DCS Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

ABBAdvance Optima Continuous gas analyzers AO2000

From:ABB | Author:LIAO | Time :2025-08-09 | 669 Browse: | 🔊 Click to read aloud ❚❚ | Share:

Description Application Information from the AO2000 gas analyzer can be transferred to a PC or DCS via the Modbus. Measurement values, status signals and also signals of analog and digital inputs and outputs are thus available for further usage. Using the AO-MDDE server the signals can be integrated into standard software (e.g. Excel, Visual Basic or LabVIEW). For further information, see Chapter 4 “AO-MDDE server and demo programs”, page 3535. AO-MDDE can be downloaded from the DVD-ROM which is delivered together with each gas analyzer. AO-MDDE does not support Modbus over TCP/IP. Basic documents 

 Modbus Application Protocol Specification V1.1b, December 28, 2006 

 Modbus over Serial Line Specification and Implementation Guide V1.02, December 20, 2006 

 Modbus Messaging on TCP/IP Implementation Guide V1.0b, October 24, 2006 These documents are available at http://www.modbus.org/specs.php. Interfaces and connection versions The RS232 and the RS485 interface located on the RS232/RS485 module in AO2000 are supported, where only one can be operated at a time. Connection versions are described in Chapter 3 “Modbus connection”, page 30. As an alternative, the Ethernet 10/100BASE-T interface can be used for data transmission via Modbus TCP/IP protocol (from software version 5.1, see page 7).

Data transfer For data transfer a combination of frames is used, that consists of 1/0 information, united to one or more telegrams. Frame The transfer values are decomposed in bytes (= 8 bit). Each of these bytes is completed by one start-bit, possibly one parity-bit (even number of “1”) and one stop-bit. In the following description the term “byte” will be used, even if ten or eleven bits will be transferred including the start-, stop- and parity-bits. Telegrams The Modbus telegrams consist of the following frames: address (1 byte), function (1 byte), data (n bytes) and check sum (2 bytes). The telegrams also take on the “shake-hands-function”: each telegram from master to slave must be responded, before a new telegram is allowed to be transmitted. The computer has to have in a adequate supervision, for excluding non answering bus participants (time-out-supervision). Admissible addresses As addresses for the participants of the bus the numbers 1 to 255 are admitted. The address 0 is the global address (broadcast-address). When this address will be used in a telegram, all participants accept this telegram without an acknowledgment to the master.

Integration The AO2000 Modbus/TCP server expects requests from the current IP addresses via the communication port. A maximum of 4 clients can be connected to the Modbus/TCP server of an AO2000 at the same time. If the connection to a client breaks down, the connection status in the Modbus/TCP server is enabled again after a max. 60 seconds. Reading out data from the AO2000 Modbus/TCP server The following procedure must be executed on the Modbus client, in order to receive data from the AO2000 Modbus/TCP server: 1. Establish a TCP connection to port 502 on the server. 2. Create a Modbus request. 3. Send the Modbus request incl. the Modbus/TCP MBAP Header. 4. Wait for a response to the same TCP connection. 5. Read the first 6 bytes of the response; these state the length of the response. 6. Read the remaining bytes of the response. Functions, addresses and registers The supported functions and the addresses and registers of Modbus over TCP/IP are equivalent to those of Modbus over RS232/RS485

Function code Function code 43 with MEI 14 (MEI = Modbus Encapsulated Interface) is used to read the device parameters to  read measured values,  transfer simulation data,  apply reference material. Address assignment of the device parameters for the function code 43 There is read access to the device parameters. Measurement components are mapped with the following structure:  Name  Measurement range start  Measurement range end  Unit The number of the first measured values register is listed under BasisM in the device parameters list. The measured value status is implemented as NAMUR status: Bit Assignmant 0 Error 1 Maintenance 2 Maintenance request 3 Beyond specification 4 Test operation, simulation measured value transmitted 5…15 Reserved for extensions 16…31 Vendor-specific The number of the first simulation data register is listed under BasisS in the device parameters list. The number of the register to apply reference material is listed under BasisR in the device parameters list. Maximum 32 Bus DIs are reserved for transferring reference material. The register "status of application" is used for feedback of the DIs for which a hardware digital output is connected. When reference material is applied, the status "maintenance" is set and a message is displayed on the gas analyzer's screen


Principle The AO2000 series gas analyzers are modular and very flexible. A gas analyzer can consist of one or more analyzer modules which in itself can measure one or more components. It is also possible to connect different kinds of I/O-modules and I/O-boards to a device. For this reason the Modbus addressing schema is not static. Data format There are six flexible groups, four configurable groups and two fixed length groups of information defined in a AO2000 gas analyzer. The grouped information can be read through “Single Modbus Request”. Flexible groups The flexible groups are:  Measurement values (see page 12)  Analog inputs (see page 12)  Analog outputs (see page 13)  Digital inputs (see page 13)  Digital outputs (see page 14)  Measurement range feedback (see page 17)  Measurement range configuration (see page 18)  Measurement range drift values (see page 19)  QAL3 calibration data (see page 21) Each flexible group has a fixed start address and, depending on the system layout, a variable number of elements. Configurable groups The configurable groups are:  Bus analog inputs (see page 14)  Bus analog outputs (see page 15)  Bus digital inputs (see page 15)  Bus digital outputs (see page 15) Each configurable group has a fixed start address and, depending on the user configuration, a variable number of elements. Fixed length groups The fixed length groups are:  Configuration display (see page 16)  Status (see page 16)

