This paper describes the use of cascade control utilized for processes with long lag times between a change in the
control output level and a change in the process variable such as temperature. A lag time period of 10 to 30 minutes
or longer would be suitable conditions for considering cascade control. A commonly used process that is described
as needing cascade control is the water tank example. Another common process that uses cascade control is
aluminum melt furnaces.
It is not the type of process; rather the qualifying condition is the long lag time of a slow process that is always out
of control. The PV will be lagging so far behind the change in the output so that no amount of PID tuning will
correct the condition. The water tank example is using the input (cold) water temperature and looking at the outlet
(hot) water temperature that is the controlling point. The outlet temperature may always lag behind the heating of the
inlet water thus providing a variance of the outlet water temperature that is out of tolerance no matter the PID
settings.
The aluminum melt furnace has a problem in the melting of cold aluminum bars as the bars are introduced into the
melt furnace. The temperature of the heating zone will rise so high due to a “cooler” condition of the melt pot and to
the long lag time that it will overheat the melt furnace. Cycling will be very severe and the melt pot will be out of
control.
The use of two TC or other types of temperature sensors at two different locations can provide for control of long
lag time response process. By placing one sensor to measure the outlet of the process temperature and another one to
measure the process product inlet temperature, we can now measure the process for cascade control.
The outlet sensor as it measures the process product outlet temperature will provide for the desired product
temperature. This is known as the temperature Setpoint Control and has other labels as well such as Outer Loop.
This loop will provide the SP level for the temperature Heat Control zone also known as the Inner Loop.
The inlet sensor will measure the process product inlet temperature and using the SP level from the Setpoint Control
of the outlet sensor provide the heat control required for controlling the inlet temperature to meet the desired
temperature for the outlet temperature. It does this by using the control output level of the SP Control Loop to set the
SP level of the Control Loop.
As the outlet temperature decreases it will increase the SP level for control of the inlet temperature control zone. As
the outlet temperature increases it will decrease the SP level for control of the inlet temperature control zone. In
providing this cascade of control it overcomes the long lag time of the process. By looking at the difference between
the two sensors and making corrections as to the heat control level, the output level can be maintained at a closer
level of control.
CLS200 and MLS300 Cascade Control Terms
Nominal heat only control cascade has two parameters for adjustments. Dual heat and cool control would have four
parameters.
The Control Loop Setpoint (Inner Loop) for heat or cool outputs has a parameter for setting the desired SP value
when the SP Control Loop (Outer Loop) output level is at 0%. It also has a parameter for setting the desired SP
value when the SP Control output level is at 100%. Full PID control modes of the Control Loop will be used for
controlling the control output level.
Watlow Winona OH 07/28/06
1241 Bundy Blvd
Winona, MN 55987
Telephone (507) 494-5656
1
© 2005 Watlow Electric Manufacturing Company
CLS200 and MLS300 Cascade Control
Setup and Tuning of Cascade Functions
The Setpoint Loop will use the loop’s SP as set by the operator for the desired temperature of the product or process.
The Setpoint Loop PID control modes will only use P and I control modes.
There is a possibly of six parameters that will need to be set for using cascade control when using the CLS200 or
MLS300 Dual Control Outputs. There are five when only using the Heating Control Output.
Follow User Guide instructions for changing parameters from the front panel keys.
First, the assignment as to which loop will be the temperature SP control loop (Primary Loop) and which loop will
be the cascade temperature Control Loop (Secondary Loop).
In the front panel display, select the Cascade Menu while in the loop number that the inlet sensor is connected to,
which is the heat control loop or Secondary Loop. For instance if Loop 2 is the heat control loop with an output to
the heat control device, the display should show Loop 2 before going into the Cascade Menu.
While in the Cascade Menu and using the keys select the PRIM. Loop or the SP Control Loop. Select any number,
but number 2. The number selected should be the output sensor loop. For instance if the outlet sensor is connected to