in the para. 4.2 are satisfied. However, the proof test can be performed in order to satisfy the requirement coming from the
demand rate of the Safety Instrumented Function, where the Metrix 5845C is involved.
SENSOR VERIFICATION CALIBRATION PROCEDURE
Mount the 5845C on a shaker table and verify the RMS output per table below. The table is divided according to the
different types of Sensitivity.

NOTICE
The test detailed in this paragraph shall be carried out by competent and trained personnel.
WARNING!
Maintenance may compromise the sensor. Follow the instruction listed into the user manual is mandatory
to ensure the correct operability of SIS.