DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

GE350 Feeder Protection System

From:GE | Author:LIAO | Time :2025-08-16 | 30 Browse: | Share:

GENERAL SAFETY PRECAUTIONS - 350

• Failure to observe and follow the instructions provided in the equipment manual(s) 

could cause irreversible damage to the equipment and could lead to property 

damage, personal injury and/or death. 

• Before attempting to use the equipment, it is important that all danger and caution 

indicators are reviewed. 

• If the equipment is used in a manner not specified by the manufacturer or 

functions abnormally, proceed with caution. Otherwise, the protection provided by 

the equipment may be impaired and can result in Impaired operation and injury.

• Caution: Hazardous voltages can cause shock, burns or death.

• Installation/service personnel must be familiar with general device test practices, 

electrical awareness and safety precautions must be followed. 

• Before performing visual inspections, tests, or periodic maintenance on this device 

or associated circuits, isolate or disconnect all hazardous live circuits and sources 

of electric power. 

• Failure to shut equipment off prior to removing the power connections could 

expose you to dangerous voltages causing injury or death. 

• All recommended equipment that should be grounded and must have a reliable 

and un-compromised grounding path for safety purposes, protection against 

electromagnetic interference and proper device operation.

• Equipment grounds should be bonded together and connected to the facility’s 

main ground system for primary power.

• Keep all ground leads as short as possible. 

• At all times, equipment ground terminal must be grounded during device 

operation and service. 

• In addition to the safety precautions mentioned all electrical connections made 

must respect the applicable local jurisdiction electrical code.

• Before working on CTs, they must be short-circuited.

• LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 

1M. Class 1M devices are considered safe to the unaided eye. Do not view directly 

with optical instruments.

• This product uses optical electronic devices (line or point sensors) to sense arc 

flash fault conditions. It is recommended to follow proper housekeeping measures 

and establish a regularly scheduled preventive maintenance routine to ensure 

proper device operation.

• This product itself is not Personal Protective Equipment (PPE). However, it can be 

used in the computation of site-specific arc flash analysis when the arc flash 

option is ordered. If a new appropriate Hazard Reduction Category code for the 

installation is determined, the user should follow the cautions mentioned in the arc 

flash installation section.

• This guide is intended to provide protective relay application guidance to mitigate 

arc flash incident energy. This guide does not endorse energized work. This guide 

does not claim that protective relaying can totally protect personnel from the 

dangers of an arc flash. The only way to completely prevent injury from arc flash 

events is to de-energize the equipment and properly follow safe lockout/tagout 

procedures to ensure the equipment remains de-energized.

Safety words and definitions

The following symbols used in this document indicate the following conditions

Note Indicates a hazardous situation which, if not avoided, will result in death or serious 

injury.

Note Indicates a hazardous situation which, if not avoided, could result in death or serious 

injury.

Note Indicates a hazardous situation which, if not avoided, could result in minor or 

moderate injury.

Note Indicates practices not related to personal injury

Overview

The 350 is a microprocessor-based relay for primary and backup over-current protection 

of medium and low voltage distribution feeders. The relay is also suitable for providing 

over-current and backup protection for small and medium size motors, transformers, 

generators, and distribution bus-bars. The small footprint and the withdrawable option 

make the 350 relay ideal for panel mounting on either new or retrofit installations. The 

combination of proven hardware, a variety of protection and control features, and 

communications, makes the relay ideal for total feeder protection and control. Equipped 

with serial (RS485), USB, and Ethernet ports with the possibility of adding redundancy 

(IEC62439, PRP and HSR), and a wide selection of protocols such as Modbus, DNP3.0, IEC 

60870-5-103, 60870-5-104, IEC61850 GOOSE, OPC-UA, the 350 relay is the best-in-class 

for MCCs and PCCs, SCADA and inter-relay communications. The 350 relay provides 

excellent transparency with respect to power system conditions and events, through its 

four-line 20-character display, as well as the EnerVista 3 Series Setup program. 

Conveniently located LEDs provide indication of relay operation, alarm, and pickup, as well 

as breaker, and relay status.

The 350 relay provides the following key benefits:

• Withdrawable small footprint – saves on rewiring and space. (non-draw out version is 

also available)

• Multiple protection groups with the added flexibility of switching through a wide 

selection of overcurrent protection and control features.

• Fast setup (Quick Setup) menu for power-system setup and a simple overcurrent 

protection configuration.

• Large four-line LCD display, LEDs, and an easy-to-navigate keypad.

• Multiple communication protocols for simultaneous access when integrated into 

monitoring and control systems.

Description of the 350 Feeder Protection System

CPU

Relay functions are controlled by two processors: a Freescale MPC5554 32-bit 

microprocessor measures all analog signals and digital inputs and controls all output 

relays; a Freescale MPC520B 32-bit microprocessor controls all the Ethernet 

communication protocols.

