DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

ABBElectro-Pneumatic Positioner TZIDC

From:ABB | Author:LIAO | Time :2025-08-27 | 297 Browse: | Share:

Low operating cost 

Compact design 

Well-proven technology 

Robust and environmentally ruggedized 

Wide operating temperature range 

 -40 ... 85 °C (-40 ... 185 °F) 

Easy to commission, “single pushbutton” 

operating philosophy 

Mechanical position indicator 

ATEX, FM, CSA, GOST and IECEx approvals 

For SIL2 safety loops 

1 Description Pos: 3.2 /==== Wechsel ein- auf zweispaltig ==== @ 0mod_1130421847171_3101.doc @ 3828 

Wechsel ein-auf zweispaltig Pos: 3.3 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Kurzbeschreibung @ 10mod_1173180169769_3101.doc @ 71118 

The TZIDC is an electronically configurable positioner with 

communication capabilities designed for mounting to pneumatic 

linear or rotary actuators. It features a small and compact design, a 

modular construction, and an excellent cost-performance ratio. 

Fully automatic determination of the control parameters and 

adaptation to the final control element yield considerable time savings 

and an optimal control behavior. 

Pos: 3.4 /Überschriften/1.1/2-spaltig/Pneumatik @ 10mod_1176211138453_3101.doc @ 76683 

1.1 Pneumatics Pos: 3.5 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Pneumatik @ 10mod_1173180645393_3101.doc @ 71139 a 

An I/P module with subsequent pneumatic amplifier is used to control 

the pneumatic actuator. The well-proven I/P module proportionally 

converts the permanent electrical positioning signal from the CPU 

into a pneumatic signal used to adjust a 3/3-way valve. 

The air flow for pressurizing or depressurizing the actuator is 

continuously adjusted. As a result, excellent control is achieved. 

When reaching the set point, the 3/3-way valve is closed in center 

position to minimize the air consumption. 

Four different pneumatics versions are available: for single-acting or 

double-acting actuators, each with “fail-safe” or “fail-freeze” function. 

Pos: 3.6 /Überschriften/1.1.1/2-spaltig/Sicherheitsfunktion "entlüftend" @ 10mod_1176211744343_3101.doc @ 76809 

1.1.1 “Fail-safe” function 

Pos: 3.7 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Sicherheitsfunktion "entlüftend" @ 10mod_1176211673796_3101.doc @ 76788 

If the electrical power supply fails, the positioner output 1 is 

depressurized, and the pneumatic actuator’s return spring moves the 

valve to the defined safe position. In case of a double-acting actuator 

the second output 2 is additionally pressurized. 

Pos: 3.8 /======= Spaltenumbruch ======== @ 0mod_1132937966324_3101.doc @ 3831 

Pos: 3.9 /Überschriften/1.1.1/2-spaltig/Sicherheitsfunktion "blockierend" @ 10mod_1176211798765_3101.doc @ 76830 

1.1.2 “Fail-freeze” function 

Pos: 3.10 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Sicherheitsfunktion "blockierend" @ 10mod_1176211845484_3101.doc @ 76851 

If the electrical power supply should fail, the positioner output 1 (and 

2, if applicable) is closed and the pneumatic actuator stops 

(“freezes”) the valve in the current position. If compressed air supply 

should fail, the positioner depressurizes the actuator. 

Pos: 3.11 /Überschriften/1.1/2-spaltig/Bedienung @ 10mod_1176211172234_3101.doc @ 76704 

1.2 Operation Pos: 3.12 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/Bedienung (Kommunikationsmöglichkeit) @ 10mod_1173184631054_3101.doc @ 71160 

The positioner has a built-in operating panel providing a 2-line LCD 

and 4 pushbuttons for optimal local configuration, commissioning and 

operational monitoring. 

Alternatively, the appropriate configuration program and the available 

communication option can be used. 

Pos: 3.13 /Überschriften/1.1/2-spaltig/Kommunikation @ 10mod_1176211201546_3101.doc @ 76725 

1.3 Communication Pos: 3.14 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kurzbeschreibung/Kommunikation @ 10mod_1176212225390_3101.doc @ 76893 

The standard TZIDC model has a local communication interface (LKS 

connector). Additionally, a “HART communication” option for 

communication via the 20 mA signal is available. Both 

communications are based on the HART Protocol. 

