’t be in a hurry. A space of 20 to 30 minutes is 

not too long in most cases. 

If you are not knowledgeable or trained and have experience with PID and tuning be sure to see the instructions on 

PID and PID tuning before attempting to tune cascade loops. 

Watlow TRU-TUNE+ can do the tuning for you. First, perform an auto tune of the heat control loop by placing the 

control mode into Tune. After the adaptive mode has been active for a while such as 1 or 2 hours, use the P and I 

values as obtained in the adaptive mode for the P and I values of the SP loop. Place the SP loop directly into 

Adaptive Mode for final tuning of the SP PID values. 

TRU-TUNE+ is not available in the CLS200 or MLS300 Series controllers, but is available in the CPC400. Also 

cascade is standard firmware in the CPC400 as well. Order option “EF” in the CLS200 and MLS300 to use cascade 

control. 

 

Watlow Winona OH 07/28/06 

1241 Bundy Blvd 

Winona, MN 55987 

Telephone (507) 494-5656 

3

© 2005 Watlow Electric Manufacturing Company 


  • DEIF RMF-112D Frequency relay
  • DEIF RMC-142D Current relay
  • DEIF RMC-132D Current relay
  • DEIF RMC-131D Current relay
  • DEIF RMC-122D Current relay
  • DEIF RMC-121D Current relay
  • DEIF RMC-111D Current relay
  • DEIF MVR-V211 Busbar Protection
  • DEIF MVR-T257 Transformer Differential Protection
  • DEIF MVR-T256 Transformer Differential Protection
  • DEIF MVR-T216 Transformer Differential Protection
  • DEIF MVR-T215 Transformer Protection
  • DEIF MVR-M257 Motor Differential Protection
  • DEIF MVR-M255 Motor Protection
  • DEIF MVR-M215 Motor Protection
  • DEIF MVR-M210 Motor Protection
  • DEIF MVR-G257 Generator Differential Protection
  • DEIF MVR-G215 Generator Protection
  • DEIF MVR-F255 Directional Feeder Protection
  • DEIF MVR-F215 Directional Feeder Protection
  • DEIF MVR-F210 Feeder Protection
  • DEIF MVR-F205 Directional Feeder Protection
  • DEIF MVR-F201 Basic Feeder Protection
  • DEIF MVR-200 series Medium Voltage Relay
  • DEIF MDR-2 Multi-differential relay
  • DEIF LMR-122D Loss of mains relay
  • DEIF LMR-111D Loss of mains relay
  • DEIF APU-4 Advanced G59 and G99 protection unit
  • DEIF iE 650 PLC - The most robust programmable automation controller available
  • DEIF iE 350 PLC - Programmable Automation PLC Controller
  • DEIF iE 250 PLC Versatile and modular intelligent energy PLC controller
  • DEIF PPM-3 EDG Protection and Power Management
  • DEIF AGC 3X 4198000234E AUTOMATIC GENSET CONTROLLER
  • SAUTER ASF123 Damper actuator with spring return
  • SAUTER ASF122 Damper actuator with spring return
  • SAUTER ASF113F122 Damper actuator with spring return
  • SAUTER ASF113F120 Damper actuator with spring return
  • SAUTER ASF112F122 Damper actuator with spring return
  • SAUTER ASF112F120 Damper actuator with spring return
  • SAUTER ASM 124/134 series - ASM134F130 Damper actuator
  • SAUTER ASM 134 series - ASM134SF132 Damper actuator
  • SAUTER ASM 124/134 series - ASM124SF132 Damper actuator
  • SAUTER ASM 124/134 series - ASM124F122 Damper actuator
  • SAUTER ASM 124/134 series - ASM124F120 Damper actuator
  • SAUTER Valve actuator ASM 105S/115S series ASM115SF152
  • SAUTER Valve actuator ASM 105S/115S series ASM105SF152
  • SAUTER Valve actuator ASM 105S/115S series ASM115SF132
  • SAUTER Valve actuator ASM 105/115 series ASM105SF132
  • SAUTER Valve actuator ASM 105/115 series ASM115F122
  • SAUTER Valve actuator ASM 105/115 series ASM115F120
  • SAUTER Valve actuator ASM 105/115 series ASM105F122
  • SAUTER Valve actuator ASM 105/115 series ASM105F120
  • SAUTER Valve actuator ASM 105/115 series ASM105F10
  • SAUTER AKF113S Rotating actuator AKF 112/113 series
  • SAUTER AKF113F122 Rotating actuator AKF 112/113 series
  • SAUTER AKF113F120 Rotating actuator AKF 112/113 series
  • SAUTER AKF112F122 Rotating actuator AKF 112/113 series
  • SAUTER AKF112F120 Rotating actuator AKF 112/113 series