Analog Input and Waveform Capture

Magnetic transformers are used to scale-down the incoming analog signals from the 

source instrument transformers. The analog signals are then passed through a 960 Hz low 

pass anti-aliasing filter. All signals are then simultaneously captured by sample and hold 

buffers to ensure there are no phase shifts. The signals are converted to digital values by a 

12-bit A/D converter before finally being passed on to the CPU for analysis.

Both current and voltage are sampled thirty-two times per power frequency cycle. These 

‘raw’ samples are scaled in software, then placed into the waveform capture buffer, thus 

emulating a fault recorder. The waveforms can be retrieved from the relay via the EnerVista 

3 Series Setup software for display and diagnostics.

Frequency

Frequency measurement is accomplished by measuring the time between zero crossings 

of the Bus VT phase A voltage. The signals are passed through a low pass filter to prevent 

false zero crossings. Sampling is synchronized to the Va-x voltage zero crossing which 

results in better co-ordination for multiple 350 relays on the same bus.

Phasors, Transients, and Harmonics

Current waveforms are processed four times every cycle with a DC Offset Filter and a 

Discrete Fourier Transform (DFT). The resulting phasors have fault current transients and 

all harmonics removed. This results in an overcurrent relay that is extremely secure and 

reliable; one that will not overreach.

Processing of AC Current Inputs

The DC Offset Filter is an infinite impulse response (IIR) digital filter, which removes the DC 

component from the asymmetrical current present at the moment a fault occurs. This is 

done for all current signals used for overcurrent protection; voltage signals bypass the DC 

Offset Filter. This filter ensures no overreach of the overcurrent protection.

The Discrete Fourier Transform (DFT) uses exactly one sample cycle to calculate a phasor 

quantity which represents the signal at the fundamental frequency; all harmonic 

components are removed. All subsequent calculations (e.g. RMS, power, etc.) are based 

upon the current and voltage phasors, such that the resulting values have no harmonic 

components.

Protection Elements

Protection elements are processed up to four times every cycle to determine if a pickup 

has occurred or a timer has expired. The protection elements use RMS current/voltage, 

based on the magnitude of the phasor. Hence, protection is impervious to both harmonics 

and DC transients.

NOTE

NOTE: Arc Flash protection elements are processed up to 8 times every cycle.

Product identification

The product identification label is located on the side panel of the 350 . This label indicates 

the product model, serial number, and date of manufacture.

Figure 2-3: 350 Product labels

The pink color text (i.e. Model, Serial Number, Instruction Manual, MFG. Date) is for 

reference only. The text can vary.

Mounting

Standard panel mount The standard panel mount and cutout dimensions are illustrated below.

CAUTION: To avoid the potential for personal injury due to fire hazards, ensure the unit is 

mounted in a safe location and/or within an appropriate enclosure.

1. Mount the collar of required depth (1.375” or 3”) to the unit (captive or non-drawout) 

using 4 screws (see above).

2. Mount the combination of unit and collar to the panel using 4 screws as shown above.

Figure 2-7: Mounting tabs (optional)

1. From the front of the panel, slide the empty case into the cutout until the bottom tab 

clicks into place (see above).

2. From the rear of the panel screw the case into the panel at the 8 screw positions 

shown above.

3. If added security is required, bend the retaining "V"tabs outward, to about 90°. These 

tabs are located on the sides of the case and appear as shown above.

The relay can now be inserted and can be panel wired.

P20 Cover (optional)

The IP20 cover minimizes potential dangers to users by preventing finger contact with 

electrical connections at the back of the 3 Series drawout units.

Attaching the cover

The steps for attaching the IP20 cover (optional) to the drawout unit are as follows:

Figure 2-13: IP20 Cover mounting - Drawout unit only

1. Place 4 custom standoffs (item#1) using the suggested tightening torque of 8lb-in in 

the following order: 

A. Remove the 2 mounting screws near letters A and C, of label ABC (item#2), and 

mount 2 standoffs.

B. Remove the 2 mounting screws near the letters B and E, of label ABCDE (item#3), 

and mount 2 standoffs.

2. Place the IP20 cover (item#4) and secure it with 4 screws (item#5) using the suggested 

tightening torque of 8lb-in.

NOTE

NOTE: Make sure the device terminals are wired before placing the cover. Use the 5 slots located 

on each side of the cover to guide the wires outside of the cover.

Retrofit kit for IP20

Before attaching the cover, remove the old labels from the device (see item#2 and item#3) 

and replace them with the new labels from the retrofit kit. Attach the cover as described in 

the previous section.

Arc flash sensors

Arc flash sensors house the fiber optics that are used to detect the arc flash. Mounting 

details depend on the sensor type (point or loop).