Pos: 3.15 /Überschriften/1.1/2-spaltig/Ein-/Ausgänge @ 10mod_1176211233015_3101.doc @ 76746 

1.4 Inputs and outputs Pos: 3.16 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kurzbeschreibung/Ein-/Ausgänge @ 10mod_1176212290390_3101.doc @ 76914 

In addition to its input for the analog position set point the TZIDC 

positioner is equipped with a digital input which can be used to 

activate various protective functions in the device via the process 

control system. A digital output allows you to output collective alarms 

or fault messages. 

Pos: 3.17 /Überschriften/1.1/2-spaltig/Modularer Aufbau @ 10mod_1176211317984_3101.doc @ 76767 

1.5 Modular design Pos: 3.18 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Kurzbeschreibung/ModularerAufbau @ 10mod_1173184783043_3101.doc @ 71181 q 

The TZIDC basic model can be enhanced at any time by retrofitting 

optional equipment. Option modules for analog or digital position 

feedback or a shutdown-module can be installed. Additionally, a 

mechanical position indicator, proximity switches or 24 V 

microswitches are available for indicating the position independently 

of the mother board function

Electro-Pneumatic Positioner TZIDC 10/18-0.22-EN 

for 4 … 20 mA two-wire technology

Basic model Optional upgrades 

1 LKS plug 9 Plug module for analog feedback (4 … 20 mA) 

2 Positioning signal 4 … 20 mA 10 Plug-in module for safety shutdown (forced depressurization) 

3 Digital input 11 Plug module for digital feedback 

4 Digital output DO 12 Installation kit for mechanical position indicator 

5 Supply, 1.4 … 6 bar 13 Installation kit for digital feedback with proximity switches 

6 Exhaust 14 Installation kit for digital feedback with 24 V microswitches 

7 I/P module with 3/3-way valve 

8 Position sensor (optional up to 270° rotation angle) 

Important 

With optional upgrades either the “Installation kit for digital feedback with proximity switches” (13) or the “Installation 

kit for digital feedback with microswitches 24 V” (14) can be used. 

In both cases, the “mechanical position indicator” (8) must be installed. 

2 Mounting versions Pos: 5.2 /==== Wechsel ein- auf zweispaltig ==== @ 0mod_1130421847171_3101.doc @ 3828 

Wechsel ein-auf zweispaltig Pos: 5.3 /Überschriften/1.1/2-spaltig/Genormter Anbau an pneumatische Linearantriebe @ 10mod_1176212852312_3101.doc @ 76956 

2.1 To linear actuators in accordance with the 

standard Pos: 5.4 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Montage/Genormter Anbau an pneumatische Linearantriebe @ 10mod_1176213091968_3101.doc @ 77040 

Lateral attachment is in accordance with DIN / IEC 534 (lateral 

attachment to NAMUR). The required attachment kit is a complete 

set of attachment material, but does not include the screwed pipe 

connections and air pipes. 

Pos: 5.5 /Überschriften/1.1/2-spaltig/Genormter Anbau an pneumatische Schwenkantriebe @ 10mod_1176212899953_3101.doc @ 76977 

2.2 To rotary actuators in accordance with the 

standard Pos: 5.6 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Montage/Genormter Anbau an pneumatische Schwenkantriebe @ 10mod_1176213146937_3101.doc @ 77061 

This attachment is designed for mounting according to the standard 

VDI/VDE 3845. The attachment kit consists of a console with 

mounting screws for mounting on a rotary actuator. The adapter for 

coupling the positioner feedback shaft to the actuator shaft has to be 

ordered separately. Screwed pipe connections and air pipes have to 

be provided on site. 

Pos: 5.7 /======= Spaltenumbruch ======== @ 0mod_1132937966324_3101.doc @ 3831 

Pos: 5.8 /Überschriften/1.1/2-spaltig/Integrierter Anbau an Regelventile @ 10mod_1176212940421_3101.doc @ 76998 

2.3 Integral mounting to control valves Pos: 5.9 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Montage/Integrierter Anbau an Regelventile, TZIDC-1x0 @ 10mod_1176213402234_3101.doc @ 77103 

The TZIDC positioner featuring standard pneumatic action is also 

suitable for integral mounting. 

