DCS Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

WATLOWCLS200, MLS300, and CAS200 Communications Specification

From:WATLOW | Author:LIAO | Time :2025-08-25 | 913 Browse: | 🔊 Click to read aloud ❚❚ ▶ | Share:

with the 7th bit set—in other words, it sends an x41 or x48.

STS (The Status Byte)

• The controller uses the status byte, or STS, to return general status 

and error flags to the host software. (The controller ignores the status 

byte in the host software's command packet.) The next table shows 

status byte values and definitions. 

• An “x” in the status bytes below indicates that the associated nibble 

may contain additional information. In most cases, the status byte is 

composed of two independent nibbles. Each nibble is independent 

so that two codes can return at once. For example, status code F1 

indicates that data has changed (Fx) and the controller is being 

updated through the front panel (x1).

Status

in Hex Description

00 The controller has nothing to report, or AB protocol is selected.

01 Access denied for editing. The controller is being updated through the 

front panel.

02 AIM Comm failure.

A0 A controller reset occurred.

Cx The controller received a command that was not a block read or block 

write. (Command Error)

Dx The block write command attempted to write beyond a particular parameter block boundary, or the host software attempted to access a data table 

block that does not exist. (Data Boundary Error)

Ex The Alarm_Status variable has changed. The software should query the 

alarm status block to determine the particular alarm flag that changed.

Fx The controller altered shared data, either internally (from the firmware) or 

externally (from the keyboard). The host software should read the Data 

Changed Register to determine which data has been altered and update 

its own run-time memory

TNSL

• Least significant byte of the transaction number. This is the first half 

of a “message stamp.”

• The controller sends back the TNSL and TNSH exactly as it received 

them, so host software can use the TNSL and TNSH bytes to keep 

track of message packets.

TNSH 

• Most significant byte of the transaction number. This is the second 

half of the “message stamp.” 

ADDL

• The low byte of the beginning data table address of the block of data 

to read or write.

ADDH

• The high byte of the beginning data table address of the block of data 

to read or write.

DATA

• The new values to be set with a write command, or the requested data 

in a response to a read command.

DLE ETX

• Every packet of information must end with the codes DLE ETX. 

These codes signal the end of a transmission.

BCC or CRC

• Communications packets include a one- or two-byte error check at 

the end of the packet. There are two error check methods: Block 

Check Character (BCC), which requires 1 byte, and Cyclic Redundancy Check (CRC), which requires 2 bytes.

Watlow Anafaze recommends that you use the default error check

method, BCC. It is easier to implement than CRC, and it is acceptable

for most applications.

Select one error check method and configure both software and

controller for that method, or they will be unable to communicate.

The error check methods work this way:

Block Check Character (BCC)

BCC checks the accuracy of each message packet transmission. It

provides a medium level of security. The BCC is the 2’s complement of

the 8-bit sum (modulo-256 arithmetic sum) of the data bytes between

the DLE STX and the DLE ETX. (1’s complement +1)

• BCC does not detect transposed bytes in a packet. 

• BCC cannot detect inserted or deleted 0 values in a packet.

• If you have sent an x10 as data (by sending DLE x10) only one of the 

DLE data bytes is included in the BCC’s sum (the DLE = x10 also).

For instance, the block read example shown in the examples section, 

adds x08 00 01 00 00 80 02 10. Note that the x10 representing DLE 

has been left out of the calculation. The sum should come to x9B.

Cyclic Redundancy Check (CRC)

CRC is a more secure error check method than BCC. It provides a very

high level of data security. It can detect:

• All single-bit and double-bit errors.

• All errors of odd numbers of bits.

• All burst errors of 16 bits or less.

• 99.997% of 17-bit error bursts.

• 99.998% of 18-bit and larger error bursts.

The CRC is calculated using the value of the data bytes and the ETX

byte. At the start of each message packet, the transmitter must clear a

16-bit CRC register. 

When a byte is transmitted, it is exclusive-ORed with the right 8 bits of

the CRC register and the result is transferred to the right 8 bits of the

CRC register. The CRC register is then shifted right 8 times by inserting

0’s on the left. 

Each time a 1 is shifted out on the right, the CRC register is ExclusiveORed with the constant value xA001. After the ETX value is

transmitted, the CRC value is sent, least significant byte (LSB) first.