For detailed installation, testing and maintenance guidance for Arc Flash sensors, see GET20057 3 Series Arc Flash Application Note.

If the relay is used in the computation for reducing the Hazard Reduction Category 

code, operands for sensor failures must be assigned to an auxiliary output relay which 

must be connected into the control logic of the breaker equipment to ensure safe 

operations when the output relay is asserted. In the event of this assertion, the Hazard 

Reduction Category code cannot be maintained unless backup protection is continuing 

to maintain it.

CAUTION: This product uses optical electronic devices (line or point sensors) to sense arc flash 

fault conditions. It is recommended to follow proper housekeeping measures & 

establish a regularly scheduled preventive maintenance routine to ensure proper 

device operation. For maintenance recommendations, see GET-20057 3 Series Arc 

Flash Application Note

Arc flash sensors are available in two different configurations, point and loop. Loop sensors 

can be used with a black-coated sensor fiber extension to connect the ends of the loop 

sensor to the 350 relay through panels up to 51 mm (2 inches) thick.

Arc Flash sensor fiber is pressure sensitive and must be handled carefully to avoid 

damage. Read the following guidelines fully before proceeding.

Care must be taken when handling the Arc Flash sensor fiber, which can be damaged if 

twisted, bent, or clamped tightly during installation.

• Do not bend sensor fiber sharply, or with a radius of less than 35 mm (1.3 inches). 

Sharp bends can damage the fiber. Do not pull or tug loops of sensor fiber, as sharp 

bends may result.

• Do not clamp sensor fiber tightly during installation. Sensor fiber should be held in 

place loosely for the best long-term performance. Avoid over-tightening ties which 

may deform or break the sensor fiber.

• Do not pull or tug sensor fiber with force, as this may cause internal damage or 

separate the fiber from the cable connector.

• Do not twist the sensor fiber, as twisting can damage the fiber resulting in 

substandard performance.

• Do not attach sensor fiber directly to the bus or other live conductors.

• Avoid surface temperatures above 70 °C or 158 °F to prolong the life of the fiber.

• Secure all sensor fibers (loosely but securely) away from any moving parts.

The point sensor fiber includes a duplex connector to connect to the back of the 350 relay 

on one end, and a compressed slim connector that connects to the sensor itself on the 

other end.

Before installing the AF sensor units, ensure that all other drilling and installation is 

complete to minimize possible damage to the sensitive unit and connected sensor fiber 

cable. Choose a location for the sensor clear of any obstructions that could shield the 

sensor from arc flash light.

FASTPATH: Review the sensor fiber handling guidelines above.

Sensor fiber should be held in place loosely for the best long-term performance. Avoid 

over-tightening ties which may deform or break the sensor fiber.

General installation:

1. Choose a location for the point sensor. 

Arc flash point sensors should be installed clear of any obstructions that could shield 

the sensor from arc flash light, and less than 2m (6ft 6") from any potential arc flash 

source.

The sensor head should be pointed towards the most likely source of arc flash.

For further guidance selecting point sensor locations, see GET-20057 3 Series Arc 

Flash Application Note.

2. Remove the slim connector from the point sensor assembly.

3. Carefully route the duplex sensor fiber from the point sensor location to the back of 

the relay unit, minimizing loops and curves for the strongest possible signal. Ensure all 

sensor fiber handling precautions are followed.

The slim connecter fits through holes with a diameter of 11 mm or greater, and can be 

threaded through holes drilled in any panels between the relay and arc flash detection 

location.

NOTE

NOTE: Install protective grommets when routing sensor fiber through metal walls.

4. Mount the point sensor using either a cable tie mount or through-hole mount, as 

detailed below.

5. Reconnect the slim connector to the point sensor.

Arc flash point sensors can be installed in one of two ways, using a cable tie mount or a 

through-hole mount.

Cable tie mount:

• Requires a 2.5-mm-wide cable tie.

• Mount the sensor on a stick or similar using the cable tie, as shown in the following 

figure.

Through-hole mount

• Requires a standard or self-tapping M3 screw, and optionally an M3 washer.

• Mount the sensor through a 10 mm hole made in the surface of any mechanical 

structure inside the switchgear or on the surface of one side of the switchgear itself, 

as shown in the following figure.

Make sure there is no dirt or dust inside the point sensor or on the surface because it 

reduces the capturing efficiency of the device, increases its transmission loss, or both. If 

the point sensor is covered with dust, clean it by blowing or wiping the dust off the point 

sensor.

FASTPATH: The material of the point sensor is not affected by water-based cleaning agents, dish 

soap, or organic solvents with an alcohol (ethanol) base. Do not use solvents or solvent 

mixtures that contain acids because they can attack or dissolve the optical plastic 

material.