  • SAUTER AKM115SAF332: Smart Actuator for ball valve, BACnet/IP
  • SAUTER AKM115SAF232  Rotating Actuator  AKM 115SA Smart Actuator
  • SAUTER AKM115SF152  Rotating Actuator  AKM 105S/115S Series
  • SAUTER AKM115SF132  Rotating Actuator  AKM 105S/115S Series
  • SAUTER AKM105SF132  Rotating Actuator  AKM 105S/115S Series
  • SAUTER AKM115F122 Rotating actuator  AKM 105/115 series
  • SAUTER Rotating actuator  AKM 105/115 series AKM115F120
  • SAUTER Rotating actuator  AKM 105/115 series AKM105F122
  • SAUTER Rotating actuator  AKM 105/115 series  AKM105F120
  • SAUTER Continuous actuator for unit valves, with stroke AXS215S
  • SAUTER Linear valve actuator AXT/AXS series AXT211
  • SAUTER Linear valve actuator AXT/AXS series AXT201
  • SAUTER Linear valve actuator AXM/AXF series AXF217S
  • SAUTER Linear valve actuator AXM/AXF series AXM217S
  • SAUTER AXM217SF404 is an electric actuator for unit valves.
  • SAUTER AXM217SF402 is an electric actuator for unit valves.
  • SAUTER Linear valve actuator AXM/AXF series AXM217
  • SAUTER Linear valve actuator AVF 124/125 series AVF125S
  • SAUTER Linear valve actuator AVF 124/125 series AVF124S
  • SAUTER Linear valve actuator AVF 124/125 series AVF124S
  • SAUTER AVM322S-R Linear valve actuator AVM 234S series
  • SAUTER AVM322-R Linear valve actuator AVM 234S series
  • SAUTER AVM322SF132 Linear valve actuator AVM 234S series
  • SAUTER AVM321SF132    Linear Valve Actuator
  • GE Power Conversion P112-6053 Advanced Micro Controller (AMC2)
  • GE Power Conversion P111-6053 Advanced Micro Controller (AMC2)
  • GE Power Conversion P110-6053 Advanced Micro Controller (AMC2)
  • GE Power Conversion P122-6052 Advanced Micro Controller (AMC2)
  • GE Power Conversion P121-6052 Advanced Micro Controller (AMC2)
  • GE Power Conversion P112-6152 Advanced Micro Controller (AMC2)
  • GE Power Conversion P110-6152 Advanced Micro Controller (AMC2)
  • GE Power Conversion P112-6052 Advanced Micro Controller (AMC2)
  • GE P106-6052 AMC2 Advanced Micro Controller Unit
  • SAUTER AVF234SF232 Linear valve actuator AVM 234S series
  • SAUTER AVF234SF132 Linear valve actuator AVM 234S series
  • SAUTER Linear valve actuator AVM 234S series AVM234SF132-6
  • SAUTER Linear valve actuator AVM 234S series AVM234SF132-5
  • SAUTER Linear valve actuator AVM 234S series AVM234SF132
  • SAUTER Linear valve actuator AVM215SF132-7
  • SAUTER Linear valve actuator AVM215SF132R
  • Linear valve actuator AVM 115SA Smart Actuator AVM115SAF332
  • Linear valve actuator AVM 115SA Smart Actuator AVM115SAF232
  • SAUTER Linear valve actuator AVM 105S/115S series AVM115SF132
  • SAUTER Linear valve actuator AVM 105S/115S series AVM105SF132
  • SAUTER AVM115F901 Linear Valve Actuator
  • SAUTER AVM115F122 Linear Valve Actuator
  • SAUTER AVM115F120 Linear Valve Actuator
  • SAUTER AVM105F122 Linear Valve Actuator
  • SAUTER AVM105F120 Linear Valve Actuator
  • SAUTER AVM105F100 Linear Valve Actuator
  • AEROTECH SM Series High-Performance Stepper Motors
  • AEROTECH BLMSC Series Linear Motors
  • AEROTECH Custom Linear Motors
  • AEROTECH BMS Series Brushless, Slotless Rotary Motors
  • AEROTECH BM Series Brushless Rotary Motors
  • AEROTECH BLMX Series Linear Motors
  • AEROTECH BLMH Series Linear Motors
  • AEROTECH BLM Series Linear Motors
  • AEROTECH BLMC Series Linear Motors
  • AEROTECH BLMUC-143  Linear motor forcer with thermistor
  • AEROTECH BLMUC-111    Linear motor forcer with thermistor
  • AEROTECH BLMUC-95  Linear motor forcer with thermistor
  • AEROTECH BLMUC-79 Linear motor forcer with thermistor
  • AEROTECH BLMUC Series Linear Motors
  • AEROTECH Automation1 FLEX Distributed Amplifier Multi-Axis Servo Control System
  • AEROTECH Automation1 HXA4 6-Axis Hexapod Servo Drive
  • AEROTECH Automation1 iHXA4 6-Axis Hexapod Servo Drive with Motion Controller
  • AEROTECH Modular System Control Console
  • AEROTECH TV Series Transformers
  • AEROTECH TM Series Transformers