The required holes are found at the back of the device. 

The benefit of this design is that the point for mechanical stroke 

measurement is protected and that the positioner and actuator are 

linked internally. No external tubing is required. 

Pos: 5.10 /Überschriften/1.1/2-spaltig/Besondere antriebsspezifische Anbauversionen @ 10mod_1176212991062_3101.doc @ 77019 

2.4 Special actuator-specific mounting Pos: 5.11 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Montage/Besondere antriebsspezifische Anbauversionen @ 10mod_1173186727709_3101.doc @ 71265 

In addition to the mounting methods described above, there are 

special actuator-specific attachments. 

Please contact us for details. 

Electro-Pneumatic Positioner TZIDC 10/18-0.22-EN 

Fig. 2: Mounting options 

1 Mounting to linear actuators acc. to DIN / IEC 534 3 Integral mounting to control valves 

2 Mounting to rotary actuators to VDI / VDE 3845 4 Integral mounting to control valves by using an adapter panel 

3 Operation Pos: 7.2 /==== Wechsel ein- auf zweispaltig ==== @ 0mod_1130421847171_3101.doc @ 3828 

Wechsel ein-auf zweispaltig Pos: 7.3 /Überschriften/1.1/2-spaltig/Allgemeines @ 10mod_1176213970765_3101.doc @ 77124 A 

3.1 General Pos: 7.4 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Betrieb/Allgemeines @ 10mod_1176214294328_3101.doc @ 77292 

Microprocessor-based position control in the TZIDC provides for 

optimal results. The positioner features high-precision control 

functions and high operational reliability. Due to their elaborate 

structure and easy accessibility, the device parameters can be 

quickly adapted to the respective application. 

The total range of parameters includes: 

- Operating parameters 

- Adjustment parameters 

- Monitoring parameters 

- Diagnosis parameters 

- Maintenance parameters 

Pos: 7.5 /Überschriften/1.1.1/2-spaltig/Betriebsparameter @ 10mod_1176214001500_3101.doc @ 77145 

3.1.1 Operating parameters 

Pos: 7.6 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Betriebsparameter @ 10mod_1176214346265_3101.doc @ 77343 

The following operating parameters can be set manually if required: 

Signal 

Signal min. 4 mA, max. signal 20 mA (0 ... 100 %) 

freely selectable for split-range operation 

min. range 20 % (3.2 mA) 

recommended range > 50 % (8.0 mA) 

Action (positioning signal) 

Increasing: Signal 4 ... 20 mA = position 0 ... 100 % 

Increasing: Signal 20 ... 4 mA = position 0 ... 100 % 

Characteristic curve (travel = f {signal}) 

Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1 or freely 

configurable with 20 reference points. 

Travel limit 

The positioning travel, i.e. the stroke or angle of rotation, can be 

reduced as required within the full range of 0 ... 100 %, provided that 

a minimum value of 20 % is observed. 

Shut-off function 

This parameter can be set separately for each end position. When 

the respective configured limit value is exceeded, the shut-off 

function causes immediate travel of the actuator until reaching the set 

end position. 

When the shut-off value is set to “0”, the position is further controlled, 

even in the respective end position. 

Travel time prolongation 

This function can be used to increase the max. travel time for full 

travel. This time parameter can be set separately for each direction. 

Important 

This function can only be used with the pneumatics with the 

safety function “fail-safe”. 

Switching points for the position 

This parameter allows you to define two position limits for signaling 

(see option “Module for digital position feedback”). 

Digital output 

The alarms generated in the TZIDC positioner can be polled via the 

digital output as a collective alarm. 

The desired information can be selected via the operator panel or 

remotely via the configuration program. 

The output can be set to “active high” or “active low”, as required. 

Digital input 

For the digital input, one of the following safety options can be 

selected. You may use the operator’s panel or configuration program 

to select an option. 

- No function (default) 

- Move to 0 % position 

- Move to 100 % position 

- Hold previous position 

- disable local configuration 

- Disable local configuration and operation 

- Disable any access (no local or remote access via a PC) 

The selected function is activated once the 24 V DC signal is no 

longer applied (< 11 V DC). 