Before installing the AF sensor units, ensure that all other drilling and installation is 

complete to minimize possible damage to the sensitive unit and connected sensor fiber 

cable.

FASTPATH: Review the sensor fiber handling guidelines above.

Sensor fiber should be held in place loosely for the best long-term performance. Avoid 

over-tightening ties which may deform or break the sensor fiber.

FASTPATH: The loop sensor fiber can be connected directly to the 350 relay without a sensor fiber 

extension, however, care must be taken to ensure correct alignment of the loop sensor 

single connectors into the 350 light sensor input.

Installing the loop sensor fiber without an extension:

1. Plan the path of the loop sensor fiber, looping through the chamber or chambers 

requiring arc flash detection. See GET-20057 3 Series Arc Flash Application Note for 

detailed examples of loop sensor installation.

2. Ensure that both ends of the loop remain close together and can reach the 350 relay 

light sensor inputs.

3. Install the loop sensor carefully, following all sensor fiber handling guidelines.

4. Plug the single connectors into the back of the 350 relay, ensuring correct alignment 

as shown

Installing the loop sensor fiber with a sensor fiber extension:

1. Plan the path of the loop sensor fiber, looping through the chamber or chambers 

requiring arc flash detection. See GET-20057 3 Series Arc Flash Application Note for 

detailed examples of loop sensor installation.

2. Ensure that both ends of the loop remain close enough together to be reached by the 

sensor fiber extension. If needed, gently pull apart the duplex sensor fiber extension 

from the end with two single connectors, being careful not to bend the fiber with a 

radius of less than 35 mm (1.3 inches).

3. Ensure that the sensor fiber extension is long enough to reach the 350 relay from the 

bulkhead connector location.

4. Mount the bulkhead connector on the side of the chamber, following the drill hole 

dimensions provided. Note that the single bulkhead connector uses washers 11.0 mm 

(0.420 in) wide, so the drill holes must be spaced accordingly if the loop sensor path 

begins and ends in the same place.

Figure 2-26: Bulkhead connector cutout

5. Install the loop sensor carefully, following all sensor fiber handling guidelines.

6. Plug the ends of the loop sensor into the bulkhead connectors.

7. Plug the single connectors on the sensor fiber extension into the other sides of the 

bulkhead connectors, and the duplex connector into the back of the 350 relay

Wire range

Use the following guidelines when selecting wires or lugs to connect to terminal blocks 

A,B,C,D,E (Drawout case design), and terminal blocks D,E (Non-drawout case design):

• 12 AWG to 22 AWG (3.3 mm2 to 0.3 mm2): Single wire termination with/without 

9.53 mm (0.375”) maximum diameter ring terminals (#8).

• 14 AWG to 22 AWG (2.1 mm2 to 0.3 mm2): Multiple wire termination with matching 

wire sizes and stranding. Two wires maximum per circuit.

• 14 AWG to 22 AWG (2.1 mm2 to 0.3 mm2): Multiple wire termination with 9.53 mm 

(0.375”) maximum diameter ring terminals (#8). Two ring terminals maximum per 

circuit.

• Suggested wiring screw tightening torque, tighten to 12 in-lb (1.35 N-m).

• Minimum suggested temperature rating for the conductors is 75C.

Use the following guidelines when selecting wires to connect to terminal strip F (Drawout 

case design), and terminal strips A,B,C (Non-drawout case design):

• 12 AWG to 24 AWG (3.3 mm2 to 0.2 mm2)

• Suggested wiring screw tightening torque: 4.5 in-lbs (0.5 N-m)

• The uncovered communications cable shield connected to the common terminal 

should not exceed 1” (2.5 cm) for proper EMC shielding of the communications cable.

Phase sequence and transformer polarity

For correct operation of the relay features, the user must follow the instrument 

transformer polarities, shown in the Typical Wiring Diagram. Note the solid square 

markings shown with all instrument transformer connections. When the connections 

adhere to this drawing, the arrow shows the direction of power flow for positive watts and 

the positive direction of lagging vars.The phase sequence is user programmable for either 

ABC or ACB rotation.

Current inputs

The 350 relay has four (4) channels for AC current inputs, each with an isolating 

transformer. There are no internal ground connections on the current inputs. Current 

transformers with 1 to 6000 A primaries may be used.

CAUTION: Verify that the relay’s nominal input current of 1 A or 5 A matches the secondary rating 

of the connected CTs. Unmatched CTs may result in equipment damage or inadequate 

protection.

CAUTION: IMPORTANT: The phase and ground current inputs will correctly measure up to 20 

times the current input’s nominal rating. Time overcurrent curves become horizontal 

lines for currents above the 20 × CT rating. This becomes apparent if the pickup level is 

set above the nominal CT rating.

