breaker-open command at a set power level.
Installation Notes
Hand-held Programmer (9905-292) is required and used by the DSLC to
configure and calibrate it to the site specific application.
The DSLC requires a power source of +24Vdc @ 1 A. The 505E power supplies
can not supply this much power, thus an external power supply may be required.
The DSLC can interface with the unit Automatic Voltage Regulator through
contacts or a +9 volt bias signal.
For more information on Woodward’s Digital Synchronizer & Load Control,
please refer to Woodward manual 02007.