Pos: 7.7 /Überschriften/1.1.1/2-spaltig/Justageparameter @ 10mod_1176214036515_3101.doc @ 77166 

3.1.2 Adjustment parameters 

Pos: 7.8 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Justageparameter @ 10mod_1176214397515_3101.doc @ 77364 

The TZIDC positioner has a special function for automatic adjustment 

of the parameters. 

Additionally, the control parameters can be set automatically (in 

adaptive control mode) or manually to optimally adapt them to the 

process requirements. 

Tolerance band 

When reaching the tolerance band the position is considered as 

corrected. From this point on, the position is further slowly readjusted until the dead band is reached. The factory setting for this 

parameter is 0.3 %. 

Dead band (sensitivity) 

When reaching the dead band, the position is held. The factory 

setting for this parameter is 0,1 %. 

Actuator spring action 

Selection of the sensor shaft rotating sense (looking into the open 

case), if the valve is moved to the safe position by the actuator spring 

(actuator is depressurized via Y1/OUT1). 

For double-acting actuators the actuator spring action corresponds to 

pressurizing the pneumatic output (OUT2). 

Display 0 ... 100 % 

Adjusting the display (0 ... 100 %) according to the direction of action 

for opening or closing the valve. 

Pos: 7.9 /Überschriften/1.1.1/2-spaltig/Betriebsüberwachungsparameter @ 10mod_1176214071453_3101.doc @ 77187 

3.1.3 Monitoring parameters 

Pos: 7.10 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Betriebsüberwachungsparameter @ 10mod_1176214447375_3101.doc @ 77385 B 

Various functions for permanent operational monitoring are 

implemented in the TZIDC operating program. The following states 

will be detected and indicated, e.g.: 

- 4 ... 20 mA signal out of range 

- position out of the adjusted range 

- positioning time-out (adjustable time parameter) 

- position controller inactive 

- counter limits (settable in the diagnosis phase) exceeded 

While automatic commissioning is in progress, the current state is 

continuously indicated on the integrated LCD. 

During operation, the LCD shows the most important process 

variables: 

- current position (in %), 

- malfunctions, alarms, messages (as code) 

Access to extended monitoring parameters is possible via HART 

communication and the DTM. 

3.1.4 Diagnosis parameters 

Pos: 7.13 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Betrieb/Diagnoseparameter @ 10mod_1176214500906_3101.doc @ 77406 

The diagnosis parameters of the TZIDC program inform the operator 

about the operating conditions of the valve. 

From this information the operator can derive which maintenance 

works are required, and when. 

Additionally, limit values can be defined for these parameters. When 

they are exceeded, an alarm is reported. 

The following values are e.g. determined: 

- Number of movements performed by the valve 

- Total travel 

The diagnosis parameters and limit values can be called up, set, and 

reset via HART communication, using the configuration program. 

Pos: 7.14 /Überschriften/1.1/2-spaltig/Bedienpanel @ 10mod_1176214143953_3101.doc @ 77229 

3.2 Operator panel Pos: 7.15 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/Allgemein/Betrieb/Bedienpanel TZIDC-1x0 @ 10mod_1176214815500_3101.doc @ 77427 

The TZIDC positioner’s operator panel with four pushbuttons allows 

for 

- operational monitoring 

- manual control 

- configuration 

- fully automatic commissioning 

The operator panel is protected by a cover which avoids 

unauthorized access to the operating elements. 

Pos: 7.16 /======= Spaltenumbruch ======== @ 0mod_1132937966324_3101.doc @ 3831 

Pos: 7.17 /Überschriften/1.1.1/2-spaltig/Ein-Tasten-Inbetriebnahme @ 10mod_1176214193156_3101.doc @ 77250 

3.2.1 Single-button commissioning 

Pos: 7.18 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Ein-Tasten-Inbetriebnahme @ 10mod_1176214842843_3101.doc @ 77448 

Commissioning the TZIDC positioner is especially easy. The 

standard Autoadjust function for automatic adaptation of the device 

parameters can be started by simply pressing a single front panel 

button, and without knowing parameterization details. 