CAUTION: Before working on CTs, they MUST be short circuited.

Ground and sensitive ground CT inputs

One dedicated ground input is referred to throughout this manual as the Ground Current

or Sensitive Ground Current input. Before making ground connections, consider that the 

relay automatically calculates the neutral (residual) current from the sum of the three 

phase current phasors. The following figures show three possible ground connections (or 

three possible sensitive ground connections).

The ground input (Terminals D8 and E8) is used in conjunction with a Zero Sequence CT as 

source, or in the neutral of wye-connected source CTs. The ground current input can be 

used to polarize the neutral directional element. When using the residual connection set 

the GROUND CT PRIMARY setpoint to a value equal to the PHASE CT PRIMARY setpoint.

In cases where the relay is equipped with sensitive ground CT (terminals D8 and E8) the 

sensitive ground current input is intended for use either with a CT in a source neutral of a 

high-impedance grounded system, or on ungrounded systems. On ungrounded systems it 

is connected residually with the phase current inputs. In this case, the SENSTV GND CT 

PRIMARY setpoint should be programmed to a value equal to the PHASE CT PRIMARY 

setpoint. The sensitive ground current input can be connected to a Zero Sequence CT for 

increased sensitivity and accuracy when physically possible in the system.

NOTE

NOTE: The Sensitive Ground input must only be used on systems where the maximum ground 

current does not exceed current input specifications

Zero sequence CT installation

The various CT connections and the exact placement of a Zero Sequence CT, for ground 

fault current detection, are shown in the figure below. Twisted pair cabling on the Zero 

Sequence CT is recommended.

Figure 2-35: Zero sequence core balance (CT) installation

Voltage inputs

The 350 relay has four channels for AC voltage inputs, each with an isolating transformer. 

Voltage transformers up to a maximum 5000:1 ratio may be used. The nominal secondary 

voltage must be in the 50 to 240 V range.The three phase inputs are designated as the “bus 

voltage”. The Bus VT connections most commonly used, wye and delta (or open delta), are 

shown in the typical wiring diagram.

NOTE

NOTE: If Delta VTs are used, the zero sequence voltage (V0) and neutral/sensitive ground 

polarizing voltage (–V0) will be zero. Also, with the Delta VT connection, the phase-neutral 

voltage cannot be measured and will not be displayed.

NOTE

NOTE: The 350 relay can be applied to both metering and protection feeders with up to 550 kV 

phase-to-phase voltage. Please ensure that the selected VT ratio and VT secondary do not 

result in a primary voltage exceeding 550 kV.

The single phase input is designated as the “Aux VT Input”. The Aux VT input channel can be 

connected for either phase-neutral voltage Van, Vbn, Vcn, or for phase-phase voltage Vab, 

Vbc, Vca as shown below.

Control power

CAUTION: Control power supplied to the relay must match the installed power supply range. If the 

applied voltage does not match, damage to the unit may occur. All grounds MUST be 

connected for safe, normal operation regardless of control power supply type.

The label found on the relay specifies its order code or model number. The installed power 

supply’s operating range will be one of the following:

LO: 24 to 48 V DC (Range: 20 to 60 V DC)

HI: 125 to 250 V DC/120 to 240 V AC (Range: 84 to 250 V DC/60 to 300 V AC (50 and 60 

Hz))

CAUTION: The relay should be connected directly to the ground bus, using the shortest practical 

path. A tinned copper, braided, shielding and bonding cable should be used. As a 

minimum, 96 strands of number 34 AWG should be used. Belden catalog number 8660 

is suitable.

CAUTION: Isolate power prior to servicing.

An external switch, circuit breaker, or other protective device must be connected near to 

the equipment

Contact inputs

External contacts can be connected to the relay’s ten (10) digital inputs. These contacts are 

wet only.

The inputs can be programmed to different thresholds depending on the DC voltage (17, 

33, 84, 166).

CAUTION: Ensure correct polarity on contact input connections and do not connect any contact 

input circuits to ground or else relay hardware may be damaged.

A wet contact has one side connected to the positive terminal of an external DC power 

supply. The other side of this contact is connected to the required contact input terminal. In 

addition, the negative side of the external source must be connected to the relay’s DC 

negative rail at Terminal C11. The maximum external source voltage for this arrangement 

is 300 V DC.

Trip and Close output relays

The 350 relay is equipped with seven electromechanical output relays: two special relays 

designed for Breaker trip and close (Relay 1 “Trip”, Relay 2 “Close”), four general purpose 

relays (Auxiliary Relays 3 to 6), and a Critical Failure relay. The special purpose relays have 

fixed operating characteristics and the general purpose relays can be configured by the 

user.