Below is a structured English procedure from AB Manual:

data_byte = all application layer data, ETX

CLEAR CRC_REGISTER

FOR each data_byte

GET data_byte

XOR (data_byte, right eight bits of CRC_REGISTER)

PLACE RESULT in right eight bits of CRC_REGISTER

DO 8 times

Shift bit right, shift in 0 at left

IF bit shifted =1

XOR (CONSTANT, CRC_REGISTER)

PLACE RESULT in CRC_REGISTER

  • DEIF RMF-112D Frequency relay
  • DEIF RMC-142D Current relay
  • DEIF RMC-132D Current relay
  • DEIF RMC-131D Current relay
  • DEIF RMC-122D Current relay
  • DEIF RMC-121D Current relay
  • DEIF RMC-111D Current relay
  • DEIF MVR-V211 Busbar Protection
  • DEIF MVR-T257 Transformer Differential Protection
  • DEIF MVR-T256 Transformer Differential Protection
  • DEIF MVR-T216 Transformer Differential Protection
  • DEIF MVR-T215 Transformer Protection
  • DEIF MVR-M257 Motor Differential Protection
  • DEIF MVR-M255 Motor Protection
  • DEIF MVR-M215 Motor Protection
  • DEIF MVR-M210 Motor Protection
  • DEIF MVR-G257 Generator Differential Protection
  • DEIF MVR-G215 Generator Protection
  • DEIF MVR-F255 Directional Feeder Protection
  • DEIF MVR-F215 Directional Feeder Protection
  • DEIF MVR-F210 Feeder Protection
  • DEIF MVR-F205 Directional Feeder Protection
  • DEIF MVR-F201 Basic Feeder Protection
  • DEIF MVR-200 series Medium Voltage Relay
  • DEIF MDR-2 Multi-differential relay
  • DEIF LMR-122D Loss of mains relay
  • DEIF LMR-111D Loss of mains relay
  • DEIF APU-4 Advanced G59 and G99 protection unit
  • DEIF iE 650 PLC - The most robust programmable automation controller available
  • DEIF iE 350 PLC - Programmable Automation PLC Controller
  • DEIF iE 250 PLC Versatile and modular intelligent energy PLC controller
  • DEIF PPM-3 EDG Protection and Power Management
  • DEIF AGC 3X 4198000234E AUTOMATIC GENSET CONTROLLER
  • SAUTER ASF123 Damper actuator with spring return
  • SAUTER ASF122 Damper actuator with spring return
  • SAUTER ASF113F122 Damper actuator with spring return
  • SAUTER ASF113F120 Damper actuator with spring return
  • SAUTER ASF112F122 Damper actuator with spring return
  • SAUTER ASF112F120 Damper actuator with spring return
  • SAUTER ASM 124/134 series - ASM134F130 Damper actuator
  • SAUTER ASM 134 series - ASM134SF132 Damper actuator
  • SAUTER ASM 124/134 series - ASM124SF132 Damper actuator
  • SAUTER ASM 124/134 series - ASM124F122 Damper actuator
  • SAUTER ASM 124/134 series - ASM124F120 Damper actuator
  • SAUTER Valve actuator ASM 105S/115S series ASM115SF152
  • SAUTER Valve actuator ASM 105S/115S series ASM105SF152
  • SAUTER Valve actuator ASM 105S/115S series ASM115SF132
  • SAUTER Valve actuator ASM 105/115 series ASM105SF132
  • SAUTER Valve actuator ASM 105/115 series ASM115F122
  • SAUTER Valve actuator ASM 105/115 series ASM115F120
  • SAUTER Valve actuator ASM 105/115 series ASM105F122
  • SAUTER Valve actuator ASM 105/115 series ASM105F120
  • SAUTER Valve actuator ASM 105/115 series ASM105F10
  • SAUTER AKF113S Rotating actuator AKF 112/113 series
  • SAUTER AKF113F122 Rotating actuator AKF 112/113 series
  • SAUTER AKF113F120 Rotating actuator AKF 112/113 series
  • SAUTER AKF112F122 Rotating actuator AKF 112/113 series
  • SAUTER AKF112F120 Rotating actuator AKF 112/113 series
  • SAUTER AKM115SAF332: Smart Actuator for ball valve, BACnet/IP
  • SAUTER AKM115SAF232  Rotating Actuator  AKM 115SA Smart Actuator
  • SAUTER AKM115SF152  Rotating Actuator  AKM 105S/115S Series
  • SAUTER AKM115SF132  Rotating Actuator  AKM 105S/115S Series
  • SAUTER AKM105SF132  Rotating Actuator  AKM 105S/115S Series