  • AEROTECH Automation1 SI4 Stepper Interface
  • AEROTECH Automation1 XI4 Servo Interface
  • AEROTECH AEROTECH Automation1 iXI4 Servo Interface with Motion Controller
  • AEROTECH Automation1 XC6e Enhanced, High-Power PWM Servo Drive
  • AEROTECH Automation1 iXC6e Enhanced, High-Power PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 XC2 Compact PWM Servo Drive
  • AEROTECH Automation1 XC4 PWM Servo Drive
  • AEROTECH Automation1 GL4 Galvo Laser Scan Head Linear Drive
  • AEROTECH Automation1 XC2e Enhanced, Compact Servo Drive with PWM+
  • AEROTECH Automation1 XC4e Enhanced, PWM Servo Drive
  • AEROTECH Automation1 XR3 Multi-Axis Servo Drive Rack
  • AEROTECH Automation1 iXR3 Multi-Axis Servo Drive Rack with Motion Controller
  • AEROTECH Automation1 iXC2 Compact PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 iXC2e Enhanced, Compact PWM+ Servo Drive with Motion Controller
  • AEROTECH Automation1 iXC4 PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 iXC4e Enhanced, PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 iPC Industrial PC with Motion Controller
  • AEROTECH EPICS & TANGO Drivers for Distributed Control Systems
  • AEROTECH .NET, C, Python & LabVIEW APIs Custom Application Develotpmen
  • AEROTECH Automation1 Industrial Ethernet Support
  • AEROTECH Automation1 iSMC Intelligent, Software-Based Motion Controller
  • AEROTECH Automation1 iXA4 1- 2- or 4-Axis PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 XA4 1- 2- or 4-Axis PWM Servo Drive
  • CTI 2500-ADP2-DISC Discrete Wiring Adapter for Series 500
  • CTI 2500-ADP1 Analog Wiring Adapter for Series 500
  • CTI 2500C-RADP-RS485 Remote Base Controller Adapter for Series 500
  • CTI 2500C-RADP-RBC Profibus RBC Adapter for Series 500
  • CTI 2500C-PADP-120V 120VAC 50W Power Supply for Series 500
  • CTI 2500-RADP RBC Adapter for Series 500
  • CTI 2500-R4500 520/530/DBC Adapter for Series 500 - MATURE
  • CTI 2500-PADP Power Supply Adapter for Series 500
  • CTI 2500-IADP I/O Adapter for Series 500
  • CTI 2500-VP15A-N4-W7 15" Flat-Panel PC with Windows® 7 Embedded
  • CTI 2500S-27-1750 Slice I/O, Ethernet, RS232/485. 900MHz, 2DIO / 4UAI / 2AI
  • CTI 2500S-26-1750 Slice I/O, Ethernet, RS232/485. 900MHz, 8DIO / 2UAI
  • CTI 2500S-23-1750 Slice I/O, Ethernet, RS232/485. 900MHz, 4DI / 4DO / 2UAI / 2AO
  • CTI 2500S-27-1550 Slice I/O, RS232/485. 2DIO / 4UAI / 2AI
  • CTI 2500S-26-1550 Slice I/O, RS232/485. 8DIO / 2UAI
  • CTI 2500S-23-1550 Slice I/O, RS232/485. 4DI / 4DO / 2UAI / 2AO
  • CTI 2500S-27-1050 Slice I/O, Ethernet, 2DIO / 4UAI / 2AI
  • CTI 2500S-26-1050 Slice I/O, Ethernet, 8DIO / 2UAI
  • CTI 2500S-23-1050 Slice I/O, Ethernet, 4DI / 4DO / 2UAI / 2AO
  • CTI 2500C-32F-CJC 32-Pin Field Wiring Connector with Cold Junction Compensation
  • CTI 2500C-32F 32-Pin Field Wiring Connector
  • CTI 2500C-8-TC Eight Thermocouple Inputs
  • CTI 2500C-8-RTD Eight RTD Inputs
  • CTI 2500C-8-RL-FC 8 Form-C Relay Outputs
  • CTI 2500C-8-IDO-24V 8 Isolated 24VDC Outputs
  • CTI 2500C-8-IDO-120V 8 Isolated 120VAC Outputs
  • CTI 2500C-16-DO-24V Sixteen 24VDC Digital Outputs
  • CTI 2500C-16-DO-120V Sixteen 120VAC Digital Outputs
  • CTI 500C-16-IDI-24V Sixteen Isolated 24V AC/DC Digital Inputs
  • CTI 2500C-16-IDI-120V Sixteen Isolated 120V AC/DC Digital Inputs
  • CTI 2500C-16-DIDO-SIM Sixteen Digital Input and Output SImulator
  • CTI 2500C-16-DI-24V Sixteen 24V AC/DC Digital Inputs
  • CTI 2500C-16-DI-120V Sixteen 120V AC/DC Digital Inputs
  • CTI 2500C-RBC-RS485 RS485 Remote Base Controller