Operation of the Trip and Close output relays is designed to be controlled by the state of 

the circuit breaker as monitored by a 52a or 52b contact.

• The Trip and Close relays reset after the breaker is detected in a state corresponding 

to the command. When a relay feature sends a command to one of these special 

relays, it will remain operational until the requested change of breaker state is 

confirmed by a breaker auxiliary contact and the initiating condition has reset.

• If the initiating feature resets, but the breaker does not change state, the output relay 

will be reset after a default interval of 2 seconds.

• If neither of the breaker auxiliary contacts, 52a nor 52b, is programmed to a contact 

input, the Trip Relay is de-energized after either the delay programmed in the Breaker 

Failure feature, or a default interval of 100 ms after the initiating input resets. The 

Close Relay is de-energized after 200 ms.

• If a delay is programmed for the Trip or Close contact seal-in time, then this delay is 

added to the reset time. Note that the default setting for the seal-in time is 40 ms.

Breaker monitoring (Trip and Close coil monitoring) is performed by a built-in voltage 

monitor on Form A output relays: #1 Trip, and #2 Close. The voltage monitor is connected 

across each of the two Form A contacts, and the relay effectively detects healthy current 

through the circuit. In order to do this, an external jumper must be connected between 

terminals A2 and A3 for Trip coil monitoring, or/and B4, and B5 for Close coil monitoring.

As long as the current through the Voltage Monitor is above the threshold of the trickle 

currents (see Technical Specification for Form A output relays), the circuit integrity for the 

Trip (Close) coil is effectively normal. If the Trip (Close) coil circuit gets disconnected, or if in 

general a high resistance is detected in the circuitry, a Trip (Close) alarm will be set and the 

“ALARM” and “MAINTENANCE” LEDs will be on.

Example 1: The figures below show the two different connections of the breaker trip (close) 

coil to the relay’s trip output #1 terminals (output #2 Close coil monitoring) for both no 

voltage monitoring and voltage monitoring of the trip (close) circuit integrity.

NOTE

NOTE: To monitor the trip coil circuit integrity, use the relay terminals A2 and B3 to connect the 

Trip coil, and provide a jumper between terminals A2 (optional voltage) and A3.

IRIG-B

IRIG-B is a standard time code format that allows time stamping of events to be 

synchronized among connected devices within 1 millisecond. The IRIG time code formats 

are serial, width-modulated codes which can be either DC level shift or amplitude 

modulated (AM) form. The type of form is auto-detected by the 350 relay. Third party 

equipment is available for generating the IRIG-B signal; this equipment may use a GPS 

satellite system to obtain the time reference so that devices at different geographic 

locations can also be synchronized.

The uncovered communications cable shield connected to the common terminal should 

not exceed 1” (2.5 cm) for proper EMC shielding of the communications cable.

350 Feeder Protection System

Chapter 3: Interfaces

Interfaces

There are two methods of interfacing with the 350 Feeder Protection System.

• Interfacing via the relay keypad and display.

• Interfacing via the EnerVista 3 Series Setup software.

This section provides an overview of the interfacing methods available with the 350 using 

the relay control panels and EnerVista 3 Series Setup software. For additional details on 

interface parameters (for example, settings, actual values, etc.), refer to the individual 

chapters.


