OMRON CJ1G-CPU45H PLC
OMRON CJ1G-CPU45H PLC
9-12 TR (Temporary Relay) Area
The TR Area contains 16 bits with addresses ranging from TR0 to TR15.
These temporarily store the ON/OFF status of an instruction block for branch
ing. TR bits are useful when there are several output branches and interlocks
cannot be used.
The TR bits can be used as many times as required and in any order required
as long as the same TR bit is not used twice in the same instruction block.
TR bits can be used only with the OUT and LD instructions. OUT instructions
(OUT TR0 to OUT TR15) store the ON OFF status of a branch point and LD
instructions recall the stored ON OFF status of the branch point.
TR bits cannot be changed from a Programming Device

Timer Area
The 4.096 timer numbers (T0000 to T4095) are shared by the HUNDRED-MS
TIMER (TIM/TIMX(550)), TEN-MS TIMER (TIMH(015)/TIMHX(551)), ONE
MS TIMER (TMHH(540)/TMHHX(552)), TENTH-MS TIMER (TIMU(541)/
TIMUX(556)) (see note), HUNDREDTH-MS TIMER (TMUH(544)/
TMUHX(557)) (see note), ACCUMULATIVE TIMER (TTIM(087)/TTIMX(555)),
TIMER WAIT (TIMW(813)/TIMWX(816)), and HIGH-SPEED TIMER WAIT
(TMHW(815)/TMHWX(817)) instructions. Timer Completion Flags and
present values (PVs) for these instructions are accessed with the timer num
bers. (The TIML(542), TIMLX(553), MTIM(543), and MTIMX(554) instructions
do not use timer numbers.)
Note CJ1-H-R CPU Units only.
When a timer number is used in an operand that requires bit data, the timer
number accesses the Completion Flag of the timer. When a timer number is
used in an operand that requires word data, the timer number accesses the
PV of the timer. Timer Completion Flags can be used as often as necessary
as normally open and normally closed conditions and the values of timer PVs
can be read as normal word data.
With CJ1-H and CJ1M CPU Units, the refresh method for timer PVs can be
set from the CX-Programmer to either BCD or binary. With CJ1 CPU Units, it
can only be set to binary.
Note It is not recommended to use the same timer number in two timer instructions
because the timers will not operate correctly if they are timing simultaneously.
(If two or more timer instructions use the same timer number, an error will be
generated during the program check, but the timers will operate as long as the
instructions are not executed in the same cycle.)
The following table shows when timer PVs and Completion Flags will be reset
| USAQEM-03-SU21 Yaskawa AC Servo Motor |
| 1794-IR8 Allen-Bradley Flex I/O RTD Module |
| 1746-TB3G Allen-Bradley Flex I/O 1794 series terminal base unit |
| 1794-OB8EP Allen-Bradley Flex I/O Digital DC Output Module |
| TK801V006 3BSC950089R2 ABB Cable Assembly with METAL HOOD |
| SYN5202-0277 3BHB006715R0277 Synchronizing and Paralleling Equipment and Systems ABB |
| PCI-5565PIORC-100A00 Reflective Memory Node Card GE |
| MVI71-DFNTProSoft Generic ASCII Ethernet Network Interface Module |
| MVI71-DNPProSoft Generic ASCII Ethernet Network Interface Module |
| MVI71-GECProSoft Generic ASCII Ethernet Network Interface Module |
| MVI71-MCMProSoft Modbus Master/Slave Network Interface Module |
| MVI71-MNETProSoft Modbus TCP / IP Interface module |
| MVI94-DNPProSoft DNP 3.0 Master/Slave Communication Module |
| UNS0867A-P,V2 HIEE405246R0002 ABB Extension Card I/O |
| N70032702L INR-244-97B-B-X5 Power supply circuit ALSTOM |
| UR4DH GE UR Module provides the relay with an array of digital inputs and outputs |
| UR4CH GE Universal Relays series CT/VT module |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|