DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

ABBAdvance Optima Continuous gas analyzers AO2000

From:ABB | Author:LIAO | Time :2025-08-09 | 267 Browse: | Share:

Description Application Information from the AO2000 gas analyzer can be transferred to a PC or DCS via the Modbus. Measurement values, status signals and also signals of analog and digital inputs and outputs are thus available for further usage. Using the AO-MDDE server the signals can be integrated into standard software (e.g. Excel, Visual Basic or LabVIEW). For further information, see Chapter 4 “AO-MDDE server and demo programs”, page 3535. AO-MDDE can be downloaded from the DVD-ROM which is delivered together with each gas analyzer. AO-MDDE does not support Modbus over TCP/IP. Basic documents 

 Modbus Application Protocol Specification V1.1b, December 28, 2006 

 Modbus over Serial Line Specification and Implementation Guide V1.02, December 20, 2006 

 Modbus Messaging on TCP/IP Implementation Guide V1.0b, October 24, 2006 These documents are available at http://www.modbus.org/specs.php. Interfaces and connection versions The RS232 and the RS485 interface located on the RS232/RS485 module in AO2000 are supported, where only one can be operated at a time. Connection versions are described in Chapter 3 “Modbus connection”, page 30. As an alternative, the Ethernet 10/100BASE-T interface can be used for data transmission via Modbus TCP/IP protocol (from software version 5.1, see page 7).

Data transfer For data transfer a combination of frames is used, that consists of 1/0 information, united to one or more telegrams. Frame The transfer values are decomposed in bytes (= 8 bit). Each of these bytes is completed by one start-bit, possibly one parity-bit (even number of “1”) and one stop-bit. In the following description the term “byte” will be used, even if ten or eleven bits will be transferred including the start-, stop- and parity-bits. Telegrams The Modbus telegrams consist of the following frames: address (1 byte), function (1 byte), data (n bytes) and check sum (2 bytes). The telegrams also take on the “shake-hands-function”: each telegram from master to slave must be responded, before a new telegram is allowed to be transmitted. The computer has to have in a adequate supervision, for excluding non answering bus participants (time-out-supervision). Admissible addresses As addresses for the participants of the bus the numbers 1 to 255 are admitted. The address 0 is the global address (broadcast-address). When this address will be used in a telegram, all participants accept this telegram without an acknowledgment to the master.

Integration The AO2000 Modbus/TCP server expects requests from the current IP addresses via the communication port. A maximum of 4 clients can be connected to the Modbus/TCP server of an AO2000 at the same time. If the connection to a client breaks down, the connection status in the Modbus/TCP server is enabled again after a max. 60 seconds. Reading out data from the AO2000 Modbus/TCP server The following procedure must be executed on the Modbus client, in order to receive data from the AO2000 Modbus/TCP server: 1. Establish a TCP connection to port 502 on the server. 2. Create a Modbus request. 3. Send the Modbus request incl. the Modbus/TCP MBAP Header. 4. Wait for a response to the same TCP connection. 5. Read the first 6 bytes of the response; these state the length of the response. 6. Read the remaining bytes of the response. Functions, addresses and registers The supported functions and the addresses and registers of Modbus over TCP/IP are equivalent to those of Modbus over RS232/RS485

Function code Function code 43 with MEI 14 (MEI = Modbus Encapsulated Interface) is used to read the device parameters to  read measured values,  transfer simulation data,  apply reference material. Address assignment of the device parameters for the function code 43 There is read access to the device parameters. Measurement components are mapped with the following structure:  Name  Measurement range start  Measurement range end  Unit The number of the first measured values register is listed under BasisM in the device parameters list. The measured value status is implemented as NAMUR status: Bit Assignmant 0 Error 1 Maintenance 2 Maintenance request 3 Beyond specification 4 Test operation, simulation measured value transmitted 5…15 Reserved for extensions 16…31 Vendor-specific The number of the first simulation data register is listed under BasisS in the device parameters list. The number of the register to apply reference material is listed under BasisR in the device parameters list. Maximum 32 Bus DIs are reserved for transferring reference material. The register "status of application" is used for feedback of the DIs for which a hardware digital output is connected. When reference material is applied, the status "maintenance" is set and a message is displayed on the gas analyzer's screen