  • CTI 2500C-RBC-PRF Profibus Remote Base Controller
  • CTI 2500C-PS-24V-35 35-Watt DC Power Supply
  • CTI 2500C-PS-120V-35 35-Watt AC Power Supply
  • CTI 2500C-R8 Eight-Slot Base
  • CTI 2500C-R4 Four-Slot Base
  • CTI 2500C-R16 Sixteen-Slot Base
  • CTI 2500C-2572-B Fast Ethernet TCP/IP Adapter
  • CTI 2500C-J750 Compact Janus PAC with 3MB Project Memory
  • CTI 2500C-C300 CPU with 512K User Memory
  • CTI 2500C-C200 CPU with 256K User Memory
  • CTI 2500C-C100 CPU with 128K User Memory
  • CTI 2500C-8-AO 8 Analog Outputs
  • CTI 2500C-8-AI 8 Analog Inputs
  • CTI 2559-FCAL Precision Calibration Connector
  • CTI 2559-FPC 40-Position Screw-Terminal Connector
  • CTI 2500-RFC PLC to RF Modem Cable
  • CTI 2500-40F 40-Position Standard Screw-Terminal Connector
  • CTI 2505 Vibration Sensor Interface Module
  • CTI 2554-A 4-Channel Isolated High Speed Counter Module
  • CTI 2553-A 2-Channel Mag Meter Input Module
  • CTI 2502 2-Channel High Speed Counter Input Module
  • CTI 2559-TC 8-Channel Thermocouple Input Module
  • CTI 2556-A 16-Channel Isolated Thermocouple Input Module
  • CTI 2556 16-Channel Isolated Thermocouple Input Module
  • CTI 2551-A 8-Channel Isolated Thermocouple Input Module
  • CTI 2559-RTD 8-Channel RTD Input Module
  • CTI 2557-A 16-Channel RTD Input Module
  • CTI 2557 16-Channel RTD Input Module
  • CTI 2552-A 8-Channel Isolated RTD Input Module
  • CTI 2534 8-Point Form-C Relay Output Module
  • CTI 2532 16-Point Form-A Relay Output Module
  • CTI  2531 32-Point Form-A Relay Output Module
  • CTI  2530 8-Point Form-C Relay Output Module
  • CTI  2562 8-Channel Analog Output Module
  • CTI  2560-A 8-Channel Isolated Analog Output Module
  • CTI  2501 8in/4out Analog Module
  • CTI  2558 8-Channel Analog Input Module
  • CTI  2555-A 16-Channel Analog Input Module
  • CTI  2550-A 8-Channel Isolated Analog Input Module
  • CTI  2599 8/16/32-Point AC Output Module
  • CTI  2598-8 8-Point AC Output Module
  • CTI   2598 8/16-Point AC Output Module
  • CTI   2597 8/16/32-Point DC Output Module
  • CTI 2596-8 8-Point DC Output Module
  • CTI 2596 8/16-Point DC Output Module
  • CTI 2595 16-Point TTL/Word Output Module
  • CTI 2591-EF 16-Point Isolated 11-146 VDC Output with Front Panel Accessible Fuses
  • CTI 2591-A 16-Point Isolated 11-146 VDC Output Module
  • CTI 2590-EF 16-Point Isolated 20-132 VAC Output with Front Panel Accessible Fuses
  • CTI 2590-A 16-Point Isolated Discrete 20-132 VAC Output Module
  • CTI 2589-B 8/16/32-Point Universal Discrete Input Module
  • CTI 2589-A 8/16/32-Point Universal Discrete Input Module
  • CTI 2588-8 8-Point Universal Discrete Input Module
  • CTI 2585 16-Point TTL/Word Input Module
  • CTI 2582 16-Point Isolated 125 VDC Input Module
  • CTI 2581 16-Point Isolated 12-56 VDC Input Module
  • CTI 2580 16-Point Isolated 95-132 VAC Input Module
  • CTI 2500-TAP RS485 Network Tap
  • CTI 2500-RIO-B RS485 Remote Base Controller
  • CTI 2500-RIO-A RS485 Remote Base Controller
  • CTI 2500-RBC Profibus Remote Base Controller
  • CTI 2515-A 100-Watt AC/DC Power Supply with Redundancy Support
  • CTI 2515 100-Watt AC Power Supply (MATURE - replaced by 2515-A)
  • CTI 2513-A 75-Watt DC Power Supply with Redundancy Support
  • CTI 2513 75-Watt 24VDC Power Supply
  • CTI 2512-A 75-Watt AC/DC Power Supply with Redundancy Support
  • CTI 2512 75-Watt AC/DC Power Supply
  • CTI 2510 125 VDC Power Supply
  • CTI 2500-SSB Single Slot Blank Front Panel
  • CTI 2500-R11-A Eleven-Slot Redundant Base
  • CTI 2500P-R16 Sixteen-Slot Base with High-Speed Channel