– Humidity acc. to DIN 40040 class F without
condensation :
● average over the year 75 %
● up to 30 days of a year 95 %
● on the other days withregard to the average of the
year, occasionnally 85 %
– Air pressure :
● operation 800 hPA ( 2000 m)
● storage 660 hPA ( 3500 m)
● Mechanical data
– degree of
protection IP 20
– housing UL94 V0
UL94 V1 for central units serie 90,
coupler 07KPxx and units ICDxx
– vibration each of three mutually
perpendicular axes 10 Hz ...57 Hz
continuous : 0.0375 mm amplitude
occasional : 0.075 mm amplitude
57 Hz ... 150 Hz
continuous : 0.5 g acceleration
occasional : 1.0 g acceleration
– shocks occasional excursion to 15 g, 11 ms,
halfsine in each of three mutually
perpendicular axes
– impact for units with a power supply > 30 VAC.
withstand According to IEC 950 : a steel sphere
test with a mass of 500 g is to fall freely
from a height of 1300 mm
● Mounting
– DIN rail 35 mm
– Screw screws Ø 4 mm (M4)
mounting
● Serial interfaces
– for connection of the RS485,
central unit to using screw terminals
the remote units
– for programming and RS232-C
setting parameter 9 pole D connector
(female)
● Termination
– on the plug-in base ECZ use 60 °C copper conductor only
Cross section :
– bus wiring terminal : twisted pair
AWG 24 (0.22 mm2
) to AWG 18 (0.8 mm2
)
– earth terminal : rigid or stranded connector
AWG 10 (5.2 mm2
)
– Others terminals :
● inputs : stranded connector
AWG 18 (0.8 mm2
) to AWG 14 (2.1 mm2
)
● outputs : stranded connector
AWG 14 (2.1 mm2
)
● power supply
AWG 14 (2.1 mm2
)
– on removable terminal 2.5 mm2 (copper N°
AWG14)
block (small section)
– on removable terminal 1.5 mm2 (copper N°
AWG16)
block (small section)
– screws tightening 7 ibs. inch (0.8 Nm)
torque (for guidance only)
● Supply connections
– 24 VDC (process and 24 VDC
power supply (-20 %, +25 %, i.e. 19.2 ... 30V)
incl. ripple
ripple factor < 5 %
– 120 VAC power supply 120 VAC
(-15%, +10%, i.e. 102 ... 132V)
50 Hz or 60 Hz (± 5 %)
– 230 VAC power supply 230 VAC
(-15%, +10%, i.e. 195.5 ... 253V)
50 Hz or 60 Hz (± 5 %)
● Voltage drops and interruptions
– DC power supply interruption time 10 ms
time interval between two
drops 1s
– AC power supply interruption time 0.5 period
time interval between two
drops 1s
● Creepage distances and clearances
according to EN 61131-2 /
IEC1131-2
● Insulation test voltages
the insulation test voltages
are according to IEC 1131-2
● Electromagnetic compatibility (EMC)
– electrostatic discharge (ESD) according to
IEC 1000-4-2
(severity level 3)
test peak voltage :
● at discharge thru air 8 kV
● at discharge
thru relay's contact 6 kV
time between two discharges > 1s
number of discharges on each
selected point 10
– radiated electromagnetic
field immunity test according to
IEC 1000-4-3
field strength 10 V/m
(severity level 3)
frequency range 27 MHz to 1000 MHz
sweep speed 1.5 x 10E-3
decade/s
– fast transient burst test (FTT) according to
IEC 1000-4-4
interference voltage for :
mains terminals 115/230 V 2 kV
mains terminals 24 V 2 kV
output terminals 24 V 1 kV
output terminals 115/230 V 2 kV
input terminals 24 V 1 kV
input terminals 115/230 V 2 kV
analogue input/output terminals 1 kV
CS 31 bus 2 kV
programming interface 0.5 kV
– surge immunity according to
IEC 1000-4-5
test voltage for
assymetric coupling common mode
power supply (115/230 VAC) 2 kV
power supply (24 VDC) 1 kV
digital inputs/outputs 1 kV
test voltage for
symetric coupling differential mode
power supply (115/230 VAC) 1 kV
power supply (24 VDC) 1 kV
digital inputs/outputs 1 kV
● ABB Procontic CS 31 system bus
The CS 31 bus is a shield twisted pair RS485
– cross 0.22 ... 0.8 mm2
(N°
AWG 24 ... N°
AWG 18)
– twists > 10 per metre
– resistance 100 /km