  • HIMA Z7308 PLC Module
  • HIMA F60 PS01
  • TRICONEX 4409 PLC Module
  • F8651X HIMA Central module F8651X
  • F3236 DIGITAL INPUT MODULE
  • HIMA-6E-B HIMA-6E-B Large System Controller
  • F8627X HIMA communication module F8627X
  • HIMA P8403 PLC Module
  • F8628X HIMA F8628X communication module
  • F8621A HIMA communication module
  • IS200VRTDH1D GE Mark VI Printed Circuit Board
  • ABB NIAMO1 PLC Module
  • HIMAcard F8650X
  • HIMA F8652 98465266 PLC Module
  • F8652X HIMA Central module
  • HIMA 62100
  • HIMA 99-7105233 B5233-1 NSMP
  • ABBSPAD 346 C3-AA
  • ABBREF543KM127BABB
  • ABB 0-63007 M003742626
  • Abb FET3251A0P1B3C0H2M
  • ABB 3HAB8800-1
  • ABB 3AUA266001B166
  • ABB3HNM07686-1
  • ABB PQF4-3 TAS
  • Honeywell 30735863-502 - SWITCH
  • Honeywell TK-CCR014 - REDUNDANT NET INTERFACE NEW ORIGINAL FREE EXPEDITED SHIPPING/
  • Honeywell 51403165-400 - new 51403165400/
  • Honeywell318-049-001 quot100 Batteries(Japan Liion2Ah14.8Wh)INTERMEC/ PR2,PR3 P/N
  • Honeywell FC-PSU-UNI2450U - Power Supply
  • Honeywell 965-0676-010 - WARNING COMPUTER SV
  • Honeywell 51403519-160 - Module
  • Honeywell 107843 - HOUSING CARBON FILE P/N NE COND # 11438 (4)
  • Honeywell VR434VA5009-1000 - Brand new in box Condensing boiler valve DHL fast shipping
  • Honeywell SPXCDALMFX - plc new FREE EXPEDITED SHIPPING/
  • Honeywell BCM-PWS - BCM-ETH BCM-MS/TP BCM-MS/TP Network controller setFedEx or DHL
  • Honeywell YSTR12D-22/C/-2J0DFA/BE/400/T/-CM.HO.TG.SB.SM,ZS,F1,LP,/FX/,1C-BT - UNMP
  • Honeywell IWS-1603-HW - 90-250VAC 1.0A UNMP
  • Honeywell 51304386-150 - MEASUREX Factory Packed
  • Honeywell CC-IP0101 - Profibus Gateway Module
  • Honeywell CC-PFB401 - / CCPFB401 (NEW IN BOX)
  • Honeywell 50071726 - St 800 Series Pressure Transmitter Remote Diaphragm 11-42VDC
  • Honeywell 621-2150 - / 6212150 (NEW NO BOX)
  • Honeywell 80360206-001 - USED YAMATAKE CLI BOARD
  • Honeywell BMDX001A-001 - ACCURAY / BOARD BMDX001A001
  • Honeywell XCL8010A - New CPU Controller.
  • Honeywell PGM-7320 - 1PCS NEW Rae Systems MiniRAE 3000 Portable VOC Monitor#XR
  • Honeywell BK-G40 - U65 *FULL INSTALLATION* Gas Meter 3?± Inlet/Outlet Spool NEW UNUSED
  • Honeywell DM106-0-B-00-0-R-1-00000-000-E0 - DPR100 250V NSNP
  • Honeywell KFD840 - PRIMARY FLIGHT DISPLAY CORE PN: 066-01206-0104
  • Honeywell 51401914-100 - 51400996-100
  • Honeywell TK-PRS021 - Module Via FEDEX/DHL
  • Honeywell C7012A1145 - 1PC New UV Flame Detector Expedited Shipping
  • Honeywell OV210 - Baxter Bakery Oven Igition Control. For DRO. 00-616973 NEW
  • Honeywell 51304431-125 - 1PC New /51304431125 1 year warranty#XR
  • Honeywell QPP-0002 - Quad Processor Module / 5 Vdc / Massima 1.2A/24Vdc/max.25mA
  • Honeywell QPP-0002 - Quad Processor Module / 5Vdc / Max. 1.2A/24Vdc/max.25mA
  • Honeywell 8C-PCNT02 - 514543363-275 module
  • Honeywell DPCB21010002 - Tata Printed Circuit Board
  • Honeywell DPCB21010002 - Tata Printed Circuit Board Rev: 0
  • Honeywell 001649-M5T028 - Tata Printed Circuit Board Rev: 0
  • Honeywell YSTD924-(J2A)-00000-FF,W3,TP,TG,SS - NSFS
  • Honeywell XF523-A - / XF523A (NEW IN BOX)
  • Honeywell TK-PRS021 - NEW IN STOCK ship by UPS
  • Honeywell 2MLR-AC22 - " 2mlr-dbsf,2mlf-ad4s,2mlf-dc4s,2mlr-ac22 Rack"
  • Honeywell 9436610 - MEASUREX NSMP
  • Honeywell RT10A-L0N-18C12S0E - RT10A.WLAN.IN.6803.CAM.STD.GMS
  • Honeywell 51305896-200 - P:C1 Rev D Nim Modem - FAST SHIP BY Fedex
  • Honeywell TK-FTEB01 - PCL module Brand New Fast Shipping By DHL
  • Honeywell 8694500 - Measurex Control Processor Module
  • Honeywell DR4500 - Truline and DR4300 Circular Chart Recorder
  • Honeywell EC-7850-A-1122 - / EC7850A1122 (NEW IN BOX)
