maxPAC
Input/Output Subsystem
Overview
The maxPAC Input/Output System links the maxDNA Distributed Control
System to real world process control inputs and outputs. The Input/Output
system uses a compact design to provide the system with greatly enhanced
I/O capacity in relatively little space. A close relationship exists, in turn,
between this I/O system and the maxDNA Distributed Processing Unit
(DPU) which it serves.
The DPU and the I/O modules mount in an I/O chassis assembly. The
backplane in the chassis assembly provides the I/O bus connection between
the DPU and the I/O modules. It also provides the system power and field
power connections to the modules. Multiple I/O chassis that share the I/O bus
can be installed in a cabinet.
Model IOP I/O Subsystem
Cabinet
Two standard cabinet types are available for the mounting of I/O system
hardware. The cabinet is available as either a NEMA (National Electrical
Manufacturers Association) type 1 or 12 and consists of the following:
Welded steel construction
Front and Rear access
I/O mounted in front and rear of cabinet (standard)
I/O mounted in front and terminations in rear of cabinet (option)
Other mounting arrangement options are also available
Removable doors
19” rack mount rails with standard E.I.A. hole spacing
Top or bottom Cable access
Size 85 7/8” h x 24 ¾”w x 38 7/8”d
Optional Cabinet styles and sizes are also available.
The following figure shows a typical cabinet arrangement with I/O in both
the front and rear of the cabinet.
Figure 1-1. Typical Cabinet Arrangement, Front and Rear Views
Chassis Assembly
Three chassis assembly types are available for the installation of the I/O
module as follows:
IOP382 Eight-pack assembly to accommodate up to eight maxPAC I/O
modules. The DPU4F can also reside in this chassis.
IOP383 Six-pack assembly to accommodate a DPU4E or a Model 564 I/O
module in the right most position along with six maxPAC I/O modules; the
DPU4E takes up the equivalent of two maxPAC I/O module positions.
IOP381 Four-pack assembly to accommodate four maxPAC or Model 564
I/O modules.
The rack assemblies contain an I/O backplane featuring edge connectors for
I/O modules and connectors for 24V system supply and 24V and 48V loop
power supplies. Input/Output modules connect to the I/O bus through four to
eight connectors on the backplane, depending on chassis style.
The backplane also contains ribbon cable connectors to interconnect chassis
assemblies and extend the I/O bus to the maximum number of modules
supported by the DPU.
DPU Mounting
DPU4E mounts in the right most position of the six-pack chassis assembly. It
occupies the equivalent of two I/O modules. Refer to Publication 278590 for
DPU4E information. DPU4F mounts in the left most position of the eightpack chassis assembly. It occupies the equivalent of one I/O module. Refer to
Publication 278705 for DPU4F information.
I/O Modules
The I/O modules are rugged enclosed printed circuit board assemblies. The
edge connection at the rear of each module provides the interface to the
backplane and the I/O bus. System power and field power, when applicable, is
also available through this connection.
While I/O modules vary by type, they may include one or more of the
following:
A color bar on the module faceplate identifies the module type. Each
module type has a unique color.
Euro-style terminal connector blocks for field wiring; each block contains
16 connectors;
Rotary address switch;
Light Emitting Diodes (LED) for module status indication;
All the modules that require field power include a front mounted fuse
disconnect and a LED fuse status indication;
All discrete modules include front mounted LEDs for input/output logic
state;
The TC module includes front-end connectors with thermistors to measure
the junction temperature for cold junction compensation.
The I/O modules may be inserted and withdrawn safely with 24 Vdc and field
power applied.
I/O Module Types
Because of the variety of input and output ranges needed in distributed control
applications, the Model IOP I/O offers many types of easily configurable
discrete and analog I/O modules. For a list of modules, along with their
ranges and number of points per module, refer to the following tables.
Digital Input (AC/DC)*
Part Number Description
IOP330 24 Vdc common input; 16 channels
IOP334 24 Vdc isolated input; 16 channels
IOP331 48 Vdc common input; 16 channels
IOP332 120 Vac/dc isolated input; 16 channels
IOP333 240 Vac/Vdc isolated input; 16 channels
IOP350 Form C relay; 10 channels
IOP351 Form A/B relay; 16 channels
IOP335 Pulse I/O , 8 channels
*ac Voltages/currents are RMS