Depending on the selected actuator type (linear or rotary), the 

displayed zero position is automatically adapted: 

- for linear actuators counter-clockwise (CTCLOCKW) 

- for rotary actuators clockwise (CLOCKW). 

Besides this standard function, a customized “Autoadjust” function is 

available. The function is launched either via the operator’s panel or 

HART communication. 

Pos: 7.19 /Überschriften/1.1.1/2-spaltig/Anzeigen @ 10mod_1176214259859_3101.doc @ 77271 

3.2.2 Display 

Pos: 7.20 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Betrieb/Anzeigen @ 10mod_1176214873937_3101.doc @ 77469 

The information indicated by the 2-line LC display is permanently 

updated and adapted during operation, to inform the operator in an 

optimal way. 

During control operation (control with or without adaptation) the 

following TZIDC data can be called up by pressing the pushbuttons 

briefly: 

- Up button: Current setpoint (mA) 

- Down button: Temperature in device 

- Up + Down buttons: Current control deviation 

4 Communication Pos: 9.2 /==== Wechsel ein- auf zweispaltig ==== @ 0mod_1130421847171_3101.doc @ 3828 

Wechsel ein-auf zweispaltig Pos: 9.3 /Überschriften/1.1/2-spaltig/DTM @ 10mod_1176215310421_3101.doc @ 77511 

4.1 DTM Pos: 9.4 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kommunikation/DTM @ 10mod_1176215507046_3101.doc @ 77595 

The DTM (Device Type Manager) for TZIDC is based on the 

FDT/DTM technology (FDT 1.2) and can be integrated in a process 

control system or loaded in a PC with the DSV401 (SMART VISION) 

program. This allows you to work with the same user interface in the 

commissioning phase, during operation, and for service tasks for 

monitoring the device, setting parameters, and uploading data. 

Communication is based on the HART protocol. It occurs via a local 

interface connection (LKS) or in frequency-modulated mode using an 

FSK-modem connected at any chosen point of the 20 mA signal line. 

Communication has no effect on operation. Newly set parameters are 

saved in the non-volatile memory directly upon the download into the 

device, and become active immediately. 

Pos: 9.5 /Überschriften/1.1/2-spaltig/LKS-Adapter (RS-232 Schnittstellenwandler) @ 10mod_1176215338250_3101.doc @ 77532 

4.2 LKS adapter (RS-232 interface converter) Pos: 9.6 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kommunikation/LKS-Adapter (RS-232 Schnittstellenwandler) @ 10mod_1176215612828_3101.doc @ 77616 

You can easily connect your TZIDC positioner to a PC, e.g., in the 

workshop or in the commissioning phase, by using the positioner’s 

LKS adapter (LKS = local communication interface). 

An RS-232 interface converter adapts the signals on the serial PC 

port to the level of the positioner’s LKS. 

Pos: 9.7 /Überschriften/1.1/2-spaltig/FSK-Modem @ 10mod_1176215390421_3101.doc @ 77553 

4.3 FSK Modem Pos: 9.8 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Kommunikation/FSK-Modem @ 10mod_1176215656328_3101.doc @ 77637 

The FSK modem establishes a digital frequency-modulated 

communication (Frequency Shift Keying) with the TZIDC positioner. 

Tapping is possible at any chosen point of the 20 mA signal line. 

We recommend that you use an electrically isolated FSK modem. It is 

bus-compatible when used with isolating amplifiers. Even connecting 

explosion-protected field devices is possible, on condition that the 

FSK modem is run outside the hazardous area.


