fuel position. Verify that linkage travel is limited by the prime mover’s fuel
control, not by the actuator stop.
Preset Rated Speed:
Set the signal generator for MPU frequency at rated speed and connect it to
terminals 5 and 6. Put the idle-rated switch in the rated position. Set the
speed trim pot, if connected, to mid-position. Observe the linkage position.
If the linkage Is at the maximum fuel position:
Slowly turn the rated speed pot counterclockwise until the linkage just
begins to move to the minimum fuel position. Start Fuel (if present) must be
adjusted to the maximum clockwise position or the actuator will not move to
maximum.
If the linkage Is at the minimum fuel position:
Slowly turn the rated speed pot clockwise until the linkage just begins to
move to the maximum fuel position.
Continue to adjust the rated speed pot very slowly in the appropriate
direction, trying to stop the linkage between the minimum and maximum fuel
stops. Because it is not possible to stop the motion, cease adjusting when
the linkage moves slowly. The rated speed reference is now set very close
to desired speed. A slight adjustment when the engine is running will
achieve the exact speed.
Preset Idle Speed:
Preset idle speed only after presetting rated speed. Set the signal generator
for the MPU frequency at idle speed. Put the idle-rated switch in the idle
pos