Principle The AO2000 series gas analyzers are modular and very flexible. A gas analyzer can consist of one or more analyzer modules which in itself can measure one or more components. It is also possible to connect different kinds of I/O-modules and I/O-boards to a device. For this reason the Modbus addressing schema is not static. Data format There are six flexible groups, four configurable groups and two fixed length groups of information defined in a AO2000 gas analyzer. The grouped information can be read through “Single Modbus Request”. Flexible groups The flexible groups are:  Measurement values (see page 12)  Analog inputs (see page 12)  Analog outputs (see page 13)  Digital inputs (see page 13)  Digital outputs (see page 14)  Measurement range feedback (see page 17)  Measurement range configuration (see page 18)  Measurement range drift values (see page 19)  QAL3 calibration data (see page 21) Each flexible group has a fixed start address and, depending on the system layout, a variable number of elements. Configurable groups The configurable groups are:  Bus analog inputs (see page 14)  Bus analog outputs (see page 15)  Bus digital inputs (see page 15)  Bus digital outputs (see page 15) Each configurable group has a fixed start address and, depending on the user configuration, a variable number of elements. Fixed length groups The fixed length groups are:  Configuration display (see page 16)  Status (see page 16)

  • ENTERASYS A4H254-8F8T Ethernet switch
  • ENTERASYS C2RPS-CHAS2 SecureStack c2 Redundant power supply chassis
  • ENTERASYS A2H124-24 Ethernet edge switch
  • EMG LID43.03 Reference voltage source
  • EMERSON PR6426010-110+C0N021916-240 32mm Eddy Current Sensor
  • EMERSON PR6423/011-110+C0N021 Eddy Current Signal Converter
  • EMERSON VE4003S2B1 DeltaV™ M-series Traditional I/O
  • EMERSON 2500M/AI4UNIV analog input module
  • EMERSON PMCspan PMC Expansion Mezzanine
  • EMERSON PR6424/011-140 16mm Eddy Current Sensor
  • EMERSON KJ3242X1-BK1 12P4711X042 S-Series H1 Card
  • EMERSON 960132-01 FX-316 Positioning Servo Drive 230 VAC
  • EMERSON KJ4006X1-BD1 Interface Terminal Block
  • EMERSON 1C31181G01 module
  • EMERSON CE4003S2B6 I/O Termination Block
  • EMERSON KJ4001X1-CK1 40-Pin Mass Termination Block
  • EMERSON VE4012S2B1 Module
  • EMERSON KL4103X1-BA1 CHARMs Smart Logic Solver Carrier
  • EMERSON A6370D/DP Overspeed Protection Monitor
  • EMERSON P188.R2 Industrial interface module
  • EMERSON VE3008 CE3008 KJ2005X1-MQ1 12P6381X042 MQ Controller
  • EMERSON TPMC917 4MB SRAM with Battery Backup and 4 Channel RS232
  • EMERSON P152.R4 Multifunctional module
  • EMERSON DA7281520 P152 Processor board
  • EMERSON PR6423/008-110 8mm Eddy Current Sensor
  • EMERSON PR6423/000-131 8mm Eddy Current Sensor
  • EMERSON MVME61006E-0163R VMEbus Single-Board Computer
  • EMERSON Ovation 5X00453G01 Remote I/O Node Controller Module
  • EMERSON 5X00070G04 Analog input
  • EMERSON Ovation 5X00070G01 Analog Input Module
  • EMERSON Ovation 5X00790G01 Compact Controller Module
  • EMERSON 5X00846G01 HART analog output module
  • EMERSON 1C31113G01 Digital output module (5-60VDC)
  • EMERSON KJ4110X1-BA1 I/O terminal module
  • EMERSON CSI3125 A3125/022-020 Shaft-Vibration Monitor
  • EMERSON 5X00273G01 Digital output module
  • EMERSON KJ4001X1-NB1 12P3368X012 REV:E 1-Wide I/O Carrier Extender Left
  • EMERSON KJ4001X1-NA1 12P3373X012 REV:C 1-Wide I/O Carrier Extender Right
  • EMERSON A6312/06 Speed and Key Monitor
  • EMERSON KJ4001X1-BE1 8-Wide I/O Carrier
  • EMERSON KJ2005X1-MQ1 KJ2005X1-MQ2 13P0072X082 MQ Controller
  • EMERSON 5X00226G03 - Ovation™ I/O Interface Controller, Electronics Module
  • EMERSON PR6423/00R-010+CON031 Vibration sensor
  • EMERSON 9199-00002 A6120 Control Module
  • Emerson Ovation 1C31234G01 - Ovation™ 16 Channel Compact Digital Input
  • Emerson Ovation KJ3002X1-BF1 12P1732X042 Controller module
  • Emerson Ovation 5X00226G01 I/O Interface Module