  • Honeywell XNX-UTAI-RNNNN - NEW Universal transmitter DHL Fast delivery
  • Honeywell SPXCDALMFX - plc new One Year Warranty #
  • Honeywell TC-RPFM01 - C200 system card brand new Fast Shipping
  • Honeywell 51196655-100 - NSMP
  • Honeywell XCL8010A - / XCL8010A (USED TESTED CLEANED)
  • Honeywell 51198801-100 - NEW CPU INTERFACE BOARD UPGRADE KIT UPIU 51306154-100
  • Honeywell 84795 - Sputtering Target 5N Al5Cu 7830x11640x13050
  • Honeywell W7704A-1004 - / W7704A1004 (USED TESTED CLEANED)
  • Honeywell RA890G1229 - FOR FSG UV Protectorelay /PL3
  • Honeywell KFS-599B - 071-01576-0101 UHF Communication Control with Mods (28V)
  • Honeywell WPC2000 - WINTRISS 9683001 WINTRISS CLUTCH/BRAKE CONTROL *NO KEYS*
  • Honeywell C7012E1112 - 1PC C7012E 1112 Burner Detector New In Box Expedited Ship #
  • Honeywell 8C-TCNTA1 - C300 system card brand new Fast Shipping
  • Honeywell ANT67A - TCAS Antenna 071-01548-0100 w/ October 2023 Repaired 8130
  • Honeywell CC-PDIS01 - PLC Module Brand New Fast Shipping FedEx or DHL
  • Honeywell R7247C1001 - 2-4SECS NSMP
  • Honeywell ALI-80A - Collins Encoding Altimeter - P/N 622-3975-011 - Tested 8130 -Serviceable
  • Honeywell 001650-M5T028 - Tata Relay Circuit Board
  • Honeywell 51196886-100 - PC BOARDS (126201 - NEW)
  • Honeywell J-HAM10 - NSNP
  • Honeywell TC-IXL062 - 1PCS module New fedex or DHL
  • Honeywell 114M4910-6 - PISTON ASSY PN NS COND 12037
  • Honeywell C7076 - 191002B Sensor Amplifier 220/240v
  • Honeywell 510STR12D21A-B77P - NSNP
  • Honeywell 51304511-200 - Module Nim Modem Via FEDEX/DHL
  • Honeywell IC-600 - Integrated Communication Unit RCZ851E 7510700-806 Removed Working
  • Honeywell TC-IAH161 - 1PC NEW REDUNDANT NET INTERFACE one year warranty#XR
  • Honeywell 2001-100-150-126-280-20-100000 - REMAN
  • Honeywell QPP-0001 - FSC QUAD PROCESSOR PACK QPP MODULE CC V1.4
  • Honeywell 30734558-001 - / 30734558001 (USED TESTED CLEANED)
  • Honeywell STD830-E1HS4AS-1-A-ADB-11C-B-21A0-00-0000 - 4500PSI NSNP
  • Honeywell 900C75-0560 - NEW HC900 Controller module FedEx DHL Fast delivery
  • Honeywell BL870 - Bezel 7014331-921 w/ October 2018 Repaired 8130
  • Honeywell STG77L-E1G000-1-A-CDC-11S-A-20A0-00-0000 - NSMP
  • Honeywell FF-SB14E12K-S2 - / FFSB14E12KS2 (USED TESTED CLEANED)
  • Honeywell 51198685-100 - "Rev. A, 140519-2-LF Power Supply Module 10A 100-240 VAC"
  • Honeywell 942-M96-M - plc new FREE EXPEDITED SHIPPING
  • Honeywell TK-IAH161 - 1PC New ANALOG INPUT TKIAH161 Expedited Shipping
  • Honeywell C7061F2001 - 1PC UV Flame Detector New In Box #
  • Honeywell 0190-20139/D - ONE Sputtering Coating Disc 4N5TI NEW
  • Honeywell 82408667-001 - NEW MEMORY BOARD ROM/RAM 82408667001
  • Honeywell C7012A1194 - NEW IN STOCK ship by UPS
  • Honeywell TK-FTEB01 - NEW IN BOX FTE BRIDGE Brand New Fast Shipping FedEx or DHL
  • Honeywell RA890G1344 - 1pc NEW Combustion Controller DHL or FedEX
  • Honeywell DH-AP-1/ - Miller 3 Workers per System 4-3/4 Ft Overall H Post Anchor
  • Honeywell TCOAV081 - NEW IN BOX ANALOG OUTPUT EXPEDITED SHIPPING
  • Honeywell W7704D1016 - Control Unit
  • Honeywell 9437710 - USED PIDP MEASUREX / 09437710-RP MODULE REV D STOCK 1603
  • Honeywell 51403165-400 - Brand new industrial computer Fast FedEx or DHL
  • Honeywell DC3200-EE-000R-240-00000-E0-0 - New DHL FastShip
  • Honeywell 51305348-100 - / 51305348100 (USED TESTED CLEANED)
  • Honeywell CC-PAIX01 - 1PCS Brand New Expedited Shipping
  • Honeywell 51305890-175 - REV B NEW
  • Honeywell XCL8010A - NEW IN STOCK ship by UPS
  • Honeywell D18-UU0000-D00000-0000-2-0000-00-E - CHART RECORDER CHART RECORDER
  • Honeywell TC-IAH161 - ANALOG INPUT NEW 1PCS