  • ENTERASYS A4H254-8F8T Ethernet switch
  • ENTERASYS C2RPS-CHAS2 SecureStack c2 Redundant power supply chassis
  • ENTERASYS A2H124-24 Ethernet edge switch
  • EMG LID43.03 Reference voltage source
  • EMERSON PR6426010-110+C0N021916-240 32mm Eddy Current Sensor
  • EMERSON PR6423/011-110+C0N021 Eddy Current Signal Converter
  • EMERSON VE4003S2B1 DeltaV™ M-series Traditional I/O
  • EMERSON 2500M/AI4UNIV analog input module
  • EMERSON PMCspan PMC Expansion Mezzanine
  • EMERSON PR6424/011-140 16mm Eddy Current Sensor
  • EMERSON KJ3242X1-BK1 12P4711X042 S-Series H1 Card
  • EMERSON 960132-01 FX-316 Positioning Servo Drive 230 VAC
  • EMERSON KJ4006X1-BD1 Interface Terminal Block
  • EMERSON 1C31181G01 module
  • EMERSON CE4003S2B6 I/O Termination Block
  • EMERSON KJ4001X1-CK1 40-Pin Mass Termination Block
  • EMERSON VE4012S2B1 Module
  • EMERSON KL4103X1-BA1 CHARMs Smart Logic Solver Carrier
  • EMERSON A6370D/DP Overspeed Protection Monitor
  • EMERSON P188.R2 Industrial interface module
  • EMERSON VE3008 CE3008 KJ2005X1-MQ1 12P6381X042 MQ Controller
  • EMERSON TPMC917 4MB SRAM with Battery Backup and 4 Channel RS232
  • EMERSON P152.R4 Multifunctional module
  • EMERSON DA7281520 P152 Processor board
  • EMERSON PR6423/008-110 8mm Eddy Current Sensor
  • EMERSON PR6423/000-131 8mm Eddy Current Sensor
  • EMERSON MVME61006E-0163R VMEbus Single-Board Computer
  • EMERSON Ovation 5X00453G01 Remote I/O Node Controller Module
  • EMERSON 5X00070G04 Analog input
  • EMERSON Ovation 5X00070G01 Analog Input Module
  • EMERSON Ovation 5X00790G01 Compact Controller Module
  • EMERSON 5X00846G01 HART analog output module
  • EMERSON 1C31113G01 Digital output module (5-60VDC)
  • EMERSON KJ4110X1-BA1 I/O terminal module
  • EMERSON CSI3125 A3125/022-020 Shaft-Vibration Monitor
  • EMERSON 5X00273G01 Digital output module
  • EMERSON KJ4001X1-NB1 12P3368X012 REV:E 1-Wide I/O Carrier Extender Left
  • EMERSON KJ4001X1-NA1 12P3373X012 REV:C 1-Wide I/O Carrier Extender Right
  • EMERSON A6312/06 Speed and Key Monitor
  • EMERSON KJ4001X1-BE1 8-Wide I/O Carrier
  • EMERSON KJ2005X1-MQ1 KJ2005X1-MQ2 13P0072X082 MQ Controller
  • EMERSON 5X00226G03 - Ovation™ I/O Interface Controller, Electronics Module
  • EMERSON PR6423/00R-010+CON031 Vibration sensor
  • EMERSON 9199-00002 A6120 Control Module
  • Emerson Ovation 1C31234G01 - Ovation™ 16 Channel Compact Digital Input
  • Emerson Ovation KJ3002X1-BF1 12P1732X042 Controller module
  • Emerson Ovation 5X00226G01 I/O Interface Module
  • Emerson Ovation™ Controller Model OCR1100(5X00481G04/5X00226G04)
  • Emerson Ovation 5X00499G01 Digital Input 24Vdc Single 32CH
  • Emerson Ovation 5X00500G01 32-Channel Digital Output Module
  • Emerson ovation VE4001S2T2B4 Analog output card
  • Emerson ovation 5X00501G01 5X00502G01 Ethernet link controller
  • EMERSON A6824R 9199-00098-13 Module
  • EMERSON A6140 9199-00058 Industrial Control Module
  • EMERSON 1C31194G03 Industrial Control Module
  • EMERSON DB1-1 Industrial Control Module
  • EMERSON PMC-IO-ADAPTER I/O module
  • EMERSON L0115012 L0115032 Control module
  • EMERSON PMC-IO-PROZESSOR Process control module
  • EMERSON PMC PROFINET Manage Gigabit Ethernet switches