  • SAUTER AKM115F122 Rotating actuator  AKM 105/115 series
  • SAUTER Rotating actuator  AKM 105/115 series AKM115F120
  • SAUTER Rotating actuator  AKM 105/115 series AKM105F122
  • SAUTER Rotating actuator  AKM 105/115 series  AKM105F120
  • SAUTER Continuous actuator for unit valves, with stroke AXS215S
  • SAUTER Linear valve actuator AXT/AXS series AXT211
  • SAUTER Linear valve actuator AXT/AXS series AXT201
  • SAUTER Linear valve actuator AXM/AXF series AXF217S
  • SAUTER Linear valve actuator AXM/AXF series AXM217S
  • SAUTER AXM217SF404 is an electric actuator for unit valves.
  • SAUTER AXM217SF402 is an electric actuator for unit valves.
  • SAUTER Linear valve actuator AXM/AXF series AXM217
  • SAUTER Linear valve actuator AVF 124/125 series AVF125S
  • SAUTER Linear valve actuator AVF 124/125 series AVF124S
  • SAUTER Linear valve actuator AVF 124/125 series AVF124S
  • SAUTER AVM322S-R Linear valve actuator AVM 234S series
  • SAUTER AVM322-R Linear valve actuator AVM 234S series
  • SAUTER AVM322SF132 Linear valve actuator AVM 234S series
  • SAUTER AVM321SF132    Linear Valve Actuator
  • GE Power Conversion P112-6053 Advanced Micro Controller (AMC2)
  • GE Power Conversion P111-6053 Advanced Micro Controller (AMC2)
  • GE Power Conversion P110-6053 Advanced Micro Controller (AMC2)
  • GE Power Conversion P122-6052 Advanced Micro Controller (AMC2)
  • GE Power Conversion P121-6052 Advanced Micro Controller (AMC2)
  • GE Power Conversion P112-6152 Advanced Micro Controller (AMC2)
  • GE Power Conversion P110-6152 Advanced Micro Controller (AMC2)
  • GE Power Conversion P112-6052 Advanced Micro Controller (AMC2)
  • GE P106-6052 AMC2 Advanced Micro Controller Unit
  • SAUTER AVF234SF232 Linear valve actuator AVM 234S series
  • SAUTER AVF234SF132 Linear valve actuator AVM 234S series
  • SAUTER Linear valve actuator AVM 234S series AVM234SF132-6
  • SAUTER Linear valve actuator AVM 234S series AVM234SF132-5
  • SAUTER Linear valve actuator AVM 234S series AVM234SF132
  • SAUTER Linear valve actuator AVM215SF132-7
  • SAUTER Linear valve actuator AVM215SF132R
  • Linear valve actuator AVM 115SA Smart Actuator AVM115SAF332
  • Linear valve actuator AVM 115SA Smart Actuator AVM115SAF232
  • SAUTER Linear valve actuator AVM 105S/115S series AVM115SF132
  • SAUTER Linear valve actuator AVM 105S/115S series AVM105SF132
  • SAUTER AVM115F901 Linear Valve Actuator
  • SAUTER AVM115F122 Linear Valve Actuator
  • SAUTER AVM115F120 Linear Valve Actuator
  • SAUTER AVM105F122 Linear Valve Actuator
  • SAUTER AVM105F120 Linear Valve Actuator
  • SAUTER AVM105F100 Linear Valve Actuator
  • AEROTECH SM Series High-Performance Stepper Motors
  • AEROTECH BLMSC Series Linear Motors
  • AEROTECH Custom Linear Motors
  • AEROTECH BMS Series Brushless, Slotless Rotary Motors
  • AEROTECH BM Series Brushless Rotary Motors
  • AEROTECH BLMX Series Linear Motors
  • AEROTECH BLMH Series Linear Motors
  • AEROTECH BLM Series Linear Motors
  • AEROTECH BLMC Series Linear Motors
  • AEROTECH BLMUC-143  Linear motor forcer with thermistor
  • AEROTECH BLMUC-111    Linear motor forcer with thermistor
  • AEROTECH BLMUC-95  Linear motor forcer with thermistor
  • AEROTECH BLMUC-79 Linear motor forcer with thermistor
  • AEROTECH BLMUC Series Linear Motors
  • AEROTECH Automation1 FLEX Distributed Amplifier Multi-Axis Servo Control System
  • AEROTECH Automation1 HXA4 6-Axis Hexapod Servo Drive
  • AEROTECH Automation1 iHXA4 6-Axis Hexapod Servo Drive with Motion Controller
  • AEROTECH Modular System Control Console
  • AEROTECH TV Series Transformers
  • AEROTECH TM Series Transformers