  • Emerson Ovation™ Controller Model OCR1100(5X00481G04/5X00226G04)
  • Emerson Ovation 5X00499G01 Digital Input 24Vdc Single 32CH
  • Emerson Ovation 5X00500G01 32-Channel Digital Output Module
  • Emerson ovation VE4001S2T2B4 Analog output card
  • Emerson ovation 5X00501G01 5X00502G01 Ethernet link controller
  • EMERSON A6824R 9199-00098-13 Module
  • EMERSON A6140 9199-00058 Industrial Control Module
  • EMERSON 1C31194G03 Industrial Control Module
  • EMERSON DB1-1 Industrial Control Module
  • EMERSON PMC-IO-ADAPTER I/O module
  • EMERSON L0115012 L0115032 Control module
  • EMERSON PMC-IO-PROZESSOR Process control module
  • EMERSON PMC PROFINET Manage Gigabit Ethernet switches
  • EMERSON A3120022-000 CSI3120 Bearing-Vibration Monitor
  • EMERSON SE3008 KJ2005X1-SQ1 12P6383X032 Controller
  • EMERSON 1000554 Printed circuit board
  • EMERSON PR6423/002-041 Sensor module
  • EMERSON 1C31232G02 Westinghouse control module
  • Abaco TRRM940 Switch
  • Abaco SWE440A Switch
  • Abaco NETernity™ RM984RC Ethernet Switch
  • Abaco NETernity™ GBX411 Ethernet Switch
  • Abaco NETernity™ GBX25
  • Abaco NETernity SWE540A
  • Abaco CP3-GESW8-TM8 Ethernet switch
  • Abaco SWE440S Ethernet switch
  • Abaco SWE450S 100GbE 3U VPX Switch Aligned to SOSA™ Standard
  • Abaco SWE550S 100GbE 6U VPX Switch Aligned to SOSA™ Standard
  • Abaco SPR870A Wideband Digital Receiver/Exciter
  • Abaco SPR507B Serial FPDP XMC/PMC
  • Abaco ICS-1572A Transceiver Module
  • Abaco daq8580 FMV Compression System
  • Abaco VP868 FPGA Card
  • Abaco HPC2812 Rugged 6U VPX High Performance Computer with Dual Intel
  • Abaco VSR347D 3U VPX Rugged Virtual Secure Router
  • Abaco VSR8000 Fully Rugged, COTS System Secure Router
  • Abaco RES3000 Compact, Rugged Ethernet Switches
  • Abaco PMC238 Expansion Card
  • Abaco EXP238 PMC/XMC Expansion Card for XVB603 VME Single Board Computer
  • Abaco VME-REPEAT-A-L VMEbus Repeater Link
  • Abaco VME-4514A VME Analog I/O Input/Output Board
  • Abaco VME-3128A Analog I/O
  • Abaco VME-3125A analog-to-digital Conversion board
  • Abaco VME-3123A VME Analog I/O Input Boards
  • Abaco PMC239/F Analog input/output board
  • Abaco PEX431 Multi-fabric Switch
  • Abaco CPCI-100A-BP 2-slot IndustryPack carrier for 3U CompactPCI
  • Abaco PMC522 Serial Controller
  • Abaco PMC522/FP Serial Controller
  • Abaco VME-2170A Digital Output 32-bit optically isolated
  • Abaco VME-1129 Digital Input Board 128-bit high voltage
  • Abaco IP-OCTALPLUS232 Eight EIA-232 asynchronous serial ports
  • Abaco IP-DIGITAL482 Digital I/O with 48 TTL Channels
  • Abaco PMC523 16-Port Serial Controller
  • EMERSON CE4003S2B1 M-series Traditional I/O
  • EMERSON SE3008 DeltaV™ SQ Controller
  • EMERSON 1C31227G01 - Ovation™ 8 Channel Analog Input
  • EMERSON 1C31224G01 - Ovation™ 8 Channel Analog Input
  • ABB UNS0119A-P,V101 3BHE029154P3 3BHE029153R0101 Digital input
  • ABB 3BDH000050R1 AM811F Battery Module
  • ABB 3ASC25H705-7 Digital output board
  • ABB UDD406A 3BHE041465P201 control board
  • ABB 3BHE014967R0002 UNS 2880B-P,V2: COB PCB Assembled
  • ABB PPC380AE02 HIEE300885R0102 module
  • ABB NU8976A99 HIER466665R0099 Processor Module
  • ABB DIS0006 2RAA005802A0003G Digital Input Module
  • ABB Bailey IMDS003 infi 90 Digital Output Slave Module
  • ABB XO08R1-B4.0 Expand the output relay module
  • ABB VA-MC15-05 Controller module
  • ABB VA-3180-10 Controller module
  • ABB 72395-4-0399123 Excitation module
  • ABB PU516A 3BSE032402R1 Engineering Board - PCI
  • ABB 3BHE044481R0101 3BHE044477P3 PPE091A101 Module
  • ABB UCD224A102 Control unit
  • ABB SNAT603CNT SNAT 603 CNT Motor Control Board
  • ABB SNAT634PAC Drive board
  • ABB UAD149A0011 Servo controller
  • ABB UCD224A103 Industrial controller module
  • ABB 3BHE029154P3/3BHE029153R0101 UNS0119A-P,V101 Processor Module
  • ABB ARCOL 0338 ARCOL 0346 Solid-state motor starter
  • ABB ARCOL 0339 Solid-state motor controller