  • EMERSON A3120022-000 CSI3120 Bearing-Vibration Monitor
  • EMERSON SE3008 KJ2005X1-SQ1 12P6383X032 Controller
  • EMERSON 1000554 Printed circuit board
  • EMERSON PR6423/002-041 Sensor module
  • EMERSON 1C31232G02 Westinghouse control module
  • Abaco TRRM940 Switch
  • Abaco SWE440A Switch
  • Abaco NETernity™ RM984RC Ethernet Switch
  • Abaco NETernity™ GBX411 Ethernet Switch
  • Abaco NETernity™ GBX25
  • Abaco NETernity SWE540A
  • Abaco CP3-GESW8-TM8 Ethernet switch
  • Abaco SWE440S Ethernet switch
  • Abaco SWE450S 100GbE 3U VPX Switch Aligned to SOSA™ Standard
  • Abaco SWE550S 100GbE 6U VPX Switch Aligned to SOSA™ Standard
  • Abaco SPR870A Wideband Digital Receiver/Exciter
  • Abaco SPR507B Serial FPDP XMC/PMC
  • Abaco ICS-1572A Transceiver Module
  • Abaco daq8580 FMV Compression System
  • Abaco VP868 FPGA Card
  • Abaco HPC2812 Rugged 6U VPX High Performance Computer with Dual Intel
  • Abaco VSR347D 3U VPX Rugged Virtual Secure Router
  • Abaco VSR8000 Fully Rugged, COTS System Secure Router
  • Abaco RES3000 Compact, Rugged Ethernet Switches
  • Abaco PMC238 Expansion Card
  • Abaco EXP238 PMC/XMC Expansion Card for XVB603 VME Single Board Computer
  • Abaco VME-REPEAT-A-L VMEbus Repeater Link
  • Abaco VME-4514A VME Analog I/O Input/Output Board
  • Abaco VME-3128A Analog I/O
  • Abaco VME-3125A analog-to-digital Conversion board
  • Abaco VME-3123A VME Analog I/O Input Boards
  • Abaco PMC239/F Analog input/output board
  • Abaco PEX431 Multi-fabric Switch
  • Abaco CPCI-100A-BP 2-slot IndustryPack carrier for 3U CompactPCI
  • Abaco PMC522 Serial Controller
  • Abaco PMC522/FP Serial Controller
  • Abaco VME-2170A Digital Output 32-bit optically isolated
  • Abaco VME-1129 Digital Input Board 128-bit high voltage
  • Abaco IP-OCTALPLUS232 Eight EIA-232 asynchronous serial ports
  • Abaco IP-DIGITAL482 Digital I/O with 48 TTL Channels
  • Abaco PMC523 16-Port Serial Controller
  • EMERSON CE4003S2B1 M-series Traditional I/O
  • EMERSON SE3008 DeltaV™ SQ Controller
  • EMERSON 1C31227G01 - Ovation™ 8 Channel Analog Input
  • EMERSON 1C31224G01 - Ovation™ 8 Channel Analog Input
  • ABB UNS0119A-P,V101 3BHE029154P3 3BHE029153R0101 Digital input
  • ABB 3BDH000050R1 AM811F Battery Module
  • ABB 3ASC25H705-7 Digital output board
  • ABB UDD406A 3BHE041465P201 control board
  • ABB 3BHE014967R0002 UNS 2880B-P,V2: COB PCB Assembled
  • ABB PPC380AE02 HIEE300885R0102 module
  • ABB NU8976A99 HIER466665R0099 Processor Module
  • ABB DIS0006 2RAA005802A0003G Digital Input Module
  • ABB Bailey IMDS003 infi 90 Digital Output Slave Module
  • ABB XO08R1-B4.0 Expand the output relay module
  • ABB VA-MC15-05 Controller module
  • ABB VA-3180-10 Controller module
  • ABB 72395-4-0399123 Excitation module
  • ABB PU516A 3BSE032402R1 Engineering Board - PCI
  • ABB 3BHE044481R0101 3BHE044477P3 PPE091A101 Module
  • ABB UCD224A102 Control unit
  • ABB SNAT603CNT SNAT 603 CNT Motor Control Board
  • ABB SNAT634PAC Drive board
  • ABB UAD149A0011 Servo controller
  • ABB UCD224A103 Industrial controller module
  • ABB 3BHE029154P3/3BHE029153R0101 UNS0119A-P,V101 Processor Module
  • ABB ARCOL 0338 ARCOL 0346 Solid-state motor starter
  • ABB ARCOL 0339 Solid-state motor controller